Urgent Rectification Works And Provision Of Firefighting Equipments At A , B , C And D Block Of Rcc Urgent Rectification Works And Provision Of Firefighting Equipments At A , B , C And D Block Of Rcc
Tender Overview
Project Description
Urgent Rectification Works And Provision Of Firefighting Equipments At A , B , C And D Block Of Rcc Urgent Rectification Works And Provision Of Firefighting Equipments At A , B , C And D Block Of Rcc , Fire Detection & Alarm System , Supply , Installation , Testing & Commissioning Of The Fire Alarm System Consisting Of The Following , Microprocessor Based Conventional Fire Alarm Control Panel , Can Accommodate Maximum Range Of 32 Zones , S . User Friendly Systems Which Involves A Touch Keypad To Program The Panel Operates On 120 - 220Vac 60 /50 Hz , Ac Mains Power Supply Standby ( Battery ) Backup 24 Vdc Power Supply With Built In Charger Zone Isolation Facility With Loop Voltage Cut Off . Resettable / Steady 24Vdc . Output . , Microprocessor Based Conventional Fire Alarm Control Panel , Can Accommodate Maximum Range Of 24 Zones , S . User Friendly Systems Which Involves A Touch Keypad To Program The Panel Operates On 120 - 220Vac 60 /50 Hz , Ac Mains Power Supply Standby ( Battery ) Backup 24 Vdc Power Supply With Built In Charger Zone Isolation Facility With Loop Voltage Cut Off . Resettable / Steady 24Vdc . Output . , Microprocessor Based Conventional Fire Alarm Control Panel , Can Accommodate Maximum Range Of 16 Zones , S . User Friendly Systems Which Involves A Touch Keypad To Program The Panel Operates On 120 - 220Vac 60 /50 Hz , Ac Mains Power Supply Standby ( Battery ) Backup 24 Vdc Power Supply With Built In Charger Zone Isolation Facility With Loop Voltage Cut Off . Resettable / Steady 24Vdc . Output . , Microprocessor Based Conventional Fire Alarm Control Panel , Can Accommodate Maximum Range Of 6 Zones , S . User Friendly Systems Which Involves A Touch Keypad To Program The Panel Operates On 120 - 220Vac 60 /50 Hz , Ac Mains Power Supply Standby ( Battery ) Backup 24 Vdc Power Supply With Built In Charger Zone Isolation Facility With Loop Voltage Cut Off . Resettable / Steady 24Vdc . Output . , Supply , Installation , Testing & Commissioning Of The Cable , Sitc Of Fire Alrm Cable- Pvc Insulated Fire Retardent Copper Flexible Cable A Sq . Mm With Isi Mark , Pvc Conduit . , Sitc Of 20Mm Dia Medium Grade Rigid Pvc Conduit With Isi Mark With Elbows , Tees , Junction Boxes , Saddle Clips With Necessary Fittings . , Smoke/Heat Detector , Sitc Of Optical Smoke/Heat Detector With Operating Voltage Range 12-24Vdc Min . , Application Temperature 30 - 70 Degree With Imported Base , Manual Call Point , Sitc Of Manual Call Point Break Glass Type Powder Coated Ms Box , 21/12 Vdc Operated , And With Necessary Attachment Like Hammer , Fire Hydrant System , Fire Brigade Connection , Sitc Of Fire Brigade Inlet Connection Fabricated From 100 Mm Dia . Ms Class B Medium Grade Pipe Three 63 Mm Dia . Gun Metal Male Threaded Non Return Valve . , Servicing And Testing Of Pumps , Hose Box , Valves Etc . , Servicing , Testing And Commissioning Of Existing Electrically Operated Fire Pump Of 75 Kw , Servicing , Testing And Commissioning Of Existing Electrically Operated Jockey Pump Of 5 . 5 Kw , Servicing , Testing And Commissioning Of Existing Electrically Operated Sprinkler Pump Of 44 . 5 Kw , Servicing , Testing And Commissioning Of Following Butter Fly Valves , 150/100/80 Mm Dia , Servicing , Testing And Commissioning Of Following Non Return Valves , 150/100/80 Mm Dia , Testin And Servicing Of Control Panel - Pump , Servicing , Testing And Commissioning Of Pressure Switch Having 1/4 Bsp ( F ) Connection Ip : 32 , Servicing , Testing And Commissioning Of Pressure Gauges 4 Dial , 0-200 Psi Range 3/8 Bsp Weather Proof Type . , Servicing , Testing And Commissioning Of Air Release Valve With Gun Metal Body , Servicing , Testing And Commissioning Of Air Cushion Vessel , Servicing , Testing And Commissioning Of Cast Iron Foot Valves Of Following Sizes , 200/150/100 Mm Dia . , Servicing , Testing And Commissioning Of Hydrant Valves Of 63Mm Dia . , Servicing , Testing And Commissioning Of Fire Fighting Hose , Servicing , Testing And Commissioning Of Hose Reel And Hose Reel Drum , Servicing , Testing And Commissioning Of Hose Box , Servicing , Testing And Commissioning Of Branch Pipe , Fire Extinguishers , Sitc Of Providing And Fixing Of Stored Pressure Abc Type Fire Extinguishers Of Capacity 6Kg As Per As Per Is 15683 : 2006 And Ce Certificate Consisting Of Welded Ms Cylindrical Body Of , With Control Valve , Syphon Tube , Discharge Nozzle , Hose , Neck Ring With Fire Rating 3A 21 B , Working Temperature -10 To 550C , Testing Pressure 35 Bar , Discharge Range 2 Meter , 90% Discharge Percentage With Helium Leak Detection Tested To 10-7 Mbar L/S And Hanging Arrangement In Appropriate Locations Of The Building Complete , Sitc Of Portable Watermist Based Extinguishers Of 6 Liters Capacity Which Fights Fires Of Class A , Class E And Class F Rating With Discharge Time Of Min . 9 Sec . And A Range Of Min . 2 Meters Welded Cylindrical Ms/Ss Body And A Hanging Arrangement In Appropriate Location As Per The Instruction Of Engineer In Charge , Test Certificate/Noc , Laison Work For Effective Approval In Writing , Contractor Shall Prepare And Submit Drawing And Other Necessary Documents , Attend All Tests And Inspections Carried Out By Local Fire Authorities , And Shall Forthwith Execute Free Of Charge If Any Rectifications Work Ordered By The Engineer- In- Charge As A Result Of Such Tests And Inspections Where These Indicate Non-Compliance With Statutory Regulations . All The Expenses Incurred In This Regard Shall Be Borne By The Contractor . The Official Payments To Be Made For Any Security Deposit Etc . In This Regard Which Shall Be Reimbursed On Production Of Original Vouncher .
BOQ
| Name of Work: URGENT RECTIFICATION WORKS AND PROVISION OF FIREFIGHTING EQUIPMENTS AT A, B, C & D BLOCK OF RCC, THIRUVANANTHAPURAM | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1.01 | FIRE DETECTION & ALARM SYSTEM | |||
| 2 | 1.02 | Supply, Installation, Testing & Commissioning of the Fire Alarm System consisting of the following | |||
| 3 | 1.03 | Microprocessor based conventional Fire Alarm Control Panel, can accommodate maximum range of 32 zones, s.User friendly systems which involves a touch keypad to program the panel Operates on 120 - 220VAC 60 /50 Hz, AC mains power supply Standby (battery) backup 24 VDC power supply with built in charger Zone Isolation facility with loop voltage cut off.Resettable / Steady 24VDC. Output. | item1 | 1 | Nos |
| 4 | 1.04 | Microprocessor based conventional Fire Alarm Control Panel, can accommodate maximum range of 24 zones, s.User friendly systems which involves a touch keypad to program the panel Operates on 120 - 220VAC 60 /50 Hz, AC mains power supply Standby (battery) backup 24 VDC power supply with built in charger Zone Isolation facility with loop voltage cut off.Resettable / Steady 24VDC. Output. | item2 | 1 | Nos |
| 5 | 1.05 | Microprocessor based conventional Fire Alarm Control Panel, can accommodate maximum range of 16 zones, s.User friendly systems which involves a touch keypad to program the panel Operates on 120 - 220VAC 60 /50 Hz, AC mains power supply Standby (battery) backup 24 VDC power supply with built in charger Zone Isolation facility with loop voltage cut off.Resettable / Steady 24VDC. Output. | item3 | 1 | Nos |
| 6 | 1.06 | Microprocessor based conventional Fire Alarm Control Panel, can accommodate maximum range of 6 zones, s.User friendly systems which involves a touch keypad to program the panel Operates on 120 - 220VAC 60 /50 Hz, AC mains power supply Standby (battery) backup 24 VDC power supply with built in charger Zone Isolation facility with loop voltage cut off.Resettable / Steady 24VDC. Output. | item4 | 1 | Nos |
| 7 | 1.07 | Supply, Installation, Testing & Commissioning of the cable | |||
| 8 | 1.08 | SITC of fire alrm cable- PVC insulated fire retardent copper flexible cable a sq.mm with ISI mark | item5 | 900 | RMT |
| 9 | 1.09 | PVC Conduit. | |||
| 10 | 1.1 | SITC of 20mm dia medium grade rigid PVC conduit with ISI mark with elbows, tees, junction boxes, saddle clips with necessary fittings. | item6 | 350 | RMT |
| 11 | 1.11 | Smoke/Heat Detector | |||
| 12 | 1.12 | SITC of optical smoke/heat detector with operating voltage range 12-24VDC min., application temperature 30 - 70 degree with imported base | item7 | 150 | Nos |
| 13 | 1.13 | Manual Call point | |||
| 14 | 1.14 | SITC of manual call point break glass type powder coated MS box, 21/12 VDC operated, and with necessary attachment like hammer | item8 | 12 | Nos |
| 15 | 1.15 | Fire Hydrant System | |||
| 16 | 1.16 | Fire Brigade Connection | |||
| 17 | 1.17 | SITC of fire brigade inlet connection fabricated from 100 mm dia. MS class B medium grade pipe three 63 mm dia. Gun metal male threaded non return valve. | item9 | 4 | Nos |
| 18 | 1.18 | Servicing and testing of Pumps, Hose box, Valves etc. | |||
| 19 | 1.19 | Servicing, Testing and Commissioning of existing electrically operated fire pump of 75 KW | item10 | 2 | Nos |
| 20 | 1.2 | Servicing, Testing and Commissioning of existing electrically operated jockey pump of 5.5 KW\n | item11 | 1 | Nos |
| 21 | 1.21 | Servicing, Testing and Commissioning of existing electrically operated Sprinkler pump of 44.5 KW\n | item12 | 1 | Nos |
| 22 | 1.22 | Servicing, Testing and Commissioning of following butter fly valves | |||
| 23 | 1.23 | 150/100/80 mm dia | item13 | 15 | Nos |
| 24 | 1.24 | Servicing, Testing and Commissioning of following Non return valves | |||
| 25 | 1.25 | 150/100/80 mm dia | item14 | 5 | Nos |
| 26 | 1.26 | Testin and Servicing of Control Panel - Pump | item15 | 1 | Nos |
| 27 | 1.27 | Servicing, Testing and Commissioning of Pressure switch having 1/4\" BSP (F) connection IP : 32 | item16 | 4 | Nos |
| 28 | 1.28 | Servicing, Testing and Commissioning of Pressure gauges 4\" dial, 0-200 PSI range 3/8\" BSP weather proof type. | item17 | 4 | Nos |
| 29 | 1.29 | Servicing, Testing and Commissioning of air release valve with gun metal body | item18 | 1 | Nos |
| 30 | 1.3 | Servicing, Testing and Commissioning of Air Cushion vessel | item19 | 1 | Nos |
| 31 | 1.31 | Servicing, Testing and Commissioning of cast iron foot valves of following sizes | |||
| 32 | 1.32 | 200/150/100 mm dia. | item20 | 4 | Nos |
| 33 | 1.33 | Servicing, Testing and Commissioning of hydrant valves of 63mm dia. | item21 | 41 | Nos |
| 34 | 1.34 | Servicing, Testing and Commissioning of fire fighting hose | item22 | 41 | Nos |
| 35 | 1.35 | Servicing, Testing and Commissioning of Hose Reel and Hose reel drum | item23 | 41 | Nos |
| 36 | 1.36 | Servicing, Testing and Commissioning of Hose box | item24 | 36 | Nos |
| 37 | 1.37 | Servicing, Testing and Commissioning of branch pipe | item25 | 6 | Nos |
| 38 | 1.38 | FIRE EXTINGUISHERS | |||
| 39 | 1.39 | SITC of Providing and fixing of stored pressure ABC type fire extinguishers of capacity 6Kg as per as per IS 15683 : 2006 and CE certificate consisting of welded MS Cylindrical body of , with control valve, Syphon tube, Discharge nozzle, hose, neck ring with fire rating 3A 21 B, working temperature -10 to 550C, testing pressure 35 bar, discharge range 2 meter, 90% discharge percentage with helium leak detection tested to 10-7 mbar l/s and hanging arrangement in appropriate locations of the building complete | item26 | 10 | Nos |
| 40 | 1.4 | SITC of Portable Watermist Based Extinguishers of 6 liters capacity which Fights fires of Class A, Class E and Class F rating with discharge time of min. 9 sec. and a range of min. 2 meters welded cylindrical MS/SS body and a hanging arrangement in appropriate location as per the instruction of Engineer in charge | item27 | 4 | Nos |
| 41 | 1.41 | TEST CERTIFICATE/NOC | |||
| 42 | 1.42 | Laison work for Effective approval in writing, Contractor shall prepare and submit drawing and other necessary documents, attend all tests and inspections carried out by Local Fire Authorities, and shall forthwith execute free of charge if any rectifications work ordered by the Engineer- in- charge as a result of such tests and inspections where these indicate non-compliance with statutory Regulations. All the expenses incurred in this regard shall be borne by the contractor. The official payments to be made for any security deposit etc. in this regard which shall be reimbursed on production of original vouncher. | item28 | 1 | Lot |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender