| 1 | 1 | Sch-A1 : Items for new 33/11 kV Substations | | | |
|---|
| 2 | 1.101 | 33/11 KV 2.5 MVA transformer with OLTC | PT-3-A1 | 10 | Nos. |
|---|
| 3 | 1.102 | 33 KV VCB ( 36KV,1250 A, 25KA) with G.I mounting structure | VCB33-A1 | 15 | Nos |
|---|
| 4 | 1.103 | 33 KV Relay & Control Panel for 33 KV Feeder 110 V DC ( with numeric relay & static TVM and communication port for SCADA) | RCP33-1-A1 | 5 | Nos |
|---|
| 5 | 1.104 | 33 KV Relay & Control Panel for 33 / 11 KV Transformer 110 V DC with out differential protection and with communication port for SCADA | RCP33-2-A1 | 10 | Nos |
|---|
| 6 | 1.105 | 33 KV Single Phase Multi Core C.T. 400-200/5-5 A ( for Feeders) | CT33-1-A1 | 15 | Nos. |
|---|
| 7 | 1.106 | 33 KV Single Phase Multi Core C.T. 100-50/5-5 A ( for Transformer) | CT33-2-A1 | 30 | Nos. |
|---|
| 8 | 1.107 | Mounting structure for 33 kV CTs | MCT33-A1 | 15 | Set |
|---|
| 9 | 1.108 | 33KV Single Phase PT outdoor type oil filled, 33KV/v3 - 110V /v3 ,class-0.2s, P.05, 20 VA | PT33-A1 | 15 | Nos. |
|---|
| 10 | 1.109 | Mounting structure for PT | MPT33-A1 | 5 | Set |
|---|
| 11 | 1.11 | 33 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch as per IS (for incoming feeders) | ISO33-1-A1 | 5 | Set |
|---|
| 12 | 1.111 | 33 KV , 800 Amp Isolators triple pole single throw manually operated without earth Blade/switch as per IS (for Transformers fdrs, PT, 33 KV incomers & DTR) | ISO33-2-A1 | 25 | Set |
|---|
| 13 | 1.112 | Mounting structure for 33 kV Isolater | MISO33-A1 | 30 | Set |
|---|
| 14 | 1.113 | 30 kV 10 KA LA Class II ZnO Station Type | LA33-1-A1 | 45 | Nos |
|---|
| 15 | 1.114 | Insulated base for 30 kV LA | LA33-X1-A1 | 45 | Nos |
|---|
| 16 | 1.115 | Surge counter for LA | LA33-X2-A1 | 45 | Nos |
|---|
| 17 | 1.116 | Mounting structure for LA | MLA-A1 | 15 | Set |
|---|
| 18 | 1.117 | 30 kV 10 KA LA Class II ZnO Distribution Class (line type) for station supply DTR with mounting structure | LA33-2-A1 | 15 | Nos |
|---|
| 19 | 1.118 | 11 KV Indoor 1250 A VCB Control and relay panel with 300-150/5/5 Amp CT, Static TVM and communication port for SCADA (for O/G feeders) | RCP11-1-A1 | 30 | Nos |
|---|
| 20 | 1.119 | 11 KV Indoor 1250 A VCB Control and Relay panel with 300-150/5/5/5 Amp CT with static TVM and communication port for SCADA ( for Incomer) | RCP11-2-A1 | 10 | Nos |
|---|
| 21 | 1.12 | 11 KV Indoor 1250 A VCB Control and relay panel with 300/5 Amp CT for incomer for bus coupler | RCP11-3-A1 | 5 | Nos |
|---|
| 22 | 1.121 | 11 kV lightning arrestor (9KV, 10KA), station type (for Transformers) | LA11-1-A1 | 30 | Nos |
|---|
| 23 | 1.122 | Mounting structure for 11 kV LA | MLA11-A1 | 10 | Set |
|---|
| 24 | 1.123 | 11 KV lightning Arrestor (9 kV, 10 kA) line type with disconnector & GI mounting Structure (for O/G feeders) | LA11-2-A1 | 90 | Nos |
|---|
| 25 | 1.124 | 11 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch as per IS (for transformers) | ISO11-1-A1 | 10 | Set |
|---|
| 26 | 1.125 | Mounting structure for 11 kV Isolator | MISO11-A1 | 10 | Set |
|---|
| 27 | 1.126 | 33/0.4 KV 100 KVA Station Service Transformer | DTR33-A1 | 5 | Nos |
|---|
| 28 | 1.127 | 33 KV HG fuse unit for station service transformer | HGF33-A1 | 5 | Set |
|---|
| 29 | 1.128 | Mounting Structure for 33KV H.G Fuse | MHGF33-A1 | 5 | Set |
|---|
| 30 | 1.129 | DTR LT Cubicle with bus bar and 2 Nos Outging MCCB's for Station Service Transformer (outdoor) | DTR33-X1-A1 | 5 | Set |
|---|
| 31 | 1.13 | Battery Bank (150 AH, 110 V) | BB110-A1 | 5 | Set |
|---|
| 32 | 1.131 | Battery Charger with DCDB | BB110-X1-A1 | 5 | Set |
|---|
| 33 | 1.132 | LT ACDB with 1 incomer + 6 O/G + 3 phase Static CT Operated Energy meter | ACDB-A1 | 5 | Set |
|---|
| 34 | 1.133 | 2.5 Sqmm 16 core Control Cable | CC-1-A1 | 3000 | Mtr |
|---|
| 35 | 1.134 | 2.5 Sqmm 4 core Control Cable | CC-2-A1 | 7000 | Mtr |
|---|
| 36 | 1.135 | 2.5 Sqmm 2 core Control Cable | CC-3-A1 | 3000 | Mtr |
|---|
| 37 | 1.136 | LT 10 Sqmm 1 core PVC Copper Cable | LTC-1-A1 | 500 | Mtr |
|---|
| 38 | 1.137 | LT XLPE Cable 1-core 120 Sq.mm. | LTC-2-A1 | 3000 | Mtr |
|---|
| 39 | 1.138 | 11 kV XLPE Cable 1-core 240 Sq.mm. | UG11-1-A1 | 3000 | Mtr |
|---|
| 40 | 1.139 | 11 KV XLPE cable 1 core, 185 sqmm | UG11-3-A1 | 9000 | Mtr |
|---|
| 41 | 1.14 | 11 kV XLPE Cable 1-core 240 Sq.mm. Termination Kit (Indoor) | UG11-1X1-A1 | 30 | Set |
|---|
| 42 | 1.141 | 11 KV XLPE cable 1 core, 185 sqmm Termination Kit (Indoor) | UG11-3X1-A1 | 90 | Set |
|---|
| 43 | 1.142 | 11 kV XLPE Cable 1-core 240 Sq.mm. Termination Kit (Outdoor) | UG11-1X2-A1 | 30 | Set |
|---|
| 44 | 1.143 | 11 KV XLPE cable 1 core, 185 sqmm Termination Kit (Outdoor) | UG11-3X2-A1 | 90 | Set |
|---|
| 45 | 1.144 | LT PVC Cable two core 25 sq mm (Aluminium) | LTC-3-A1 | 3000 | Mtr. |
|---|
| 46 | 1.145 | Bi-metallic lug (assorted) | BML-A1 | 150 | Nos |
|---|
| 47 | 1.146 | Switchyard Area Lighting : | | | |
|---|
| 48 | 1.147 | Floodlighting (LED) 35W 6000K with waterproof fixture incl all accessories | SL-A1 | 80 | Nos |
|---|
| 49 | 1.148 | Street Lighting G.I Poles (8 m) | SLP-A1 | 20 | Nos |
|---|
| 50 | 1.149 | 2-core, 4sqmm. 1000 V grade PVC copper Cable | LTC-4-A1 | 2000 | Mtr |
|---|
| 51 | 1.15 | Termination lug for above | LTC4-X1-A1 | 320 | Nos |
|---|
| 52 | 1.151 | LT AC Panel for switchyard Lighting with light sensor / solenoid switch | SL-X1-A1 | 5 | Set |
|---|
| 53 | 1.152 | GI Conduits 20 mm | SL-X2-A1 | 750 | Mtr |
|---|
| 54 | 1.153 | Bus System and Support Structure: | | | |
|---|
| 55 | 1.154 | Switchyard Support Structure (G.I. lattice structure) with fdn bolts including Nut & bolts | SWS-A1 | 45 | MT |
|---|
| 56 | 1.155 | TEE Clamp for wolf | TCL-1-A1 | 90 | Nos |
|---|
| 57 | 1.156 | ACSR Wolf Conductor | ACSR-1-A1 | 3 | Km |
|---|
| 58 | 1.157 | 33 kV Disc Insulator 70 KN | DI33-A1 | 225 | Nos |
|---|
| 59 | 1.158 | Hardware fittings with Tension Clamp for wolf | DI33-X1-A1 | 225 | Nos |
|---|
| 60 | 1.159 | UPG Clamp for wolf | ACSR1-X1-A1 | 60 | Nos |
|---|
| 61 | 1.16 | 33KV Post Insulator with accessories | PI33-A1 | 60 | Nos |
|---|
| 62 | 1.161 | Mandatory spare parts and Other Equipment : | | | |
|---|
| 63 | 1.162 | 3 kg Co2 Fire Extinguisher + Sand Bucket | CO2-A1 | 30 | Set |
|---|
| 64 | 1.163 | Furniture and equipment for Substation Control Rooms (Annexure FR) | FR-A1 | 5 | Lot |
|---|
| 65 | 1.164 | Mandatory spare parts & tools for substations (Annexture MS - List 1) | MSP-1-A1 | 5 | Lot |
|---|
| 66 | 1.165 | Mandatory spare parts & tools for Circle (Annexture MS - List 2) | MSP-2 | 1 | Lot |
|---|
| 67 | 1.166 | Evacuation of 11kV power: | | | |
|---|
| 68 | 1.167 | Galvanized S.T. poles, 410 sp-39, 9.5m | STP-1-A1 | 60 | Nos |
|---|
| 69 | 1.168 | 11 kV GO-AB Switch , channel base, 400A (for 11 KV O/G Fdrs ) | GOAB11-A1 | 30 | Set |
|---|
| 70 | 1.169 | Channel cross arm, 75x40x4.8x2800mm | Ch-1-A1 | 210 | Nos |
|---|
| 71 | 1.17 | 11 kV Disc Insulator 70 KN | DI11-A1 | 90 | Nos |
|---|
| 72 | 1.171 | Hardware fittings with tension clamp for Raccoon | DI11-X1-A1 | 90 | Set |
|---|
| 73 | 1.172 | 11 kV pin insulators with GI pin. | PI11-A1 | 90 | Nos |
|---|
| 74 | 1.173 | Jam clamp 9.5M top | Cl-1-A1 | 60 | Nos |
|---|
| 75 | 1.174 | Pole clamp 9.5M top | Cl-2-A1 | 60 | Nos |
|---|
| 76 | 1.175 | Pole clamp 9.5M middle | Cl-3-A1 | 120 | Nos |
|---|
| 77 | 1.176 | Pole clamp 9.5M bottom | Cl-4-A1 | 120 | Nos |
|---|
| 78 | 1.177 | HT stay Set | SSHT-A1 | 60 | Nos |
|---|
| 79 | 1.178 | GI Through bolt 5/8x10' inch | BT-1-A1 | 210 | Nos |
|---|
| 80 | 1.179 | MS bolt 5/8x4' inch | BT-2-A1 | 144 | kg |
|---|
| 81 | 1.18 | G.I Pipe for 11 KV Cables riser on poles (75 mm Dia) | GIP-1-A1 | 300 | Mtr |
|---|
| 82 | 1.181 | Switchyard Earthing and Other Items : | | | |
|---|
| 83 | 1.182 | Earthmat Materials as per (Annexure ES) | EMM-A1 | 5 | Lot |
|---|
| 84 | 1.183 | Safety Insulation mat for indoor 11 kv Switchgear Panels 1m width | SM11-A1 | 50 | Mtr |
|---|
| 85 | 1.184 | Other minor items for completion of the works (SCh-A1) | MI-A1 | 5 | Lot |
|---|
| 86 | 2 | Sch-A2 Items for augmentation / upgrading of existing substations | | | |
|---|
| 87 | 2.101 | 33/11 KV 10 MVA transformer with OLTC | PT-1-A2 | 2 | Nos |
|---|
| 88 | 2.102 | 33/11 KV 5 MVA transformer with OLTC | PT-2-A2 | 2 | Nos |
|---|
| 89 | 2.103 | 33/11 KV 2.5 MVA transformer with OLTC | PT-3-A2 | 7 | Nos |
|---|
| 90 | 2.104 | 33 KV VCB ( 36KV,1250 A, 25KA) with G.I mounting structure | VCB33-A2 | 26 | Nos |
|---|
| 91 | 2.105 | 33 KV Relay & Control Panel for 33 KV Feeder 110 V DC ( with numeric relay & static TVM and communication port for SCADA) | RCP33-1-A2 | 14 | Nos |
|---|
| 92 | 2.106 | 33 KV Relay & Control Panel for 33 / 11 KV Transformer 110 V DC with out differential protection and with communication port for SCADA | RCP33-2-A2 | 14 | Nos |
|---|
| 93 | 2.107 | 33 KV Relay & Control Panel for 33 / 11 KV Transformer 110 V DC with differential protection and communication port for SCADA | RCP33-3-A2 | 2 | Nos |
|---|
| 94 | 2.108 | 33 KV Single Phase Multi Core C.T. 400-200/5-5 A ( for Feeders) | CT33-1-A2 | 42 | Nos. |
|---|
| 95 | 2.109 | 33 KV Single Phase Multi Core C.T. 100-50/5-5 A ( for Transformer) | CT33-2-A2 | 36 | Nos. |
|---|
| 96 | 2.11 | 33 KV Single Phase Multi Core C.T. 200-100/5-5-5 A ( for Transformer) | CT33-3-A2 | 6 | Nos. |
|---|
| 97 | 2.111 | Mounting structure for 33 kV CTs | MCT33-A2 | 28 | Set |
|---|
| 98 | 2.112 | 33KV Single Phase PT outdoor type oil filled, 33KV/v3 - 110V /v3 ,class-0.2s, P.05, 20 VA | PT33-A2 | 18 | Nos |
|---|
| 99 | 2.113 | Mounting structure for PT | MPT33-A2 | 6 | Set |
|---|
| 100 | 2.114 | 33 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch as per IS (for incoming feeders) | ISO33-1-A2 | 15 | Set |
|---|
| 101 | 2.115 | 33 KV , 800 Amp Isolators triple pole single throw manually operated without earth Blade/switch as per IS (for Transformers fdrs, PT, 33 KV incomers & DTR) | ISO33-2-A2 | 39 | Set |
|---|
| 102 | 2.116 | Mounting structure for 33 kV Isolater | MISO33-A2 | 54 | Set |
|---|
| 103 | 2.117 | 30 kV 10 KA LA Class II ZnO Station Type | LA33-1-A2 | 81 | Nos |
|---|
| 104 | 2.118 | Insulated base for 30 kV LA | LA33-X1-A2 | 81 | Nos |
|---|
| 105 | 2.119 | Surge counter for LA | LA33-X2-A2 | 81 | Nos |
|---|
| 106 | 2.12 | Mounting structure for LA | MLA-A2 | 27 | Set |
|---|
| 107 | 2.121 | 30 kV 10 KA LA Class II ZnO Distribution Class (line type) for station service DTR with mounting structure | LA33-2-A2 | 21 | Nos |
|---|
| 108 | 2.122 | 11 KV Indoor 1250 A VCB Control and relay panel with 300-150/5/5 Amp CT, Static TVM and communication port for SCADA (for O/G feeders) | RCP11-1-A2 | 38 | Nos |
|---|
| 109 | 2.123 | 11 KV Indoor 1250 A VCB Control and Relay panel with 300-150/5/5/5 Amp CT with static TVM and communication port for SCADA ( for Incomer) | RCP11-2-A2 | 12 | Nos |
|---|
| 110 | 2.124 | 11 KV Indoor 1250 A VCB Control and relay panel with 300/5 Amp CT for incomer for bus coupler | RCP11-3-A2 | 6 | Nos |
|---|
| 111 | 2.125 | 11 kV lightning arrestor (9KV, 10KA), station type (for Transformers) | LA11-1-A2 | 36 | Nos |
|---|
| 112 | 2.126 | Mounting structure for 11 kV LA | MLA11-A2 | 12 | Set |
|---|
| 113 | 2.127 | 11 KV lightning Arrestor (9 kV, 10 kA) line type with disconnector & GI mounting Structure (for O/G feeders) | LA11-2-A2 | 114 | Nos |
|---|
| 114 | 2.128 | 11 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch as per IS (for transformers) | ISO11-1-A2 | 12 | Set |
|---|
| 115 | 2.129 | Mounting structure for 11 kV Isolator | MISO11-A2 | 12 | Set |
|---|
| 116 | 2.13 | 33/0.4 KV 100 KVA Station Service Transformer | DTR33-A2 | 7 | Nos |
|---|
| 117 | 2.131 | 33 KV HG fuse unit for station service transformer | HGF33-A2 | 7 | Set |
|---|
| 118 | 2.132 | Mounting Structure for 33KV H.G Fuse | MHGF33-A2 | 7 | Set |
|---|
| 119 | 2.133 | DTR LT Cubicle with bus bar and 2 Nos Outging MCCB's for Station Service Transformer (outdoor) | DTR33-X1-A2 | 7 | Set |
|---|
| 120 | 2.134 | Battery Bank (150 AH, 110 V) | BB110-A2 | 6 | Set |
|---|
| 121 | 2.135 | Battery Charger with DCDB | BB110-X1-A2 | 6 | Set |
|---|
| 122 | 2.136 | LT ACDB with 1 incomer + 6 O/G + 3 phase Static CT Operated Energy meter | ACDB-A2 | 6 | Set |
|---|
| 123 | 2.137 | 2.5 Sqmm 16 core Control Cable | CC-1-A2 | 5100 | Mtr |
|---|
| 124 | 2.138 | 2.5 Sqmm 4 core Control Cable | CC-2-A2 | 11150 | Mtr |
|---|
| 125 | 2.139 | 2.5 Sqmm 2 core Control Cable | CC-3-A2 | 5100 | Mtr |
|---|
| 126 | 2.14 | LT 10 Sqmm 1 core PVC Copper Cable | LTC-1-A2 | 600 | Mtr |
|---|
| 127 | 2.141 | LT XLPE Cable 1-core 120 Sq.mm. | LTC-2-A2 | 3600 | Mtr |
|---|
| 128 | 2.142 | 11 kV XLPE Cable 1-core 240 Sq.mm. | UG11-1-A2 | 4200 | Mtr |
|---|
| 129 | 2.143 | 11 kV XLPE Cable 1-core 400 Sq.mm. | UG11-2-A2 | 600 | Mtr |
|---|
| 130 | 2.144 | 11 KV XLPE cable 1 core, 185 sqmm | UG11-3-A2 | 11700 | Mtr |
|---|
| 131 | 2.145 | 11 kV XLPE Cable 1-core 240 Sq.mm. Termination Kit (Indoor) | UG11-1X1-A2 | 42 | Set |
|---|
| 132 | 2.146 | 11 kV XLPE Cable 1-core 400 Sq.mm. Termination Kit (Indoor) | UG11-2X1-A2 | 6 | Set |
|---|
| 133 | 2.147 | 11 KV XLPE cable 1 core, 185 sqmm Termination Kit (Indoor) | UG11-3X1-A2 | 114 | Set |
|---|
| 134 | 2.148 | 11 kV XLPE Cable 1-core 240 Sq.mm. Termination Kit (Outdoor) | UG11-1X2-A2 | 42 | Set |
|---|
| 135 | 2.149 | 11 kV XLPE Cable 1-core 400 Sq.mm. Termination Kit (Outdoor) | UG11-2X2-A2 | 6 | Set |
|---|
| 136 | 2.15 | 11 KV XLPE cable 1 core, 185 sqmm Termination Kit (Outdoor) | UG11-3X2-A2 | 126 | Set |
|---|
| 137 | 2.151 | LT PVC Cable two core 25 sq mm (Aluminium) | LTC-3-A2 | 3600 | Mtr. |
|---|
| 138 | 2.152 | Bi-metallic lug (assorted) | BML-A2 | 180 | Nos |
|---|
| 139 | 2.153 | Switchyard Area Lighting :- | | | |
|---|
| 140 | 2.154 | Floodlighting (LED) 35W 6000K with waterproof fixture incl all accessories | SL-A2 | 102 | Nos |
|---|
| 141 | 2.155 | Street Lighting G.I Poles (8 m) | SLP-A2 | 24 | Nos |
|---|
| 142 | 2.156 | 2-core, 4sqmm. 1000 V grade PVC copper Cable | LTC-4-A2 | 2600 | Mtr |
|---|
| 143 | 2.157 | Termination lug for above | LTC4-X1-A2 | 408 | Nos |
|---|
| 144 | 2.158 | LT AC Panel for switchyard Lighting with light sensor / solenoid switch | SL-X1-A2 | 7 | Set |
|---|
| 145 | 2.159 | GI Conduits 20 mm | SL-X2-A2 | 950 | Mtr |
|---|
| 146 | 2.16 | Bus System and Support Structure: | | | |
|---|
| 147 | 2.161 | Switchyard Support Structure (G.I. lattice structure) with fdn bolts including Nut & bolts | SWS-A2 | 65 | MT |
|---|
| 148 | 2.162 | TEE Clamp for wolf | TCL-1-A2 | 195 | Nos |
|---|
| 149 | 2.163 | ACSR Wolf Conductor | ACSR-1-A2 | 7.05 | Km |
|---|
| 150 | 2.164 | 33 kV Disc Insulator 70 KN | DI33-A2 | 432 | Nos |
|---|
| 151 | 2.165 | Hardware fittings with Tension Clamp for wolf | DI33-X1-A2 | 432 | Nos |
|---|
| 152 | 2.166 | UPG Clamp for wolf | ACSR1-X1-A2 | 141 | Nos |
|---|
| 153 | 2.167 | 33KV Post Insulator with accessories | PI33-A2 | 129 | Nos |
|---|
| 154 | 2.168 | Mandatory spare parts and Other Equipment : | | | |
|---|
| 155 | 2.169 | 3 kg Co2 Fire Extinguisher + Sand Bucket | CO2-A2 | 51 | Set |
|---|
| 156 | 2.17 | Furniture and equipment for Substation Control Rooms (Annexure FR) | FR-A2 | 8 | Lot |
|---|
| 157 | 2.171 | Mandatory spare parts & tools for substations (Annexture MS - List 1) | MSP-1-A2 | 8 | Lot |
|---|
| 158 | 2.172 | Evacuation of 11kV power: | | | |
|---|
| 159 | 2.173 | Galvanized S.T. poles, 410 sp-39, 9.5m | STP-1-A2 | 80 | Nos |
|---|
| 160 | 2.174 | 11 kV GO-AB Switch , channel base, 400A (for 11 KV O/G Fdrs ) | GOAB11-A2 | 40 | Set |
|---|
| 161 | 2.175 | Channel cross arm, 75x40x4.8x2800mm | Ch-1-A2 | 280 | Nos |
|---|
| 162 | 2.176 | 11 kV Disc Insulator 70 KN | DI11-A2 | 120 | Nos |
|---|
| 163 | 2.177 | Hardware fittings with tension clamp for Raccoon | DI11-X1-A2 | 120 | Set |
|---|
| 164 | 2.178 | 11 kV pin insulators with GI pin. | PI11-A2 | 120 | Nos |
|---|
| 165 | 2.179 | Jam clamp 9.5M top | Cl-1-A2 | 80 | Nos |
|---|
| 166 | 2.18 | Pole clamp 9.5M top | Cl-2-A2 | 80 | Nos |
|---|
| 167 | 2.181 | Pole clamp 9.5M middle | Cl-3-A2 | 160 | Nos |
|---|
| 168 | 2.182 | Pole clamp 9.5M bottom | Cl-4-A2 | 160 | Nos |
|---|
| 169 | 2.183 | HT stay Set | SSHT-A2 | 80 | Nos |
|---|
| 170 | 2.184 | GI Through bolt 5/8x10' inch | BT-1-A2 | 280 | Nos |
|---|
| 171 | 2.185 | MS bolt 5/8x4' inch | BT-2-A2 | 192 | kg |
|---|
| 172 | 2.186 | G.I Pipe for 11 KV Cables riser on poles (75 mm Dia) | GIP-1-A2 | 400 | Mtr |
|---|
| 173 | 2.187 | Switchyard Earthing and Other Items : | | | |
|---|
| 174 | 2.188 | Earthmat Materials as per (Annexure ES) | EMM-A2 | 9 | Lot |
|---|
| 175 | 2.189 | Safety Insulation mat for indoor 11 kv Switchgear Panels 1m width | SM11-A2 | 80 | Mtr |
|---|
| 176 | 2.19 | Other minor items for completion of the works (Sch-A2) | MI-A2 | 8 | Lot |
|---|
| 177 | 3 | Sch - A3 Items for 33kV Bay Extensions | | | |
|---|
| 178 | 3.101 | 33 KV VCB ( 36KV,1250 A, 25KA) with G.I mounting structure | VCB33-A3 | 1 | nos |
|---|
| 179 | 3.102 | 33 KV Single Phase Multi Core C.T. 400-200/5-5 A ( for Feeders) | CT33-1-A3 | 3 | nos |
|---|
| 180 | 3.103 | 33KV Single Phase PT outdoor type oil filled, 33KV/v3 - 110V /v3 ,class-0.2s, P.05, 20 VA | PT33-A3 | 3 | nos |
|---|
| 181 | 3.104 | 33 KV , 800 Amp Isolators triple pole single throw manually operated without earth Blade/switch | ISO33-2-A3 | 1 | Set |
|---|
| 182 | 3.105 | 33 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch | ISO33-1-A3 | 1 | Set |
|---|
| 183 | 3.106 | 30 kV 10 KA LA station class with insulated base, surge monitor & G.I mounting structure | LA33-1A-A3 | 3 | nos |
|---|
| 184 | 3.107 | 33 KV G.O./DO fuse unit 200 A/400 A | GODO-1-A3 | 1 | Set |
|---|
| 185 | 3.108 | 33 KV Relay & Control Panel for 33 KV Feeder 110 V DC ( with numeric relay & static TVM and communication port for SCADA) | RCP33-1-A3 | 1 | Nos |
|---|
| 186 | 3.109 | 2.5 Sqmm 16 core Control Cable | CC-1-A3 | 100 | Mtr |
|---|
| 187 | 3.11 | 2.5 Sqmm 4 core Control Cable | CC-2-A3 | 200 | Mtr |
|---|
| 188 | 3.111 | LT 10 Sqmm 1 core PVC Copper Cable | LTC-1-A3 | 150 | Mtr. |
|---|
| 189 | 3.112 | Switchyard Support Structure (G.I. lattice structure) with fdn bolts including Nut & bolts | SWS-A3 | 8 | MT |
|---|
| 190 | 3.113 | UPG Clamp for wolf | ACSR1-X1-A3 | 12 | Nos |
|---|
| 191 | 3.114 | ACSR Wolf Conductor | ACSR-1-A3 | 200 | Mtr |
|---|
| 192 | 3.115 | 33 kV Disc Insulator 70 KN | DI33-A3 | 36 | Nos |
|---|
| 193 | 3.116 | Hardware fittings with Tension Clamp for wolf | DI33-X1-A3 | 12 | Nos |
|---|
| 194 | 3.117 | Other minor items for completion of the works (Sch-A3) | MI-A3 | 1 | Lot |
|---|