Repair/Maintenance Of Internal Switch Gears , Sub Main Wiring , Service Connections And Earthing At Rms Contents
Tender Value
25 Lakhs
Estimated cost
Bid Submission
08 Nov 2019
0 days left
EMD
50000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Rangapahar → Nagaland
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Repair/Maintenance Of Internal Switch Gears , Sub Main Wiring , Service Connections And Earthing At Rms Contents
BOQ
| Name of Work: REPAIR/ MAINTENANCE OF INTERNAL SWITCH GEARS, SUB MAIN WIRING, SERVICE CONNECTIONS AND EARTHING AT RMS | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Taking down existing burnt aluminium/copper sub-main wiring with PVC insulated & unsheathed Four run of 6.0 Sqmm single core multi stranded copper copnductor cable (FRLSH) 1100 Volt grade along with one run of Sqmm PVC insulated & Unsheathed copper conductor cable (FRLSH) 1100 Volt grade connected to common earth dolly as earth continuty conductor, drawn through 20 mm dia PVC Casing Caping after and inclduing taking down existing submain wiring complete all as specified and as directed Note:- Four runs of 6.0 Sqmm cable one run 4.0 Sqmm \nMake : Finolex/Havells/RR Kabel.Make of caping/casing & PVC boxes : Prestoplast/finolex/Supreme | 100 | RM | |
| 2 | 2 | Ditto All as per item No 01 above but two run of 2.5 Sqmm wire and one run of 1.5 Sqm for Earth wire. | 300 | RM | |
| 3 | 3 | Ditto All as per item No 01 above but two run of 10 Sqmm wire and one run of 6.0 Sqm for Earth wire. | 150 | RM | |
| 4 | 4 | Ditto All as per item No 01 above but two run of 6 Sqmm wire and one run of 4.0 Sqm for Earth wire. | 200 | RM | |
| 5 | 5 | Ditto All as per item No 01 above but two run of 4 Sqmm wire and one run of 2.5 Sqm for Earth wire. | 350 | RM | |
| 6 | 6 | M&L for MCB Distribution board double door type (for incoming MCCB & out going MCBs) tpn 4 Way, sheet steel powder painted with bus bar neutral link & earth bar etc and fixing only incoming MCCB and MCBs of various rating capacity including taking down old unsv DB of any capacity complete all as specified and as directed. \nMake : Legrand cat No 507750 or Equivelent in Havells/Indoasian | 10 | Each | |
| 7 | 7 | All as per item No 06 above but Make : Legrand cat No 507751 or Equivelent in Havells/Indoasian | 10 | Each | |
| 8 | 8 | M&L for MCB Distribution board double door type SPN 12 way sheet steel powder painted with bus bar neutral link & earth din rail, recessed with wall surfaces by chase cutting and making good disturbed surfaces of wall complete all as specified and as directed. Make : Legrand Cat No 507612 or equivalent in ABB/Siemens | 10 | Each | |
| 9 | 9 | All as per item No 08 above but SPN 8 Way Make : Legrand Cat No 507611 or equivalent in ABB/Siemens | 30 | Each | |
| 10 | 10 | All as per item No 05 above but SPN 4 Way Make : Legrand Cat No 507610 or equivalent in ABB/Siemens | 50 | Each | |
| 11 | 11 | All as per item No 05 above but SPN 2 Way Make : Legrand Cat No 5077911 or equivalent in ABB/Siemens | 75 | Each | |
| 12 | 12 | M&L for MCCB FP, 415 Volts adjustable type, 160 Amps 4 pole with breaking capacity 36 KA suitable for fixing in MCB DB complete all as specified and as directed. Make : Legrand cat No 420097 or equivalent in ABB/Siemens. | 15 | Each | |
| 13 | 13 | All as per item No 12 above MCCB FP, 415 Volts adjustable type, 125 Amps 4 pole with breaking capacity 36 KA suitable for fixing in MCB DB complete all as specified and as directed. Make : Legrand cat No 420096 or equivalent in ABB/Siemens. | 20 | Each | |
| 14 | 14 | M&L for MCB TPN 40 Amps 415 Volt 50 Hz suitable for fixing in MCB DB 'C' series, complete all specified and as directed. Make:Legrand Cat No 408681 or equivalent in ABB/Siemens. | 50 | Each | |
| 15 | 15 | M&L for MCB TPN 63 Amps 415 Volt 50 Hz suitable for fixing in MCB DB 'C' series, complete all specified and as directed. Make:Legrand Cat No 408683 or equivalent in ABB/Siemens. | 100 | Each | |
| 16 | 16 | M&L for MCB TP 63 Amps 415 Volt 50 Hz suitable for fixing in MCB DB 'C' series, complete all specified and as directed. Make:Legrand Cat No 408661 or equivalent in ABB/Siemens. | 20 | Each | |
| 17 | 17 | M&L for MCB TPN 100 Amps 415 Volt 50 Hz suitable for fixing in MCB DB 'C' series, complete all specified and as directed. Make:Legrand Cat No 408704 or equivalent in ABB/Siemens. | 50 | Each | |
| 18 | 18 | M&L for MCB 32 Amps SPN 240 Volt 'C' series, breaking capacity 10 KA complete all specified and as directed. Make:Legrand Cat No 408617 or equivalent in ABB/Siemens. | 150 | Each | |
| 19 | 19 | M&L for MCB 40 Amps SPN 240 Volt 'C' series, breaking capacity 10 KA complete all specified and as directed. Make:Legrand Cat No 408617 or equivalent in ABB/Siemens. | 150 | Each | |
| 20 | 20 | M&L for MCB 63 Amps SPN 240 Volt 'C' series, breaking capacity 10 KA complete all specified and as directed. Make:Legrand Cat No 408620 or equivalent in ABB/Siemens. | 70 | Each | |
| 21 | 21 | M&L forMCB 6 to 32 Amps SP 240 Volt 'C' series, breaking capacity 10 KA complete all specified and as directed.Make:Legrand Cat No 408587 to 95 or equivalent in ABB/Siemens. | 500 | Each | |
| 22 | 22 | M&L for MCB 06 to 32 Amps SPN 240 Volt 'C' series, breaking capacity 10 KA complete all specified and as directed. Make:Legrand Cat No 408609 to 408617 or equivalent in ABB/Siemens. | 420 | Each | |
| 23 | 23 | Replacement of MCCB 25 to 100 Amps 4 pole 16 KA complete as specified and as directed. Make : Legrand cat No 420011 to 420015 or equivalent to ABB/Siemens | 15 | Each | |
| 24 | 24 | Replacement of MCCB 125 Amps 4 pole 16 KA complete as specified and as directed. Make : Legrand cat No 420016 or equivalent to ABB/Siemens | 15 | Each | |
| 25 | 25 | S&F 1100 Volts grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hanger not more than 1 meter apart including 4 mm suspension wire one twine core cable flat or circular stranded conductor of size 4 Sqmm | 385 | RM | |
| 26 | 26 | All as per item No 25.00 above but 6 Sqmm twine core cable. | 500 | RM | |
| 27 | 27 | All as per item No 25.00 above but 10 Sqmm twine core cable. | 400 | RM | |
| 28 | 28 | All as per item No 25.00 above but 16 Sqmm twine core cable. | 300 | RM | |
| 29 | 29 | M&L for earthing complete with galvanized steel earth plate electrode of size 600x600x6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level connected to galvanised earth lead wire 4 mm dia as earth lead connectd by means of bolts, nuts, washers and check nuts all as shown in electrical plate No 3 of MES SSR Part-I, including testing on completion complete all as specified and as directed. NOTE:- (i) The unit rate shall also included for earth work in hard/ dense soil, PCC (1:3:6) type C1, CI cover 10 mm thick, funnel with GI watering pipe 20mm dia Medium grade, GI protection pipe light grade 15mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (notes) under sub heading earthing, specified on Sl Page No 389 of MES SSR Part-II. (ii) Earthing lead and GI protection pipe beyond 7.5m will be measured and paid separately. (iii) Test points shall be made of GI strip 32x6 mm bridge type mounted on insulators, where ever applicable\n | 20 | Each Set |
AI Tender Summary
Tender Timeline
Oct 19, 2019
11:30 IST
Tender Published
Tender notice published.
CompletedNov 08, 2019
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedNov 11, 2019
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender