Military Engineer Services-MES has published Repair Maintenance And Overhauling Of Dg Sets Crane Incinetor Sirens Battery Charger Including Replacement Of Worn Out Parts And Connected Controlling Accessories At Mil Stn Agartala Under Age I Agartala. Submission Date for this Tender is 31-10-2019. Battery Chargers Tenders in AGARTALA Tripura. Bidders can get complete Tender details and download the document.
Name of Work: REPAIR, MAINT AND OVERHAULING OF DG SETS, CRANE, INCINETOR, SIRENS, BATTERY CHARGER INCLUDING REPLACEMENT OF WORN OUT PARTS AND CONNECTED CONTROLLING ACCESSORIES AT MIL STN AGARTALA | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 0.01 | Schedule'A' Part-I: E&M works | |||
2 | 1 | Dismantling and supply and fixing for air filter element suitable for 45 KVA Crompton Greaves DG set , all as specified and directed . | 4 | Each set | |
3 | 1.01 | All as per item No.1.00 here-in-before but for 30 KVA | 1 | Each | |
4 | 2 | Dismantling , taking out complete engine head assembly of 30 KVA CROMPTON GREAVES ,3YDA,MK-3 from engine block for replacement of unserviceable parts/ spares/accessories/mounting and reassembling after replacement complete and testing all as specified and directed. Note : New parts/ spares /accessories / mounting shall be paid separately as supply only under relevant items here in below | 1 | Each Job | |
5 | 2.01 | Supply only 'O' ring suitable for 30 KVA ,CG ,3 YDA DG set | 1 | Each set | |
6 | 2.02 | Supply only cylinder head Gasket suitable for 30 KVA ,CG ,3 YDA DG set | 1 | Each set | |
7 | 2.03 | Supply only piston with piston ring set and gudgen pin complete suitable for 30 KVA ,CG ,3 YDA DG set | 3 | Each set | |
8 | 2.04 | Supply only cylinder liner suitable for 30 KVA ,CG ,3 YDA DG set | 2 | Each | |
9 | 2.05 | Supply only small end and big end bearing suitable for 30 KVA ,CG ,3 YDA DG set | 3 | Each pair | |
10 | 3 | Drain out existing old engine oil, cleaning sump by K-oil and supply and filling new engine oil 20W 40 Grade Castrol CRB all as specified and directed. Make : Castrol | 130 | Litres | |
11 | 4 | Dismantling and supply and fixing PVC ,armoured fuel pipe from tank to DG Set (Over flow and incoming both) in various installation as per sample all as specified and directed. | 40 | R/M | |
12 | 5 | Disconnecting the Radiator complete from DG set , taking into workshop for cleaning fines by cleaning agent , brazing into damaged fines , water circulation tubes etc,. Taking back to installation ,refixing into original position including supply and replacement of rubber hose pipes complete set of Kirloskar make 45/30 KVA DG set all as specified and directed. | 6 | Each Job | |
13 | 6 | Disconnect ,removing burnt carbon brush with holder assembly and supply and fixing new carbon brush with holder assembly suitable for 'Kirloskar ' 45 KVA ,3 Ph ,4 wire 440 Volt,RB -44 , DG set all as specified and directed. | 1 | Each set | |
14 | 7 | Cleaning entire structure of crane 2 to 5 Ton capacity .Remove all grease and oil from crane parts ,including railing ramp etc.Painting of crane with existing paint colour of two coat over red oxide primer complete all as specified and directed. | 2 | Each Job | |
15 | 8 | M & L for changing of gear oil of grane Type EP-320 thick level (Make : Monex) including cleaning of gear box by Engine oil complete all as specified and directed. | 30 | Litres | |
16 | 9 | Disconnecting ,nut and bolt ,taking out existing ant vibration generating mounting pad , supply and fixing of new ant vibration generating mounting pad suitable to resist withstand the load of 30/45 KVA DG set confirm to ISO certified , all as specified and directed . Make : Poly band or Equivalent make | 12 | Each | |
17 | 10 | Dismantling and supply and fixing for flexible Asbestos rope of 80 to 150mm dia insulation into DG Set exhaust pipe including taking down existing burnt rope all as specified and directed . | 18 | Kgs | |
18 | 11 | Taking down DG set from existing platform by disconnecting electrical cables , Battery terminals, exhaust silencer pipes ,earthing connections etc and shifted to safe place . After raising platform , floors (separate measurable items), re installation to DG set with all connected accessories , testing and commissioning etc all as specified and directed of DG set of Kirloskar 45 KVA/30 KVA . | 1 | Each Job | |
19 | 12 | S&F for Onload Changeover Switch, AC 23 (side handle), 100 Amp, 415 volts, 50 Hz in sheet enclosure with side handle including making incoming and outgoing connections complete all as specified and directed Make: Cat No. IHCFFE0100 of Havells or equivalent in Legrand/Indoasian | 2 | Each | |
20 | 13 | S&F for Change over Switch ,four pole 63 Amp, 415 volts, 50 Hz in sheet enclosure with side handle ,conforming to IS/IEC 60947-1&3 including making incoming and outgoing connections complete all as specified and directed Make : Cat No. IHCFFE0063 of Havells or equivalent in Legrand/Indoasian | 3 | Each | |
21 | 14 | Disconnect ,and supply and fixing fuel filter element suitable for following make and capacity of DG set , all as specified and directed . | |||
22 | 14.01 | (i) Kirloskar , 45 KVA,HA 49 4TC | 1 | Each Set | |
23 | 14.02 | (ii) Kirloskar ,45 KVA,RB-44 | 1 | Each Set | |
24 | 14.03 | (iiI) Kirloskar ,30 KVA,RB-33 | 3 | Each Set | |
25 | 14.04 | (iv) Kirloskar ,30 KVA,3R104D | 1 | Each Set | |
26 | 14.05 | (v) C Greaves ,30 KVA ,3YDA MK-3 | 1 | Each Set | |
27 | 14.06 | (vi) C Greaves ,45 KVA ,4YDA MK-3 | 4 | Each Set | |
28 | 14.07 | (vii) C Greaves ,100 KVA ,4YDA MK-3 | 1 | Each Set | |
29 | 15 | Disconnecting nuts and bolts ,taking down existing unserviceable self starter and supply and fixing new self starter consisting of starter pinion ,gear spindle ,coupling housing , pre-tension spring complete suitable to start 45 KVA Crompton Greaves DG Set and having operating voltage 12 V,DC including all fixing arrangement all as specified and directed . | 1 | Each | |
30 | 16 | Disconnecting nuts and bolts ,taking down existing unserviceable self starter and supply and fixing new self starter consisting of starter pinion ,gear spindle ,coupling housing , pre-tension spring complete suitable to start 30 KVA Kirloskar DG Set and having operating voltage 12 V,DC including all fixing arrangement all as specified and directed . | 2 | Each | |
31 | 17 | Disconnect ,and supply and fixing lubricant oil filter element suitable for following make and capacity of DG set , all as specified and directed . | |||
32 | 17.01 | (i) Kirloskar , 45 KVA,HA 49 4TC | 1 | Each | |
33 | 17.02 | (ii) Kirloskar ,45 KVA,RB-44 | 1 | Each | |
34 | 17.03 | (iiI) Kirloskar ,30 KVA,RB-33 | 3 | Each | |
35 | 17.04 | (iv) Kirloskar ,30 KVA,3R104D | 1 | Each | |
36 | 17.05 | (v) C Greaves ,30 KVA ,3YDA MK-3 | 1 | Each | |
37 | 17.06 | (vi) C Greaves ,45 KVA ,4YDA MK-3 | 4 | Each | |
38 | 17.07 | (vii) C Greaves ,100 KVA ,4YDA MK-3 | 1 | Each | |
39 | 18 | S&F for MCCB four pole 100 Amp, 415 volts, 50 Hz having adjustable thermal setting range 70% to 100% and fixed magnetic setting (Ics = 75% of Icu) and breaking capacity 25 KA conforming to IS/IEC:60947-2, including making incoming and outgoing connections complete all as specified and directed Make : Havells Cat No. IHLASF0100# or equivalent in Legrant/ Indoasian | 1 | Each | |
40 | 19 | S&F for MCCB four pole 125 Amp, 415 volts, 50 Hz having adjustable thermal setting range 70% to 100% and fixed magnetic setting (Ics = 75% of Icu) and breaking capacity 25 KA conforming to IS/IEC:60947-2, including making incoming and outgoing connections complete all as specified and directed Make : Havells Cat No. IHLASF0125# or equivalent in Legrant/ Indoasian | 1 | Each | |
41 | 20 | Dismantling of fuel injectors from DG set ,segregation for serviceable and worn out parts ,carry out repair and replacement of worn out parts such as injector nozzle ,O-ring ,injector cup, injector barrel, injector plunger , including pressure testing and fitting to engine and testing the engine for proper functioning etc all as specified and directed . | |||
42 | 20.01 | (i) Kirloskar , 45 KVA,RB-44 | 4 | Each | |
43 | 20.02 | (ii) C Greaves,30KVA,3 YDA | 3 | Each | |
44 | 20.03 | (iiI) Kirloskar ,30 KVA,RB-33 | 3 | Each | |
45 | 21 | Disconnecting the Radiator complete from DG set , taking into workshop for cleaning fines by cleaning agent , brazing into damaged fines , water circulation tubes etc,. Taking back to installation ,refixing into original position including supply and replacement of rubber hose pipes complete set of Kirloskar make 45/30 KVA DG set all as specified and directed. | 6 | Each Job | |
46 | 22 | Dismantling and supply and fixing fan belt suitable for following DG Set all as Specified and directed .Make : Fenner or equivalent make | |||
47 | 22.01 | (i) Kirloskar , 45 KVA,HA 49 4TC | 1 | Each | |
48 | 22.02 | (ii) Kirloskar ,45 KVA,RB-44 | 1 | Each | |
49 | 22.03 | (iiI) Kirloskar ,30 KVA,RB-33 | 3 | Each | |
50 | 22.04 | (iv) Kirloskar ,30 KVA,3R104D | 1 | Each | |
51 | 22.05 | (v) C Greaves ,30 KVA ,3YDA MK-3 | 1 | Set of 3 | |
52 | 22.06 | (vi) C Greaves ,45 KVA ,4YDA MK-3 | 4 | Set of 3 | |
53 | 22.07 | (vii) C Greaves ,100 KVA ,4YDA MK-3 | 1 | Set of 3 | |
54 | 23 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of pipe and getting out in soft/loose soil all as directed and specified. | 38 | CUM | |
55 | 24 | Removing excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point. | 12 | CUM | |
56 | 25 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm all as specified and directed. | 28 | CUM | |
57 | 26 | M&L for sand cushioning to PVC/XLPE cable with river sand and punning to provide required cushioning to under ground cable all as specified and directed. Note :-Only punned thickness shall be taken for measurement | 14 | CUM | |
58 | 27 | Supplying and Laying sub class 'B' brick for protection of LT under ground cable laid dry, flat abutting each other with gaps between adjacent brick not exceeding 10mm after taking out the old unserviceable cable protection brick all as specified and directed. | 1060 | Each | |
59 | 28 | M&L Heavy duty armoured LT U/G cable of size 50 Sqmm 3.5 Core ,1100v grade,PVC insulated,PVC sheathed mutistranded aluminium cable passing through pipe/trench/cable duct/fixed on wall by proper size of GI clamps with nut and bolts etc ,making good the disturbed surface complete all as specified and as directed. | 85 | RM | |
60 | 29 | M&L Heavy duty armoured LT U/G cable of size 70 Sqmm 3.5 Core ,1100v grade,PVC insulated,PVC sheathed mutistranded aluminium cable passing through pipe/trench/cable duct/fixed on wall by proper size of GI clamps with nut and bolts etc ,making good the disturbed surface complete all as specified and as directed. | 80 | RM | |
61 | 30 | S&F GI steel tubing light grade for protection of cable on poles, under road crossing etc of 40 mm bore. | 20 | RM | |
62 | 31 | Dismantling of fuel injection pump from DG set ,segregating for serviceable and worn out parts such as timing shaft ,oil seal ,thrust bearing and other minor parts including testing all as specified and directed of following capacity of DG sets. | |||
63 | 31.01 | (i) Kirloskar , 45 KVA,RB-44 | 1 | Each Job | |
64 | 31.02 | (ii) C Greaves,30KVA,3 YDA | 1 | Each Job | |
65 | 31.03 | (iiI) Kirloskar ,30 KVA,RB-33 | 1 | Each Job | |
66 | 32 | M&L for Earthing complete in replacement with galvanised iron mild steel earth plate electrode 60 cm x 60 cm x 6.3mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to galvanised earth lead of GI strip of size 25mm x 4mm by means of GI Bolts, Nuts, check nuts and washers of the earth and thimbles and other end of the earth strip connected to earthing test point and protected by galvanised iron pipe light grade 40mm dia from earth plate to Panel and installations and water pipe 20mm dia GI medium grade raised upto a level of 50cm above ground level with plug at top, earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab of 100 mm thick using 8.00mm dia TMT bars @ 100mm C/C as reinforcement, 20 mm dia GI pipe medium grade for watering pipe, wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm including necessary earth work in soft/loose soil, returning, refilling and removing of surplus soil to a distance not of MES Schedule Part-I of SSR-2009 exceeding 50 mtr testing complete all as shown in electrical plate No-3 as specified and directed | 8 | Each Set | |
67 | 33 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to ploes or any other indicated situation for loop earthing etc. as required 32 x 6 mm Galvanaised iron strip complete all as specified and directed | 20 | RM | |
68 | 33.01 | All as per item No.33.00 here-in-before but for 25 x 4mm GI Strip | 24 | RM |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy