| 1 | 1 | Dismantling and taking out old existing serviceable/unserviceable ACSR conductor of any description and in any position from HT/LT over head lines poles including disconnection after taking proper written shut down from 11KV main receiving station Dhar Road all as specified and directed by Engr-in-Charge | | 4 | Quintal |
|---|
| 2 | 2 | Dismantling & taking out of old existing serviceable/unserviceable steel & iron items from poles such as cross arms, bracing, supports, clamps and back plate fabricated from structural steel sections including nuts & bolts, washers of any description and in any position from OH over head lines poles complete all as specified and directed by Engr-in-Charge. | | 3 | Quintal |
|---|
| 3 | 3 | Dismantling and taking out existing HT/LT insulators of any types and any size all as specified and directed by Engr-in-Charge | | 200 | Each |
|---|
| 4 | 4 | Excavation in trenches in any type of soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide and getting out complete all as specified and as directed by the Engr-in-Charge | | 900 | Cubic\nmetre |
|---|
| 5 | 5 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick (soil) complete all as specified and as directed by the Engineer-in-Charge | | 575 | Cubic\nmetre |
|---|
| 6 | 6 | Removing excavated surplus soil n exc. 50 metre distance and depositing where directed at a level n exc. 1.5m above the starting point complete all as specified and as directed by the Engineer-in-Charge | | 325 | Cubic\nmetre |
|---|
| 7 | 7 | M & L for dry sand cushioning with a layer of sand 8cm deep before laying the cable and 15 cm deep after laying, stretching the cable in trenches and punning the sand layer gently complete all as specified and as directed by the Engr-in-Charge . ( Punning thickness 18cm of sand shall be measured) | | 275 | Cubic\nmetre |
|---|
| 8 | 8 | M & L for brick, laid dry, old size well burnt sub class ‘B’ laid with width equal to length of brick as mechanical protection to underground cable complete all as specified and as directed by the Engineer-in-Charge | | 27 | Per 1000 \nNos |
|---|
| 9 | 9 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 35 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge | | 300 | Running \nmetre |
|---|
| 10 | 10 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 185 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 550 | Running \nmetre |
|---|
| 11 | 11 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 150 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 165 | Running \nmetre |
|---|
| 12 | 12 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 120 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 700 | Running \nmetre |
|---|
| 13 | 13 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 95 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 1200 | Running \nmetre |
|---|
| 14 | 14 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 70 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 900 | Running \nmetre |
|---|
| 15 | 15 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core, cross sectional area 50 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 250 | Running \nmetre |
|---|
| 16 | 16 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 core, cross sectional area 16 Sqmm laid in trenches or through floor/duct/fixing on wall etc complete all as specified and as directed by the Engr-in-Charge. | | 3500 | Running \nmetre |
|---|
| 17 | 17 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 2 core, cross sectional area 10 Sqmm laid in trenches or through floor/duct/fixing on wall etc.of any size complete all as specified and as directed by the Engr-in-Charge | | 400 | Running \nmetre |
|---|
| 18 | 18 | Supply and laying or fixing or passing through pipe from junction box to street light connection, 1100 volts grade heavy duty cable with PVC solid insulated aluminium conductor served with an inner sheathing PVC tape and over all PVC sheathed size 6 sqmm 2 core nominal cross section complete all as specified and directed by the Engr-in-Charge. | | 600 | Running \nmetre |
|---|
| 19 | 19 | Supply, laying, connecting up and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 3 core, cross sectional area 95 Sqmm laid in trenches or through floor/duct/fixing on wall etc. complete all as specified and as directed by the Engr-in-Charge | | 930 | Running \nmetre |
|---|
| 20 | 20 | Supply and fix street light junction box of size 200mm x140mm x 95mm outdoor type, weather proof, factory made out of PVC sheet 1.8mm thick with front side hinged opening having locking arrangement with nuts & bolts & arrangement for incoming and outgoing cable/wire complete comprising with the following :-\n(a) Bus bar with four aluminium strips,100 Amps capacity insulated with insulators, including coding, including PVC cable of suitable size from bus bar to MCB.\n(b) MCB SPN 5 to 30 Amps -01 No.\n(c) Clamps made out of 25mm x 3mm flat iron duly welded with nuts & bolts complete all as specified and directed.\n | | 55 | Each |
|---|
| 21 | 21 | Supply and fix street light junction box of size 200mm x140mm x 95mm outdoor type, weather proof, factory made out of PVC sheet 1.8mm thick with front side hinged opening having locking arrangement with nuts & bolts & arrangement for incoming and outgoing cable/wire complete comprising with the following :-\n(a) Bus bar with two aluminium strips,100 Amps capacity insulated with insulators, including coding, including PVC cable of suitable size from bus bar to MCB.\n(b) MCB SPN 5 to 30 Amps -01 No.\n(c) Clamps made out of 25mm x 3mm flat iron duly welded with nuts & bolts complete all as specified and directed.\n | | 14 | Each |
|---|
| 22 | 22 | M&L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 32mmx6mm galvanized strip as earth lead by means of bolts, nuts, check nuts and washers of galvanized and earth strip protected by provision of GI pipe light weight 50mm bore all as specified or indicated in electrical plate No. 3 of MES Part-I, including testing on completion including the material and labour for the following :-\n(a) Excavation and earth work for drilling hole for electrode in any type of soil including removal of surplus soil to a distance n.exc 50 mtr. \n(b) PCC pit in cement concrete 1:2:4 type B-1. \n(c) Precast RCC cover with suitable handle 50 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.\n(d) Funnel with watering pipe of GI 20 mm nominal bore light grade and copper lugs etc all as specified. \n(e) Common salt, charcoal filling, test point made out of phosphorous bronze with fixing arrangement | | 5 | Each Set |
|---|
| 23 | 23 | Supply, fabricate, install and testing of outdoor cubical inclined top type LT panel board having width 500 mm (minimum) with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of 600 amps for phases & neutral duly laminated with PVC sleeves with colour coding, plate for fixing MCCB's, cover plate for covering MCCB's with openings for MCCB's knobs including two nos hinged doors, front and back openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including provision of CTs, sliding fuse, LED indicator, control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, all meters and comprising the following items duly connected with other electrical acessories and marking of all Incoming/outgoing feeders for identification of feeders by using sticker letters all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works ,cable glands, lugs, nut & bolts and washers etc . (ii) General arrangement drawing of LT panel shall be approved by Accepting Officer before procurement. | | 2 | Each Set |
|---|
| 24 | 24 | INCOMING: (a) MCCB, 400 Amp, 36 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, \n conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos\nOUTGOING : (a) MCCB, 250 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=02 Nos.\n (b) MCCB, 100 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=02 Nos.\n (c) Ammeter 0-250 Amps, 96 mm X 96 mm, digital type with inbuilt three way ON/OFF selector switch ( 1 No.)\n (d) Indicating lamps for three phases ( set of 3 Nos)\n (e) Voltmeter 0 – 500 Volts, 96 mm X 96 mm, electronic digital type, with inbuilt three way ON/OFF selector switch ( 1 No.)\n (f) CTs 5A/50 - 01 Set (set of three)\n (g)Selector switch for Amp/Volt Meter - 02 Nos.\n | | | |
|---|
| 25 | 25 | Supply, fabricate, install and testing of outdoor cubical inclined top type LT panel board having width 500 mm (minimum) with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of 600 amps for phases & neutral duly laminated with PVC sleeves with colour coding, plate for fixing MCCB's, cover plate for covering MCCB's with openings for MCCB's knobs including two nos hinged doors, front and back openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including provision of CTs, sliding fuse, LED indicator, control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, all meters and comprising the following items duly connected with other electrical acessories and marking of all Incoming/outgoing feeders for identification of feeders by using sticker letters all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works, cable glands, lugs, nut & bolts and washers etc . (ii) General arrangement drawing of LT panel shall be approved by Accepting Officer before procurement. | | 2 | Each Set |
|---|
| 26 | 26 | INCOMING: (a) MCCB, 250 Amp, 36 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, \n conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos\nOUTGOING : (a) MCCB, 100 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=03 Nos.\n (b) MCCB, 63 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=01 Nos.\n (c) Ammeter 0-250 Amps, 96 mm X 96 mm, digital type with inbuilt three way ON/OFF selector switch ( 1 No.)\n (d) Indicating lamps for three phases ( set of 3 Nos)\n (e) Voltmeter 0 – 500 Volts, 96 mm X 96 mm, electronic digital type, with inbuilt three way ON/OFF selector switch ( 1 No.)\n (f) CTs 5A/50 - 01 Set (set of three)\n (g)Selector switch for Amp/Volt Meter - 02 Nos.\n | | | |
|---|
| 27 | 27 | Supply, fabricate, install and testing of outdoor cubical inclined top type LT panel board having width 500 mm (minimum) with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of 600 amps for phases & neutral duly laminated with PVC sleeves with colour coding, plate for fixing MCCB's, cover plate for covering MCCB's with openings for MCCB's knobs including two nos hinged doors, front and back openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including provision of CTs, sliding fuse, LED indicator, control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, all meters and comprising the following items duly connected with other electrical acessories and marking of all Incoming/outgoing feeders for identification of feeders by using sticker letters all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works, cable glands, lugs, nut & bolts and washers etc . (ii) General arrangement drawing of LT panel shall be approved by Accepting Officer before procurement. | | 2 | Each Set |
|---|
| 28 | 28 | INCOMING: (a) MCCB,250 Amp, 36 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, \n conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos\nOUTGOING : (a) MCCB, 200 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=01 Nos.\n (b) MCCB, 63 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=03 Nos.\n (c) Ammeter 0-250 Amps, 96 mm X 96 mm, digital type with inbuilt three way ON/OFF selector switch ( 1 No.)\n (d) Indicating lamps for three phases ( set of 3 Nos)\n (e) Voltmeter 0 – 500 Volts, 96 mm X 96 mm, electronic digital type, with inbuilt three way ON/OFF selector switch ( 1 No.)\n (f) CTs 5A/50 - 01 Set (set of three)\n (g)Selector switch for Amp/Volt Meter - 02 Nos.\n | | | |
|---|
| 29 | 29 | Supply, fabricate, install and testing of outdoor cubical inclined top type LT panel board having width 500 mm (minimum) with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of 600 amps for phases & neutral duly laminated with PVC sleeves with colour coding, plate for fixing MCCB's, cover plate for covering MCCB's with openings for MCCB's knobs including two nos hinged doors, front and back openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including provision of CTs, sliding fuse, LED indicator, control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, all meters and comprising the following items duly connected with other electrical acessories and marking of all Incoming/outgoing feeders for identification of feeders by using sticker letters all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works, cable glands, lugs, nut & bolts and washers etc . (ii) General arrangement drawing of LT panel shall be approved by Accepting Officer before procurement. | | 1 | Each Set |
|---|
| 30 | 30 | INCOMING: (a) MCCB, 200 Amp, 36 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, \n conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos\nOUTGOING : (a) MCCB, 100 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=02 Nos.\n (b) MCCB, 63 Amp, 25 kA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase,\n conform to IS/IEC 60947-2 & IEC 60947-2,=02 Nos.\n (c) Ammeter 0-250 Amps, 96 mm X 96 mm, digital type with inbuilt three way ON/OFF selector switch ( 1 No.)\n (d) Indicating lamps for three phases ( set of 3 Nos)\n (e) Voltmeter 0 – 500 Volts, 96 mm X 96 mm, electronic digital type, with inbuilt three way ON/OFF selector switch ( 1 No.)\n (f) CTs 5A/50 - 01 Set (set of three)\n (g)Selector switch for Amp/Volt Meter - 02 Nos.\n | | | |
|---|
| 31 | 31 | Supply, fabricate, install and testing of outdoor cubical/enclosure/feeder piller box made with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of suitable amps for phases & neutral duly laminated with PVC sleeves with colour coding, suitable for housing with and including MCCB 250 Amps, 4 poles, 25 KA including two nos hinged doors, front openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, and comprising the following items duly connected with other electrical acessories all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works . (ii) MCCB 250 Amp, 25 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos (iii) Cable glands, lugs, nut & bolts and washers Complete fixing accessories. | | 3 | Each Set |
|---|
| 32 | 32 | Supply, fabricate, install and testing of outdoor cubical/enclosure/feeder piller box made with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of suitable amps for phases & neutral duly laminated with PVC sleeves with colour coding, suitable for housing with and including MCCB 200Amps, 4 poles, 25 KA including two nos hinged doors, front openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, and comprising the following items duly connected with other electrical acessories all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works . (ii) MCCB 200 Amp, 25 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos (iii) Cable glands, lugs, nut & bolts and washers Complete fixing accessories. | | 3 | Each Set |
|---|
| 33 | 33 | Supply, fabricate, install and testing of outdoor cubical/enclosure/feeder piller box made with 3.15 mm thick CRCA sheet powder coated with all necessary frame work with suitable size angle iron, CPRI approved, IP-54 protection provision including aluminum bus bar of suitable amps for phases & neutral duly laminated with PVC sleeves with colour coding, suitable for housing with and including MCCB 100 Amps, 4 poles, 25 KA including two nos hinged doors, front openable with locking arrangements, handles, etc. The cabinet and all accessories should be chemically treated with nine tank process for anticorrosive treatment. The panel should be suitable for 415 Volts, 50 Hz, 3 phase 4 wire system including control cables, etc as required and internal connection should be pre-wired with suitable size of power cable/ copper solid wire/strip for instrument/protecting devices, and comprising the following items duly connected with other electrical acessories all as specified and directed by Engr-in-charge including necessary foundation work of the panel board with PCC 1:2:4 type B-1 (using 20mm graded aggregate) and angle iron base for panel of size 40 mm X 40 mm X 6 mm thickness, etc complete. The LT panel/feeder pillar shall comprises of the following :- NOTE : (i) Quoted rates shall be deemed inclusive for PCC works . (ii) MCCB 100 Amp, 25 KA, adjustable type with thermal magnetic release, 4 pole 415 volts 3phase, conform to IS/IEC 60947-2 & IEC 60947-2, = 01 Nos (iii) Cable glands, lugs, nut & bolts and washers Complete fixing accessories. | | 4 | Each Set |
|---|
| 34 | 34 | M & L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination end heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed by the Engineer-in-Charge | | 3 | Each |
|---|
| 35 | 35 | M & L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed by the Engineer-in-Charge | | 1 | Each |
|---|
| 36 | 36 | M & L for cable jointing kit for 1100 Volts (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 10 to 16 Sqmm sqmm complete all as specified and as directed by the Engineer-in-Charge | | 4 | Each |
|---|
| 37 | 37 | M & L for cable jointing kit for 1100 Volts (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm sqmm complete all as specified and as directed by the Engineer-in-Charge | | 2 | Each |
|---|
| 38 | 38 | M & L for cable jointing kit for 1100 Volts (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm sqmm complete all as specified and as directed by the Engineer-in-Charge | | 2 | Each |
|---|
| 39 | 39 | M & L for cable jointing kit for 1100 Volts (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm sqmm complete all as specified and as directed by the Engineer-in-Charge | | 2 | Each |
|---|
| 40 | 40 | Supply and laying/fixing 100mm bore,medium grade GI tubing for protection of underground cable, fixed on poles/cross arms/laid under road with MS clamps with nut, bolt washer, etc., complete all as specified and as directed by Engr-in-Charge | | 10 | Running \nmetre |
|---|
| 41 | 41 | Supply and laying/fixing 80mm bore,medium grade GI tubing for protection of underground cable, fixed on poles/cross arms/laid under road with MS clamps with nut, bolt washer, etc., complete all as specified and as directed by Engr-in-Charge | | 20 | Running \nmetre |
|---|
| 42 | 42 | Supply and laying/fixing 50mm bore,medium grade GI tubing for protection of underground cable, fixed on poles/cross arms/laid under road with MS clamps with nut, bolt washer, etc. complete all as specified and as directed by Engr-in-Charge | | 20 | Running \nmetre |
|---|
| 43 | 43 | Supply and laying/fixing 40mm bore,medium grade GI tubing for protection of underground cable, fixed on poles/cross arms/laid under road with MS clamps with nut, bolt washer, etc. complete all as specified and as directed by Engr-in-Charge | | 100 | Running \nmetre |
|---|
| 44 | 44 | Supply and fixing 15mm bore, light grade GI tubing for protection of cable, fixed on poles/cross arms with MS clamps with nut, bolt washer, etc., complete all as specified and as directed by Engr-in-Charge. | | 100 | Running \nmetre |
|---|
| 45 | 45 | Supply and fixing reinforced pre-cast concrete cable route indicator over the HT/LT cables size 800mm (lenght) x 100mm (thicknes) x ( 350mm Width at bottom and 200mm at top) and engraved/ marked with \"11KV HT/1100 VOLT LT CABLE\" in appropriate size and painting with two coats of synthetic enamel paint of colour RED and BLACK combination including earth works and PCC work for foundation complete all as specified and directed by the Engr-in-Charge. | | 100 | Each Job |
|---|