Sales : +91-777 804 8217
| Name of Work: \"Design, supply, installation, testing and commissioning of Renewable sources (Solar PV, Biomass) and Storage (Li-Ion and Flow batteries) integrated Smart Grid field pilots (3 nos.) under the UI-ASSIST project\". | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1.1 | Pilot 3 ( Rural Smart Grid with SPV, Storage, Biomass approximately 45km from IIT Kanpur Campus) (Total 100 kWp SPV = 70 + 30 kWp)\nSolar PV Modules for Chhabbaniwada and Bargadiyapurwa:\nSupply, installation,testing and Commissioning of Solar PV module (300-380Wp) monocrytalline or higher specifications with efficiency higher than 19.5% under standard test conditions. All modules provided with their flash sheets giving test reports of all the important parameters. Requisite certification of conversion efficiency after statistical sample testing by an MNRE approved certifying agency have to be provided by the bidder.The PV modules will conform to IEC62109 Part 1 and 2 for testing, for safety qualification or equivalent.Warranty of solar PV modules for 90% performance at 10 years, 80% at 25 years and 25 years for structures.Junction boxes with appropriate bypass diodes for each panel and cable entry will be IP65 compatible. \nincluding AJB (Array Junction Box ) 3In/1 out \n(70 KWp for Chhabaniwada + 30 KWp for Bargadiyapurwa) | Item1 | 1 | Set |
| 2 | 2.01 | Inverter for Bargadiyapurwa:\nHybrid Inverter for Bargadiyapurwa:\nSupply, installation,testing & commissioning of 50kW, 415V Three phase hybrid Inverter, IP 65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, ac power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. Should have remote control and power scheduling & limiting capability using software, such as SCADA. | Item2 | 1 | No. |
| 3 | 2.02 | Grid Tie (50kW) String Inverters for Bargadiyapurwa:\nSupply, installation, testing & commissioning of 50kW, 415V Three phase grid tie Inverter (with unit of 10kW) of 50kW capacity, IP 65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, ac power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications.\nGrid Tie string Inverter 10 KW: 5 No. | Item3 | 5 | No. |
| 4 | 3.01 | Inverters for Chhabbaniwada\nHybrid Inverter for Chhabbaniwada:\nSupply, installation, testing & commissioning of 70kW, 415V Three phase hybrid Inverter, IP 65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, ac power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. Should have remote control and power scheduling & limiting capability using software, such as SCADA. | Item4 | 1 | No. |
| 5 | 3.02 | Grid Tie Innverter for Chhabbaniwada:\nSupply, installation, testing & commissioning of 70kW, 415V Three phase grid tie Inverter (with minimum unit of 10kW) of 50kW capacity, IP 65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, ac power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications.\nGrid Tie Inverter, 70kW (with 10kW units): 7 No. | Item5 | 7 | No. |
| 6 | 4 | Li-ion Battery for Chhabbaniwada and Bargadiyapurwa:\nSupply, installation, testing & commissioning of 50 kw capacity, with net usable output of 100kWh, around 500V, Li-ion Battery Bank with BMS (Battery Management System), minimum 6000 cycle life on 80% DOD, @0.2C Charge and 0.2 Discharge, CE/UL certified, protection class IP55, Wi-Fi/RS485 and ethernet compatible and capable of integrating with SCADA as per the tender specifications. \nNote: The cost also included the mounting arrangement for battery bank. | Item6 | 2 | Set |
| 7 | 5 | Hybrid Biomass System:\nSupply, installation,testing & commissioning of Hybrid type Biomass unit - 30 kW capable of working on animal waste, agricultral waste, wooden palats and plastic waste and its integration with the smart grid network having following specifications.\n1 Mixing tank with stirrer-Capacity to hold 20 cu.m\n2 Slurry feeding tank-Capacity to hold 5 cu.m\n3 BIOGAS DIGESTER (WITH FLOATING DRUM ON TOP) (Type–KVIC Floating drum type)\n4 Digester slurry evacuation tank with pump capacity to hold 40cu.m\n5 Gas supply line -200m gas pipe line\n6 Biogas Flow Meter\n7 Desulferization Unit-20 cu.m/hour capacity\n8 Pressure Relief Valve\n9 Gas Stoves\n10 Balloon PVC fabric-100 cu.m capacity\n11 Four Strokes, naturally aspirated engine operating at 1500 rpm rated for prime duty compirising of (30kW)\n12 Three-phase power meter\n13 Electrical works upto Change over switch, Mixer, Blower\n14 Balloon, Engine & Scrubber platform\n15 Animal waste separator (Solid Liquid Separator)-Capacity 2 cum slurry/hour | Item7 | 1 | Set |
| 8 | 5.01 | Synchronising Control Panel of rating 3 phase, 415V, 63 Amp with inbuilt logic controller for integration with the existing SCADA system. The panel shall be with RS485,wifi/ethernet communication facility. Protection class of the panel shall be IP 54. | Item8 | 1 | Set |
| 9 | 5.02 | It shall contain all necessary required sensors, transducers and internal control wiring for control & command facility to the various components of the Biomass system upto the synchronising control panel. | Item9 | 1 | Set |
| 10 | 5.03 | The associated civil works for foundation, structure and any brick work for commssioning of the Biomass system shall be included in the quoted price. | Item10 | 2 | Cum |
| 11 | 6 | Structure for Solar Panel modules of Chhabbaniwada and Bargadiyapurwa:\nDesign, Supply & installation of Module Mounting Structure (MMS) for 70 kWp +30 KWp with GI 250 grade (stands) and GI 350 (cross arms) grade material. \n(70 KWp for Chhabaniwada + 30 KWp for Bargadiyapurwa). \nThis will include the PCC foundation( M30 grade concrete) and GI framework for moounting the solar panels as per the detailed specifications. The bidder shall provide the STAAD report for mounting arrangement suitable to sustain 170 KMPH wind speed. | Item11 | 1 | Set |
| 12 | 7 | PCC (M20 Grade Concrete) foundation work for the Solar PV mounting structure, ACDB panels, Inverters and other equipments as per the approved design and as per specifications of the tender. | Item12 | 12 | Cum |
| 13 | 8 | Three Phase LTCT meter with CTs: for Chhabbaniwada and Bargadiyapurwa\nSupply, installation, testing & commissioning of Energy meter (3P), specs -\n• Type- 3 phase 4 wire LTCT operated smart energy meter\n• Accuracy class- 0.5s\n• Energy parameter- import & export energy\n• Operating voltage- 3x 240V single phase, +/- 10%\n• Operating current- 5A\n• Frequency- 50Hz +/- 5%\n• Communication Protocol- DLMS compliance as per IS 15959, IS16444, IPv6\n• Communication Options- Optical Port/ RS485/ RS232/ Ethernet/ Wi-Fi/ GSM, compatibility for SCADA and AMI integration\n• Internal battery- yes: for power fail mode display operation\n• Standards- As per IS 16444, IEC 62052-11, IEC 62053-22, 62053-24, 62052-31, IEC 60060-1\n• Power consumption, accuracy limit, impulse voltage, construction requirements, resistance to heat & fire, climatic influence, electromagnetic compatibility (EMC)- As per above mentioned Standards\n• Security Policy- data access: as per DLMS/ COSEM server\n* Should be capable of storing 45 days of 15 minutes consumption data | Item13 | 30 | No. |
| 14 | 9 | Single Phase Smart Meters for Chhabbaniwada and Bargadiyapurwa\nSupply, installation, testing & commissioning of Energy meter (1P), with minimum specifications mentioned below.\ni) Meters should support 4 quadrant measurement of power(Import/Export), with open protocols like DLMS, COSEM, IS16444, \nii) two way communications along with remote connect/disconnect of power supply.\niii) Should support internal communication interface for Data Concentrator Unit (DCU) / Headend System (HES) and HAN device.\niv) Should avail port for local communication\nv) Should be capable of storing 45 days of 15 minutes consumption data\nvi) Should record billing, load survey, event & tampers, instantaneous and demand parameters\nvii) Should provide feature for firmware upgrade, tariff configuration, load limit setting, tamper reset, MD (Maximum Demand) reset and time set transaction. These features should also be possible to realize remotely.\nviii) Should have load limiting provision with audible alarm\nix) Should have capability to communicate over RF. Should have compatibility for SCADA and AMI integration\nx) These single phase smart meters may communicate directly to the Data Concentrator Unit (DCU) and can be used to collect data from multiple meters (hopping) which can be sent to the Head End System (HES) via DCU.\n• Internal battery- yes: for power fail mode display operation | Item14 | 200 | No. |
| 15 | 10 | Data Concentrator Unit (DCU): \ni) minimum number of 32 nodes can be handled\nii) In built memory (SD card)\niii) connectivity to Device (Smart Meter) : RF Mesh\niv) Connectivity with Edge DCU : RF Mesh \nv) Should support multiple smart meters over RS485 and RF network both\nvi) Push/Pull mode of operation, remote firmware upgrade and configuration of device\nvii) Support group data collection by single command\nviii) Auto RTC sync with HES time\nix) IP 54 insulating encased meter and protective Class II\nx) Password protection for optical communication; authenticated, password-protected transactions and encryption for RF mesh (Sub-GHz 865-867 ISM Band), GPRS and RS-485 communication.\nNote: Repeators should also be provided as per requirement at the installation site. The cost of repeaters to be included in this item.\n | Item15 | 20 | No. |
| 16 | 11 | Edge Data Concentrator Unit (DCU): \ni) minimum number of 32 nodes can be handled\nii) In built memory (SD card)\niii) connectivity to Device (Smart Meters and DCU) : RF Mesh\niv) Connectivity with switch at village smart control room : optical fibre.\nv) Should support multiple smart meters over RS485 and RF network both\nvi) Push/Pull mode of operation, remote firmware upgrade and configuration of device\nvii) Support group data collection by single command\nviii) Auto RTC sync with HES time\nix) IP 54 insulating encased meter and protective Class II\nx) Password protection for optical communication; authenticated, password-protected transactions and encryption for RF mesh (Sub-GHz 865-867 ISM Band), GPRS and RS-485 communication.\n\n | Item16 | 2 | No. |
| 17 | 12 | Ethernet Switch with fibre ports and GPRS uplink\ni) minimum number of 24 ports (20 ethernet + 4 foptical fibre) \nii) In built memory (SD card)\niii) connectivity to edge DCU and other devices: Optical fibre and ethernet\niv) Connectivity between two ethernet switches (one at each village hamlet control rooms): Single Mode Fiber Optic\nFrom Ethernet switch to Smart Grid Control Centre at IIT Kanpur via GPRS.\nconnectivity to HES at local village hamlet control rooms (both village meter databases need to be in sync) : Ethernet \nix) IP54 insulating and protective Class II\nx) Password protection.\n\n | Item17 | 2 | No. |
| 18 | 13.01 | Synchronizing Panel cum ACDB for Chhabbaniwada:\nSupply, installation, testing & commissioning of ACDB panel with 4 nos. incomer TPN MCCB/MCB of each of rating 100 A(Grid), 63A (interconnceting grid), 160A (Battery) & 160A (solar PV) each and 8 nos. outgoing feeders each of capacity 100A TPN MCCB (2 no. (1W+1S), 63A TPN MCB (4 no. (3W+1S)) and 5-32 Amp TPN MCB (2 nos.(1W+1S)). The panels shall be with the relays, internal control wiring, communication based on RS485, ethernet, wifi and compatible for mounting smart meters for all incomers & outgoing feeders for working as per the logic/algorithm as per the specification of the tender. It shall be integratable with SCADA, AMI & ADMS. The scope includes all the hardwares and softwares neccessary for above integration as per specification. Protection Class: IP54\nMicroprocessor controlled syncronising panel with controller | Item18 | 1 | Nos. |
| 19 | 13.02 | Synchronizing Panel cum ACDB for Bargadiyapurwa:\nSupply, installation, testing & commissioning of ACDB panel with 5 nos. incomer TPN MCCB/MCB of each of rating 100A, 100A, 63A, 40A & 40A each and 9 nos. outgoing feeders each of capacity 100A TPN MCCB (3 no. (2W+1S), 63A TPN MCB (2 no. (1W+1S)) and 5-32 Amp TPN MCB (4 nos.(2W+2S)). The panels shall be with the relays, internal control wiring, communication based on RS485, ethernet, wifi and compatible for mounting smart meters for all incomers& outgoing feeders for working as per the logic/algorithm as per the specification of the tender. The scope includes all the hardwares and softwares neccessary for above integration as per specification.Protection Class: IP54\nMicroprocessor controlled syncronising panel with controller | Item19 | 1 | Nos. |
| 20 | 14 | Supply, installation, testing & commissioning of GPRS based switch / router (Remote Monitoring Unit) | Item20 | 2 | Nos. |
| 21 | 15.01 | Field ACDB panel of Solar System for Chhabbaniwada \nSupply, installation, testing & commissioning of Microprocessor based controlled synchronising panel with controller ACDB panel with 7 nos. incomer TPN MCCB/MCB of each of rating 100A, 100A, 63A, 40A & 40A each and 2 nos. outgoing feeders each of capacity 160A TPN MCCB (2 no. (1W+1S)). The panels shall be with the relays, internal control wiring, communication based on RS485, ethernet, Wi-Fi and compatible for mounting smart meters for all incomers& outgoing feeders for working as per the logic/algorithm as per the specification of the tender. The scope includes all the hardware, and necessary software required for above integration as per specification. Protection Class: IP54\n | Item21 | 1 | No.s |
| 22 | 15.02 | Field ACDB panel of Solar System for Bargadiyapurwa \nSupply, installation, testing & commissioning of Microprocessor based controlled synchronising panel with controller ACDB panel with 3 nos. incomer TPN MCCB/MCB of each of rating 100A, 100A, 63A, 40A & 40A each and 2 nos. outgoing feeders each of capacity 63A TPN MCCB (2 no. (1W+1S)). The panels shall be with the relays, internal control wiring, communication based on RS485, ethernet, Wi-Fi and compatible for mounting smart meters for all incomers& outgoing feeders for working as per the logic/algorithm as per the specification of the tender. The scope includes all the hardware, and necessary software required for above integration as per specification. Protection Class: IP54 | Item22 | 1 | No.s |
| 23 | 16.01 | Single Mode optical fibre cable:\nDirect Burial Armoured Optical Fiber Cable:\nSupplying and laying of optical fiber cables including termination at both ends in Wall/Rack mount LIU. Laying of underground cable should be in 1m deep trench and the cable should be laid in HDPE pipe and lined with brick and sand. Cable markers should be put at every 30m and turns. | Item23 | 2000 | mtr. |
| 24 | 16.02 | Communication Cable\nRS 485 Communication Cable 2 Pair Twisted Armoured Cable Cu | Item24 | 100 | mtr. |
| 25 | 17.01 | Supply and laying of AYFY, XLPE insulated cable 1100 V of 4Cx6 sq.mm, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item25 | 2000 | mtr. |
| 26 | 17.02 | Supply and laying of AYFY, XLPE insulated cable 1100 V of 3½Cx70 sq.mm, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item26 | 100 | mtr. |
| 27 | 17.03 | Supply and laying of AYFY, XLPE insulated cable 1100 V of 3½Cx120 sq.mm, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item27 | 1200 | mtr. |
| 28 | 17.04 | Supply and laying of Copper Cable (AC), 1100 V armoured, PVC insulated of 4Cx16 sq. mm, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item28 | 200 | mtr. |
| 29 | 17.05 | DC Copper Screened Cable, PVC insulated 1100 V of 1Cx16 sq. mm, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item29 | 200 | mtr. |
| 30 | 17.06 | DC Copper Screened Cable, PVC insulated 1100 V of 1Cx70 sq. mm, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item30 | 50 | mtr. |
| 31 | 17.07 | 4Cx6 sq. mm Al, 1100 V, PVC insulated unarmoured cable for street lighting, including end termination with brass compression gland and aluminium lugs of suitable lugs | Item31 | 1500 | mtr. |
| 32 | 17.08 | Cable for submersible pumps\nFlexible 3Cx6sq.mm Cu, 1100 V, PVC insulated screened cable | Item32 | 100 | mtr. |
| 33 | 18.01 | HDPE Pipe: HDPE Pipe with accessories 50 mm | Item33 | 3000 | mtr. |
| 34 | 18.02 | HDPE Pipe with accessories 100 mm | Item34 | 1000 | mtr. |
| 35 | 19.01 | Pyranometer: Pyranometers (Operatig Temp:-40 to 80 deg Celsius) Spectral Response:0.31 to 2.8 microns,Sensitivity:7-14 microvolt/w/Sq.m Time response(95%):max 15sec Non linearity: ±0.5% Tilt Error: ±0.5% Input power:230VAC Non stability: Max ±0.8% | Item35 | 1 | set |
| 36 | 19.02 | Pyrheliometer: Pyrheliometers (Operating Temp:-40 to 80 deg Celsius) Spectral Response: 200 to 4000 nm, Sensitivity:7-14 microvolt/w/Sq.m Time response(< 5s), Non linearity: ±0.2% Input power:230VAC. | Item36 | 1 | set |
| 37 | 19.03 | Anemometer: As per the tender document | Item37 | 1 | set |
| 38 | 19.04 | Sun Tracker\nWe require Sun Tracker with latest Technology. It should be suitable for above mention Pyranometer and Pyrheliometer. The System should be with integrated GPS for automatic configuration of Location and time data. The inbuilt GPS should periodically and regularly update the time data to correct internal Clock of the system. The Instrument should be levelled easily during Installation with the help of the bubble leveler on the top of the Instrument. The Instrument should be made of rugged and distinctive cast aluminum housing and supplied with tripod and levelling feet, azimuth adjustment and provision for tie down bolts, Necessary mounting structure with zenith adjustment for mounting Pyrheliometer should be included.\n | Item38 | 1 | set |
| 39 | 19.05 | Data Logger/Data Acquisition System\n\nData Logger should be user programmable and low-powered unit which should be able to measure sensors, drives direct communication and telecommunications, analyzes data, controls external devices, and stores data and programs in onboard, non-volatile storage as well as should be having option for memory expansion using memory card. Logger should be having a battery-backed clock assures accurate timekeeping. The onboard, C or BASIC-like programming language which is easy to understand and supports data processing and analysis routines.\n\nUser should be able to connect with logger via web browser directly for configuration or data collection; Logger should be operational in extreme environments with a standard operating range of -40° to +70°C. User can connect around 10 to 15 devices at a time to the Data Logger.\n | Item39 | 1 | Set |
| 40 | 20.01 | Submersible Pumps for Chhabbaniwada and Bargadiyapurwa\n2HP independent BLDC solar pumps with solar panels of capacity 5kW each including their mounting structures, foundation,wiring, earthing, lighting arrestors, GPRS based energy meter and charge controller etc. complete in all respect as per specification.\n | Item40 | 2 | No. |
| 41 | 20.02 | Solar Water Pumps for Chhabbaniwada and Bargadiyapurwa\n5HP independent BLDC solar pumps with solar panels of capacity 5kW each including their mounting structures, foundation,wiring, earthing, lighting arrestors, GPRS based energy meter and charge controller etc. complete in all respect as per specification. \nDCDB: DC Distribution Box (1x18Module) with Fuse holders & DC SPD\n Supply, installation,testing and commissioning of 430V LA \nNote: The solar PV panels shall be from the approved make list. | Item41 | 10 | Set |
| 42 | 21 | GPS Master clock at both control room (Chhbbaniwada and Bargadiyapurwa)\nAlongwith Antenna & 30 mt antenna Cable. \n01 no. NTP/SNTP port output \n1 PPS \nRS232/RS485 port \nPower supply: 90-260V AC \n2x20 LCD display | Item42 | 2 | No. |
| 43 | 22 | GIS Mapping\nGIS mapping of all the 3 pilots should be carried out using standard open source software upto the consumer smart meter level.\nThis should essentially cover starting from distribution transformer to the consumer points covering substation equipments, LT poles, solar pumps, and street lights. | Item43 | 1 | lot |
| 44 | 23 | Communication and software for of data from all the 3 field pilots to the local control room and also to the Smart Grid control Centre at IIT Kanpur and local billing application etc | Item44 | 2 | No. |
| 45 | 24.01 | Desktop Computers for both hamlets with following minimum configuration.\nOne high end desktop\nIntel Core i7 (6 Cores/12MB/12T/up to 4.6 GHz/65W) Processor \n16GB (1x16GB) 2666MHz DDR4 \n3.5 inch 2TB (2x1TB) 7200rpm SATA Hard Disk Drive \nMonitor 24” Full HD \n8x DVD+/-RW 9.5mm Optical Disk Drive \nWired Mouse / Wired Keyboard \nWindows 10 Pro (64bit) English | Item45 | 1 | No. |
| 46 | 24.02 | Desktop Computers for both hamlets with following minimum configuration.\nTwo desktop computers with corei5, 8GB, 1TB HDD storage\nIntel Core i5\n16GB (1x8GB) 2666MHz DDR4 \n3.5 inch 1TB 7200rpm SATA Hard Disk Drive \nMonitor 22” Full HD \n8x DVD+/-RW 9.5mm Optical Disk Drive \nWired Mouse / Wired Keyboard \nWindows 10 Home basic (64bit) English\n | Item46 | 2 | No. |
| 47 | 25 | Inkjet Printers with tank system for both hamlets with Print, Scan, Copy functionality\nMinimum Ink Droplet Volume: 3 pl\nPrinter Language: ESC / P-R\nPrint Direction: Bi-directional printing, Uni-directional printing\nNozzle Configuration:180 x 1 nozzles Black, 59 x 1 nozzles per colour (Cyan, Magenta, Yellow)\nMaximum Resolution: 5760 x 1440 dpi (with Variable-Sized Droplet Technology)\nAutomatic 2-sided Printing: Yes | Item47 | 2 | No. |
| 48 | 26 | Cat-6 Cable | Item48 | 500 | mtr. |
| 49 | 27.01 | NVR 32 channel\nSupply, Installation, Testing and Commissioning of Networked Video Recorder for 32 IP Camera inputs which shall support upto 5 MP recording resolution, min. 32 TB inbuilt capability to accomodate surveillance grade SATA hard Disk drives, multiple resolution recording options, shall have BNC, HDMI & VGA outputs, The Unit shall have 10 /100 /1000 Mbps self-adaptive Ethernet interface through RJ-45 port. The unit shall have 16 alarm inputs and 4 Alarm Outputs. The NVR shall have, USB interface, RS-232 interface & RTs-485 interface . The NVR unit shall support 2 way Audio for atleast single Channel. | Item49 | 1 | No. |
| 50 | 27.02 | Night vision bullet camera with H.265 / H.264 / MJPEG video compression\n1/3\" Progressive scan outdoor applications, ONVIF compilant with ICR, POE compliant, having sensitivity upto 0.01lux at F1.2, the Camera be able to generate real time video at the resolution of 1280x960 at 25fps (PAL), 2.8~12mm Varifocal Lens, IP66 rated enclosure, H.265/MJPEG compression, dual-stream, DC12V & PoE, Digital Wide Dynamic range, 3D digital noise reduction, Back Light Compensation, IR illumination up to 20m, On-board memory storage card slot (up to 64GB), Vandal proof. The camera shall have important image settings like , brightness, contrast, sharpeness, saturation etc & shall be adjustable through client software or web browser. The Camera shall trigger the alarm on the critical events like Motion detection, Tampering alarm, Network disconnect, IP address confict, Storage full , Storage error etc. | Item50 | 5 | No. |
| 51 | 27.03 | Supply, Installatin, Testing and Commissioning of 22\" LED High resolution, High contrast ratio Color LED Monitor for CCTV system. | Item51 | 1 | No. |
| 52 | 28.01 | Construction of Control Rooms at Chhaba Niwada & Bargadiyapurwa, and Processing Unit Building for Indo US Project .\nINTERNAL WIRING\nPoint Wiring: Wiring for light point/fan point/exhaust fan point/call bell point with 1.5 Sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate,suitable GI box and earthing the point with 1.5 Sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.\nGroup A | Item52 | 110 | Point |
| 53 | 28.02 | Twin Control Point wiring in STEEL conduit, with modular type switch :-\nWiring for twin control light point with 1.5 Sq.Mm FRLS PVC insulated copper conductor single core cable in surface/recessed steel conduit, 2 way modular switch, modular plate,suitable GI box and earthing the point with 1.5 Sqmm FRLS PVC insulated copper conductor single core cable etc. as required. | Item53 | 10 | Point |
| 54 | 28.03 | Power plug wiring in STEEL conduit (2 x 4 Sq.Mm.) :-\nWiring for light /power plug with 2 x 4 Sq.Mm. FRLS PVC insulated, copper conductor single core cable in surface / recessed steel conduit along with 1 no. 4 Sq.Mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. | Item54 | 400 | mtr |
| 55 | 28.04 | Circuit / Sub main wiring in Steel conduit :-\nWiring for circuit / submain wiring alongwith earth wire with the following sizes of PVC insulated, copper conductor single core cable in surface/ recessed steel conduit as required. \n2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. | Item55 | 400 | mtr |
| 56 | 28.05 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of PVC insulated, copper conductor single core cable in surface/ recessed steel conduit as required. \n2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. | Item56 | 400 | mtr |
| 57 | 28.06 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of PVC insulated, copper conductor single core cable in surface/ recessed steel conduit as required. \n2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire | Item57 | 10 | mtr |
| 58 | 28.07 | Supply and fixing of following sizes of steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (20 mm) | Item58 | 200 | M |
| 59 | 28.08 | Supply and fixing of following sizes of steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (25 mm) | Item59 | 400 | M |
| 60 | 28.09 | Supply and fixing of following sizes of steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (32 mm) | Item60 | 400 | M |
| 61 | 28.1 | Supply and fixing of suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps. modular switch, connection etc. as required. | Item61 | 50 | Each |
| 62 | 28.11 | S/F power plug point modular type accessories :-\nSupply and fixing of suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps. modular switch, connection etc. as required. | Item62 | 20 | Each |
| 63 | 28.12 | S/F modular type electronic fan regulator :-\nSupply and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. | Item63 | 18 | Each |
| 64 | 28.13 | S/F modular type blanking plate :-\nSupply and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. | Item64 | 20 | Each |
| 65 | 29.01 | Supplying and fixing 20 A, 240 volts, SPN industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. | Item65 | 5 | Each |
| 66 | 29.02 | Supplying and fixing 5 amps. to 32 amps. rating, 240/415 V, 10kA, \"C\" curve, miniature circuit breaker (MCB) suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole | Item66 | 40 | Each |
| 67 | 29.03 | Supplying & fixing single pole, blanking plate in the existing MCB DB complete etc. as required. | Item67 | 20 | Each |
| 68 | 29.04 | Supplying and fixing following way VTP&N MCB distribution board of steel sheet for 415 volts,on surface /recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators). 6 way (4 + 18), Double door | Item68 | 2 | Each |
| 69 | 29.05 | Supplying and fixing following way VTP&N MCB distribution board of steel sheet for 415 volts,on surface /recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators). 8 way (4 + 24), Double door | Item69 | 1 | Each |
| 70 | 29.06 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.(63 Amps) | Item70 | 3 | Each |
| 71 | 29.07 | Supplying and fixing 30 A, 415 volts, TPN industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 amps “C” curve, TP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. | Item71 | 2 | Each |
| 72 | 30.01 | LIGHTNING PROTECTION AND EARTHING\nEarthing with G.I. earth pipe 4.5 metre long, 40 mm dia\nincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. | Item72 | 20 | each |
| 73 | 30.02 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | Item73 | 3 | set |
| 74 | 30.03 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm\nthick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | Item74 | 5 | set |
| 75 | 30.04 | Providing and fixing 25mm x 5 mm G.I strip on surface or in recess for connections etc. as required. | Item75 | 300 | meter |
| 76 | 30.05 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | Item76 | 400 | meter |
| 77 | 30.06 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. | Item77 | 25 | Nos |
| 78 | 30.07 | Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. | Item78 | 3 | Nos |
| 79 | 30.08 | Jointing copper / G.I. tape (with another copper/ G I tape, baseof the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. | Item79 | 50 | Nos |
| 80 | 30.09 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | Item80 | 150 | meter |
| 81 | 30.1 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | Item81 | 50 | meter |
| 82 | 30.11 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | Item82 | 50 | meter |
| 83 | 30.12 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | Item83 | 50 | meter |
| 84 | 31.01 | INTERNAL LIGHTING FIXTURES & FANS\nLIGHTING FIXTURES & FANS\nSupply, installation, testing & commissioning of 20W LED Batten surface mounting luminarire with high effciency PMMA diffuser including all necessary accessories complete. | Item84 | 80 | Nos |
| 85 | 31.02 | Supply, installation, testing & commissioning of 5-8W LED 6500K (300-400MM.) Wall/Surface mounted Light | Item85 | 20 | No |
| 86 | 31.03 | Supply, installation, testing & commissioning of 12W LED wall Bracket light fixture with glass to give glare free light | Item86 | 12 | No |
| 87 | 31.04 | Supply and installation of surface mounted Round 12 W LED down lighter in powder coated white finish with integrated electronic driver, including all required mounting accessories complete. | Item87 | 10 | No |
| 88 | 31.05 | Supply, installation, testing & commissioning of 9W LED IP54 bulkhead luminaire with opal diffuser Wall/Surface mounted Light | Item88 | 6 | Each |
| 89 | 31.06 | Supply , Installation,Testing and Commissioning OF CEILING & EXHAUST FANS\nSupply , Installation,Testing and Commissioning of AC 230/250 volts, 50 HZ ceiling fan with standard down rod, blades, 2 nos. caps & regulator etc. ISI marked complete as required.\n600 mm sweep 5-star\n | Item89 | 3 | No.s |
| 90 | 31.07 | Supply, Installation,Testing and Commissioning OF CEILING & EXHAUST FANS\nSupply, Installation,Testing and Commissioning of AC 230/250 volts, 50 HZ ceiling fan with standard down rod, blades, 2 nos. caps & regulator etc. ISI marked complete as required.\n1200 mm sweep, 5-star\n | Item90 | 18 | No.s |
| 91 | 31.08 | Supply, Installation,Testing and Commissioning of AC 230/250 volts, 50 HZ exhaust fan with louvers / shutters including providing nuts, bolts, mounting frame and other accessories etc. complete \n250 mm sweep 1250 rpm | Item91 | 16 | No.s |
| 92 | 31.09 | S/F of hexagonal fan box with hexagonal side of approx. 80 mm.in length fabricated from 14 SWG M.S. sheet incorporating with 10 mm. dia. M.S. round bar duly bent for supporting fan ha nger painted with red oxide and screwing arrangement with wiring conduit laid in the R.C.C. roof before concreting along with supply of all materials including fan hook, labour, T&P etc. for proper completion of work. | Item92 | 21 | No.s |
| 93 | 31.1 | MISCELLANEOUS ITEMS\nSupplying, installation, testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10 Amp, for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required. | Item93 | 2 | Each |
| 94 | 32.01 | Supplying, installation, testing & commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & Off of street lights at sun set & sun rise or twilight (Auto ON, Auto Off, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. \n3 output (1 output per phase) and suitable for three phase supply | Item94 | 2 | Each |
| 95 | 32.02 | Providing and fixing M.V. danger notice plate of 200mmx150mm made of mild steel, atleast 2mm thick and vitreous enamelled white on both sides and with inscription single red colour on FRLSont side as required. | Item95 | 4 | Each |
| 96 | 32.03 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete.\n250 mm. dia. RCC Pipes | Item96 | 30 | MTRS |
| 97 | 32.04 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. | Item97 | 25 | Each |
| 98 | 33.01 | L.T. PANEL AND DISTRIBUTION BOARD\nM V SWITCHGEAR\nNote:All LT Panels (Switch boards), Sub Panels shall be Validated Design as per the standards IEC 61439-1/2. The Panels and the associated equipment including switchgear, control gear, Busbar supports, Busbar orientation, Busbar links etc shall be identical in construction to the assembly which has undergone the total type test. • The tottaly type tested designs of the switchboards shall be proven design from switchgear manufacturer (OEM)• All Switch gears shall conforms Ics= 100% Icu as per IEC 60947-2• Switchboards shall have a short circuit level of minimum of 50 KA withstand. The enclosures shall be designed to take care of normal stress as well as abnormal electro-mechanical stress due to short circuit conditions. Switchboards shall have Rated Impulse withstand voltage of 12kv.• Switchboards must have mechanical impact IK10 tested• Busbars shall be made of high conductivity, and high strength Aluminium E91 grade. Busbar shall be suitable to withstand the stresses of fault level as specified in schedule of quantities. Degree of Protection of Enclosures shall be IEC60529.\n\nGA drawings shall be got approved from Engineer in charge before fabrication.The panel shalls be inspected by Engineer In charge or their authorised person in their manufacturing plant. | Item98 | 3 | No.s |
| 99 | 33.02 | Building PANEL\nSupply, Installation, Testing & Commissioning ofBuilding panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification.\nIncomer: 100A TPN 35kA MCCB with microprocessor release with adjustable OL, SC and EF protection \nBusbar: 150 A TPN busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. \nInstruments: 2A, C curve SP MCB - 3 nos.\nRYB indication lamp, LED type - 3 nos.\n1 No 3 phase Digital Multi function meter to read V, A, F, kW, kWh, Acc class 1.\n400/5A 5VA class 1 resin cast CT - 1 set\nOutgoing: 63A TPN 35kA MCCB with microprocessor release with adjustable OL, SC and EF protection - 2 nos. \n32A, TPN, 35kA CCB, thermal magnetic having adjustable O/L, SC protection - 5 nos. \nThe switchboard shall be complete with all inter connections, risers, internal wiring, labels etc complete as required | Item99 | 3 | No.s |
| 100 | 33.03 | Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. (Perforated cable tray shall be used, where wire mesh and ladder type cable tray difficult to used as required \n100 mm width X 50 mm depth X 1.6 mm thickness | Item100 | 30 | Metre |
| 101 | 33.04 | Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. (Perforated cable tray shall be used, where wire mesh and ladder type cable tray difficult to used as required \n150 mm width X 50 mm depth X 1.6 mm thickness | Item101 | 30 | Metre |
| 102 | 33.05 | Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. (Perforated cable tray shall be used, where wire mesh and ladder type cable tray difficult to used as required \n300 mm width X 50 mm depth X 1.6 mm thickness | Item102 | 30 | Metre |
| 103 | 34.01 | EXTERNAL LIGHTING\nSupply, installation, testing and commisning of New generation energy saving and environmental friendly long life 25 W LED street light made up of pressure\ndie cast aluminium housing with high power LED as lighting source and lens embedded PC cover with\nIP66 protection and impact resistance of IK07. | Item103 | 75 | Each |
| 104 | 34.02 | Supply & fixing of 65 mm dia.'B' class GI pole 4.5 mtr. Long for post top lantern i/c bas eplate 300 x 300 x 3mm GI reducer & nipple for mounting the fitting with painting etc. grounting in cement concrete 1: 3: 6 (1 cement : 3 coarse sand : 6 grade stone aggregate 40mm nominal size 0.4mm dia x 0.5 mm high to accomade the looping) complete as reqd. | Item104 | 20 | Each |
| 105 | 34.03 | S&F, connecting and commissioning looping type cable end control box with MS sheet of 16 SWG of size 200 mm x 200 mm x 125 mm having 1 no. 6amp to 32 amp SPMCB 250 volt and 2 nos. brass neutral link 12.5 mm square rod 6 way approx. 60 mm long and fixed on 5 mm thick bakelite sheet. Box shall have almirah type hing and panel key type lock front door duly painted with earthing strud etc. complete as required. | Item105 | 20 | Each |
| 106 | 34.04 | Timer switch for street lights | Item106 | 2 | No. |
| 107 | 35.01 | SUB HEAD (IX) :- DATA SYSTEM,TELEPHONE SYSTEM \nSupplying and fixing of 25 mm Steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. | Item107 | 50 | mtrs |
| 108 | 35.02 | Supplying and fixing of 32 mm steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. | Item108 | 50 | mtrs |
| 109 | 35.03 | Supplying and fixing of GI box of following size modules, alongwith modular base & cover plate for modular switches in recess etc as required.\n1 or 2 Module (75mmX75mm) | Item109 | 25 | No.s |
| 110 | 35.04 | Supplying and drawing 2 pair, 0.5 sq mm FR PVC insulated copper conductor, un armoured telephone cable in the existing surface/recessed steel/ PVC conduit. | Item110 | 150 | mtrs |
| 111 | 35.05 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.\nTelephone socket | Item111 | 6 | No.s |
| 112 | 36.01 | FIRE DETECTION SYSTEM\nFIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)\nSupplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. | Item112 | 3 | Each |
| 113 | 36.02 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. | Item113 | 3 | Each |
| 114 | 36.03 | Supplying, installation, testing & commissioning talk back slave station in surface/recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/microphone enclosed in a M.S.(16 SWG)/ ABS box with break glass in front etc. complete as required. | Item114 | 3 | Each |
| 115 | 37 | Design and Scope for Civil Works\n1.\tDesign, preparing architectural drawings , structural drawing, BOQ & supply and execution of the following civil works in Chhaba Newad & Bargadiyapurwa for Rural Solar pilot project as per tender specification.\n2.\tSoil Investigation at Chhaba Niwada & Bargadiyapurwa upto the depth level of 20 mtr. As per design & scope for civil work. \n3.\tDesign and execution of the Boundary wall work at Chhabaniwada (270 mtr. perimeter) & Bargadiyapurwa (120 mtr. Perimeter) upto the height of 300 mm above from the existing bituminous road and as per design & scope for civil work.\n4.\tEarthfilling work at Chhabaniwada ( 4550 sq.mtr. Area) & Bargdiyapurwa ( 800 sq.mtr.) upto the height of 300 mm above the existing bituminous road and as per design & scope for civil work. ( Note: Pls. visit the site for actual assesment before quoting the bid)\n5.\tInternal CC Road of width 3.0 mtr, thickness 150 mm with PCC of 1:4:8 of thickness 150 mm with storm water drainage to make the building approachable from the existing bituminous road. \n6.\tControl Room Chhabaniwada as per tentative plan enclosed and and as per design & scope for civil work with 4 mtr height from floor finished to soffit of the slab.( Note: Pls. visit the site for actual assesment before quoting the bid)\n7.\tControl Room Bargadiyapurwa as per tentative plan enclosed and and as per design & scope for civil work with 4 mtr height from floor finished to soffit of the slab .( Note: Pls. visit the site for actual assesment before quoting the bid)\n8.\tProcessing unit Building in Chhabbaniwada as per tentative plan enclosed and as per design & scope for civil work with 4 mtr height from floor finished to soffit of the slab.( Note: Pls. visit the site for actual assesment before quoting the bid)\n | Item115 | 1 | Job |
| 116 | 38 | Gravel Filling in the solar PV array area | Item116 | 50 | Cum |
| 117 | 39 | Safety: Fire extinguisher With sand bucket (4 Kg ABC type ) | Item117 | 10 | No. |
| 118 | 40 | Pilot 1 ( Semi-Urban Smart Grid Pilot with SPV, Storage and Thermal Storage inside IIT Kanpur Campus) (Total 200 kWp = 30*5 + 25 + 25 kWp)\nSolar PV Modules:\nSupply, installation,testing and Commissioning of Solar PV module (300-380Wp) monocrytalline or higher specifications with efficiency higher than 19.5 % under standard test conditions. All modules provided with their flash sheets giving test reports of all the important parameters. Requisite certification of conversion efficiency after statistical sample testing by an MNRE approved certifying agency have to be provided by the bidder.The PV modules will conform to IEC62109 Part 1 and 2 for testing, for safety qualification or equivalent.Warranty of solar PV modules for 90% performance at 10 years, 80% at 25 years and 25 years for structures.Junction boxes with appropriate bypass diodes for each panel and cable entry will be IP65 compatible.\n \n(30x 5KWp for 30 number of houses (total for houses 150kWp), 2x 25kWp for 2 number of EV charging station (total for EV charging station 50 kWp). This will include the foundation and GI framework for moounting the soalr panels as per the detailed specifications. The bidder shall provide the STAAD report for mounting arrangement suitable to sustain 170 KMPH wind speed. | Item118 | 1 | kWp |
| 119 | 41 | Grid Connected Inverter for 30 Houses:\nSupply, installation,testing & commissioning of 30 number of 5kWp grid connected, single phase Inverter, IP 65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, AC power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. | Item119 | 30 | No. |
| 120 | 42 | Hybrid Inverter 2 EV charging stations:\nSupply, installation, testing & commissioning of 2 number of 25kWp, three phase hybrid Inverter, IP65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, AC power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. | Item120 | 2 | No. |
| 121 | 43 | Hybrid Inverter for lane-32:\nSupply, installation,testing & commissioning of 50kW, 415V Three phase hybrid Inverter, IP65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, ac power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. Battery and inverter in a outdoor type enclosure for flow battery along with control panel and cabling. | Item121 | 1 | No. |
| 122 | 44 | Hybrid Inverter for lane-33:\nSupply, installation,testing & commissioning of 70kW, 415V Three phase hybrid Inverter, IP65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, ac power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. Battery and inverter in a single outdoor type enclosure for Li-ion along with control panel and cabling | Item122 | 1 | No. |
| 123 | 45 | Li-ion Battery for Lane-33:\nSupply, installation,testing & commissioning of 70kW capacity, with 140kWh, around 500V, Li-ion Battery Bank with BMS (Battery Management System), minimum 6000 cycle life on 80% DOD, @0.2C Charge and 0.2 Discharge, CE/UL certified , protection class IP 20, Wi-Fi/RS485 compatible and capable of integrating with SCADA as per the tender specifications. Battery and inverter in a single outdoor type enclosure for Li-ion along with control panel and cabling\nNote: The cost also included the mounting arrangement. | Item123 | 1 | set |
| 124 | 46 | Redox flow Battery for Lane-32:\nSupply, installation,testing & commissioning of 50kW capacity, with 100kWh, around 500V, Li-ion Battery Bank with BMS (Battery Management System), atleast 15000 cycle life on 100% DOD, @0.2C Charge and 0.2 Discharge, CE/UL certified , protection class IP 20, Wi-Fi/RS485 compatible and capable of integrating with SCADA as per the tender specifications. Battery and inverter in a outdoor type enclosure for flow battery along with control panel and cabling \nNote: The cost also included the mounting arrangement. | Item124 | 1 | set |
| 125 | 47 | Li-ion Battery for 2 EV Charging station:\nSupply, installation,testing & commissioning of 70kW capacity, with 140kWh, around 500V, Li-ion Battery Bank with BMS (Battery Management System), minimum 6000 cycle life on 80% DOD, @.2C Charge and .2 Discharge, CE/UL certified, protection class IP20, Wi-Fi/RS485 compatible and capable of integrating with SCADA as per the tender specifications. \nNote: The cost also included the mounting arrangement. | Item125 | 2 | set |
| 126 | 48 | EV charging station:\nEV charging station with charging capacity of 100 kW\ni) 1 no. CHAdeMO (DC Charger), \nii) 1 no. CCS (DC charger)\niii) 1 no. (AC Charger)\niv) 2 no. three wheeler (AC charger) | Item126 | 2 | set |
| 127 | 49 | Three Phase LTCT meter with CTs: for Chhabbaniwada and Bargadiyapurwa\nSupply, installation, testing & commissioning of Energy meter (3P), specs -\n• Type- 3 phase 4 wire LTCT operated smart energy meter\n• Accuracy class- 0.5s\n• Energy parameter- import & export energy\n• Operating voltage- 3x 240V single phase, +/- 10%\n• Operating current- 5A\n• Frequency- 50Hz +/- 5%\n• Communication Protocol- DLMS compliance as per IS 15959, IS16444, IPv6\n• Communication Options- Optical Port/ RS485/ RS232/ Ethernet/ Wi-Fi/ GSM, compatibility for SCADA and AMI integration\n• Internal battery- yes: for power fail mode display operation\n• Standards- As per IS 16444, IEC 62052-11, IEC 62053-22, 62053-24, 62052-31, IEC 60060-1\n• Power consumption, accuracy limit, impulse voltage, construction requirements, resistance to heat & fire, climatic influence, electromagnetic compatibility (EMC)- As per above mentioned Standards\n• Security Policy- data access: as per DLMS/ COSEM server\n* Should be capable of storing 45 days of 15 minutes consumption data | Item127 | 8 | No. |
| 128 | 50 | Single Phase Smart Meters for Chhabbaniwada and Bargadiyapurwa\nSupply, installation, testing & commissioning of Energy meter (1P), with minimum specifications mentioned below.\ni) Meters should support 4 quadrant measurement of power(Import/Export), with open protocols like DLMS, COSEM, IS16444, \nii) two way communications along with remote connect/disconnect of power supply.\niii) Should support internal communication interface for Data Concentrator Unit (DCU) / Headend System (HES) and HAN device.\niv) Should avail port for local communication\nv) Should be capable of storing 45 days of 15 minutes consumption data\nvi) Should record billing, load survey, event & tampers, instantaneous and demand parameters\nvii) Should provide feature for firmware upgrade, tariff configuration, load limit setting, tamper reset, MD (Maximum Demand) reset and time set transaction. These features should also be possible to realize remotely.\nviii) Should have load limiting provision with audible alarm\nix) Should have capability to communicate over RF. Should have compatibility for SCADA and AMI integration\nx) These single phase smart meters may communicate directly to the Data Concentrator Unit (DCU) and can be used to collect data from multiple meters (hopping) which can be sent to the Head End System (HES) via DCU.\n• Internal battery- yes: for power fail mode display operation | Item128 | 40 | No. |
| 129 | 51 | Data Concentrator Unit (DCU): \ni) minimum number of 32 nodes can be handled\nii) In built memory (SD card)\niii) connectivity to Device (Smart Meter) : RF Mesh\niv) Connectivity with Edge DCU : RF Mesh \nv) Should support multiple smart meters over RS485 and RF network both\nvi) Push/Pull mode of operation, remote firmware upgrade and configuration of device\nvii) Support group data collection by single command\nviii) Auto RTC sync with HES time\nix) IP 54 insulating encased meter and protective Class II\nx) Password protection for optical communication; authenticated, password-protected transactions and encryption for RF mesh (Sub-GHz 865-867 ISM Band), GPRS and RS-485 communication.\nNote: Repeators should also be provided as per requirement at the installation site. The cost of repeaters to be included in this item.\n | Item129 | 10 | No. |
| 130 | 52 | 3-ph ACDB suitable for outdoor installation IP55, having 2 incomers one of 250A rating and the other of 160A rating and one outgoing of 250A rating communicable MCCBs | Item130 | 2 | No. |
| 131 | 53.01 | Supply and laying of AYFY, XLPE insulated cable 1100 V of 3½Cx185 sq.mm | Item131 | 100 | mtr. |
| 132 | 53.02 | Supply and installation of DC Copper Screened Cable, PVC insulated 1100 V of 3Cx6 sq. mm | Item132 | 500 | mtr. |
| 133 | 53.03 | Supply and installation of DC Copper Screened Cable, PVC insulated 1100 V of 1Cx6 sq. mm | Item133 | 600 | mtr. |
| 134 | 54.01 | LIGHTNING PROTECTION AND EARTHING\nEarthing with G.I. earth pipe 4.5 metre long, 40 mm dia\nincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. | Item134 | 94 | each |
| 135 | 54.02 | Providing and fixing 25mm x 5 mm G.I strip on surface or in recess for connections etc. as required. | Item135 | 1500 | meter |
| 136 | 54.03 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | Item136 | 600 | meter |
| 137 | 54.04 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. | Item137 | 32 | Nos |
| 138 | 54.05 | Jointing copper / G.I. tape (with another copper/ G I tape, baseof the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. | Item138 | 32 | Nos |
| 139 | 54.06 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | Item139 | 32 | meter |
| 140 | 54.07 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | Item140 | 32 | meter |
| 141 | 54.08 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | Item141 | 32 | meter |
| 142 | 54.09 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | Item142 | 32 | meter |
| 143 | 55 | Safety: Fire extinguisher With sand bucket (4 Kg ABC type ) | Item143 | 4 | No. |
| 144 | 56 | Pilot 2 ( Urban Smart Grid Pilot with SPV, Storage and Thermal Storage inside IIT Kanpur Campus) (Total 50 kWp = 25 + 25 kWp)\nSolar PV Modules:\nSupply, installation,testing and Commissioning of Solar PV module (300-380Wp) monocrytalline or higher specifications with efficiency higher than 19.5 % under standard test conditions. All modules provided with their flash sheets giving test reports of all the important parameters. Requisite certification of conversion efficiency after statistical sample testing by an MNRE approved certifying agency have to be provided by the bidder.The PV modules will conform to IEC62109 Part 1 and 2 for testing, for safety qualification or equivalent.Warranty of solar PV modules for 90% performance at 10 years, 80% at 25 years and 25 years for structures.Junction boxes with appropriate bypass diodes for each panel and cable entry will be IP65 compatible.\n \n(30x 5KWp for 30 number of houses (total for houses 150kWp), 2x 25kWp for 2 number of EV charging station (total for EV charging station 50 kWp). This will include the foundation and GI framework for moounting the soalr panels as per the detailed specifications. The bidder shall provide the STAAD report for mounting arrangement suitable to sustain 170 KMPH wind speed. | Item144 | 1 | kWp |
| 145 | 57 | Hybrid Inverter for Residence apartment block-C and block-D:\nSupply, installation, testing & commissioning of 2 number of 100kW, three phase hybrid Inverter, IP65 (Power Conditioning Unit) with In-build MPPT, capable of operating in grid feeding mode and capable of creating islanded microgrid, depending on the availability of grid. Capable for monitoring of parameters such as battery SoC, battery power, solar PV power, AC power, mode of operation, PV voltage, current, battery voltage, battery current, grid voltage, current, frequency, power factor, battery temperature etc. through SCADA as per tender specifications. | Item145 | 2 | No. |
| 146 | 58 | Li-ion Battery for Residence apartment block-C and block-D:\nSupply, installation,testing & commissioning of 50kW capacity, with 50kWh, around 500V, Li-ion Battery Bank with BMS (Battery Management System), minimum 6000 cycle life on 80% DOD, @0.2C Charge and 0.2 Discharge, CE/UL certified, protection class IP 20, Wi-Fi/RS485 compatible and capable of integrating with SCADA as per the tender specifications. \nNote: The cost also included the mounting arrangement. | Item146 | 2 | set |
| 147 | 59.01 | Supply and laying of AYFY, XLPE insulated cable 1100 V of 3½Cx120 sq.mm | Item147 | 100 | mtr. |
| 148 | 59.02 | Supply and installation of DC Copper Screened Cable, PVC insulated 1100 V of 1Cx70 sq. mm | Item148 | 100 | mtr. |
| 149 | 60.01 | LIGHTNING PROTECTION AND EARTHING\nEarthing with G.I. earth pipe 4.5 metre long, 40 mm dia\nincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. | Item149 | 10 | Each |
| 150 | 60.02 | Providing and fixing 25mm x 5 mm G.I strip on surface or in recess for connections etc. as required. | Item150 | 1500 | meter |
| 151 | 60.03 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | Item151 | 600 | meter |
| 152 | 60.04 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. | Item152 | 32 | Nos |
| 153 | 60.05 | Jointing copper / G.I. tape (with another copper/ G I tape, baseof the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. | Item153 | 5 | Nos |
| 154 | 60.06 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | Item154 | 5 | meter |
| 155 | 60.07 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | Item155 | 5 | meter |
| 156 | 60.08 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | Item156 | 5 | meter |
| 157 | 60.09 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | Item157 | 5 | meter |
| 158 | 61 | Safety: Fire extinguisher With sand bucket (4 Kg ABC type ) | Item158 | 2 | No. |
| 159 | 62 | Defect Liability Period and AMC or Warranty:\nComprehensive annual maintanance contract of the pilots for 3 years after expiry of 1 year defect liability period (Defect Liability period will start after successful completion of the three pilots). | Item159 | 5 | Years |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy