Repairs Replacement Of Distribution Board And Bldg Earthing Including Repair Maintenance Of Exhaust Fans Geysers Etc And Connected Works Of Wellington Station And Repair Servicing Of Dg Sets Amf Panels Solar Lights Solar Water Heaters Including Repai, Wellington-Tamil Nadu

Military Engineer Services-MES has published Repairs Replacement Of Distribution Board And Bldg Earthing Including Repair Maintenance Of Exhaust Fans Geysers Etc And Connected Works Of Wellington Station And Repair Servicing Of Dg Sets Amf Panels Solar Lights Solar Water Heaters Including Repai. Submission Date for this Tender is 25-10-2019. Electrification Work Tenders in Wellington Tamil Nadu. Bidders can get complete Tender details and download the document.




Tender Notice

22062167
Repairs Replacement Of Distribution Board And Bldg Earthing Including Repair Maintenance Of Exhaust Fans Geysers Etc And Connected Works Of Wellington Station And Repair Servicing Of Dg Sets Amf Panels Solar Lights Solar Water Heaters Including Repai
National Competitive Bid
Indian
Tamil Nadu
Wellington
25-10-2019

Tender Details

Repairs Replacement Of Distribution Board And Bldg Earthing Including Repair Maintenance Of Exhaust Fans Geysers Etc And Connected Works Of Wellington Station And Repair Servicing Of Dg Sets Amf Panels Solar Lights Solar Water Heaters Including Repai

Key Value

Document Fees
INR 500 /-
EMD
INR 40000.0 /-
Tender Value
INR 20 Lakhs /-

BOQ Items

Name of Work: REPAIRS / REPLACEMENT OF DISTRIBUTION BOARD AND BLDG EARTHING INCLUDING REPAIR MAINTENANCE OF EXHAUST FANS, GEYSERS, ETC AND CONNECTED WORKS OF WELLINGTON STATION AND REPAIR / SERVICING OF DG SETS, AMF PANELS, SOLAR LIGHTS, SOLAR WATER HEATERS INCLUDING REPAIR / REPLACEMENT OF LIGHTENING PROTECTION SYSTEM UNDER GE WELLINGTON.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking down unserviceable DBs with MCBs and Supply and fix MCB DB SPN 4 way 230 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. 10 EACH
2 2 Taking down unserviceable DBs including MCBs and Supply and fix MCB DB SPN 8 way 230 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. 5 EACH
3 3 Taking down unserviceable DBs including MCBs and Supply and fix MCB DB TPN 4 way 230 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. 5 EACH
4 4 Taking down unserviceable DBs of any type and supply and fixing weather proof IP rated, CPRI certified, Thermo Plastic Polycarbonate, dust and water protected, Anti corrosive, insulated, shock proof, UV Resistant Distribution Board with Hinges in individual compartments along with Transparent / Non-transparent combination all as specified and directed. Model : 1166L x 1168H x 206D of Make Hensel or Equivalent.\nGeneral Specification.\nType of enclosure: Thermoplastic Polycarbonate\nPanel SIze : 1166 x 1168 x 206mm\nBusbar Rating : 25 x 6mm (150A)\nDegree of protection : IP66, Indoor type wall mounted\nSystem Voltage : 415V, 50Hz, 4 Wire + E\nCable entry: IN/OUT from bottom\nFinish Shade\nEnclosure & Accessories : RAL 7035\nMounting structure : RAL 7016\nIncomer\n125A FP 25KA MCCB Microprocessor - 1 No\nRYB indicating lamps, 2A Fuse terminal blocks - 3 Nos\nDisconnecting terminal Block - 1 No\nOutgoing\n63A FP 25KA MCCB - 2Nos\n32A MCB DP, 10KA - 14 Nos\n63A FP 30Ma RCCB - 1 No\n10Sqmm terminal block 30A - 28 Nos\n16Sqmm terminal block - 4 Nos\n50Sqmm terminal block - 4 Nos\nCable in - 70Sqmm x 3.5 Core\nCable out -50Sqmm x 3.5 core- 1 No, 16Sqmm x 4 core-1No, 6Sqmm x 2 core -1 No\n 3 EACH
5 5 Taking down unserviceable DBs of any type and supply and fixing weather proof IP rated, CPRI certified, Thermo Plastic Polycarbonate, dust and water protected, Anti corrosive, insulated, shock proof, UV Resistant Distribution Board with Hinges in individual compartments along with Transparent / Non-transparent combination all as specified and directed. Model : DB4; Dim:896L x 628H x 206D of Make Hensel or Equivalent.\nGeneral Specification.\nType of enclosure: Thermoplastic Polycarbonate\nPanel SIze : 896 x 628 x 206mm\nBusbar Rating : 25 x 6mm (150A)\nDegree of protection : IP66, Indoor type wall mounted\nSystem Voltage : 415V, 50Hz, 4 Wire + E\nCable entry: IN/OUT from bottom\nFinish Shade\nEnclosure & Accessories : RAL 7035\nMounting structure : RAL 7016\nIncomer\n63A FP 25KA MCCB Microprocessor - 1 No\nRYB indicating lamps, 2A Fuse terminal blocks - 3 Nos\nDisconnecting terminal Block - 1 No\nOutgoing\n63A FP 30mA RCCB - 1No\n32A MCB DP, 10KA - 10 Nos\n6A SP 10KA MCB - 2 Nos\n10Sqmm terminal block 32A - 20 Nos\n16Sqmm terminal block - 4 Nos\n4Sqmm terminal block - 4 Nos\nCable in - 35Sqmm x 3.5 Core\nCable out -6Sqmm x 2 core -10 No, 16Sqmm x 4 core -1No, 2.5Sqmm x 2 core -2 Nos 3 EACH
6 6 MCB SP 230V 6-32 Amps capacity all as specified and directed. (Make: Havells Cat No DHMGCSPF006-032 or equivalent in Legrand / L&T) 40 EACH
7 7 MCB SPN 230V 6-32 Amps capacity all as specified and directed. (Make: Havells Cat No.DHMGCSNF006-032 or equivalent in Legrand / L&T) 20 EACH
8 8 MCB TPN 415V 40 Amp capacity all as specified and directed. (Make: Havells Cat No: DHMGCTNF063 or equivalent in Legrand / L&T) 10 EACH
9 9 Taking down unserviceable plug and socket and Supply and fix single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one 20amps SP MCB all as specified and directed 10 EACH
10 10 Taking down Submain wiring 2 x 4 Sqmm PVC insulated aluminium conductor along with PVC Conduit and Material and Labour for Submain wiring with 2 runs of FRLS grade PVC copper conductor cable 4 sqmm, multistranded along with FRLS grade PVC insulated copper earth continuity conductor 4 Sqmm drawn through and including PVC Conduit pipe 20 mm dia with all fittings all as specified and directed. 200 RM
11 11 All as per Item No 10 hereinbefore but with casing and caping all as specified and directed. 50 RM
12 12 Taking down Submain wiring 2 x 6 Sqmm PVC insulated aluminium conductor along with PVC Conduit and Material and Labour for Submain wiring with 2 runs of FRLS grade PVC copper conductor cable 6 sqmm, multistranded along with FRLS grade PVC insulated copper earth continuity conductor 6 Sqmm drawn through and including PVC Conduit pipe 20 mm dia with all fittings all as specified and directed. 80 RM
13 13 All as per Item No 12 hereinbefore but in casing and caping all as specified and directed. \nNote for item No 10 to 13: Two runs of copper cable, one run of earth continuity and one run of conduit / casing and caping shall be measured as one unit length. 50 RM
14 14 Earthing complete with galvanized steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanized earth wire of size 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 connected to earth testing point including necessary excavation, earth work, PCC pit ,RCC cover 1:2:4 type B1 with 8 mm dia MS bars at 100c/c , funnel ,watering pipe etc. all specified and directed including testing on completion . 5 EACH
15 15 Cutting chases in stone masonry wall / concrete floor /roof for laying PVC conduit and making good to facings where required and pointing in cement mortar 1:3 and making good cutting not exceeding 10cm girth all as specifed and directed. 250 RM
16 16 Taking down exhaust fan of any size and make carefully from any height after disconnecting the electric connection and refixing the same after necessary repairs / servicing , including reconnecting electrical connection and testing complete all as specified and directed. \nNote:- (i) Rate shall be deemed to be inclusive of Dismantling the fan, Servicing, cleaning, oiling, greasing and assemble the fan properly including tightening all the bolts , nuts screws clamps etc complete.\n(ii) Spares required for repairs of exhaust fan and rewinding of exhaust fan will be measured and paid separately. 20 EACH
17 17 Rewinding of Exhaust fan motor with super enamelled copper winding wire of suitable gauge after cutting and removing the burnt out existing winding, including varnishing , heating , providing fresh insulating material for 300 mm sweep all as specified and directed. 10 EACH
18 18 Rewinding of Exhaust fan motor with super enamelled copper winding wire of suitable gauge after cutting and removing the burnt out existing winding, including varnishing, heating, providing fresh insulating material for 375/380/450 mm sweep all as specified and directed. 18 EACH
19 19 Taking out unserviceable ball bearings and supply and fix new ball bearing of suitable size for any make of Exhaust fan 300/375/380/450 mm sweep all as specified and directed. 15 EACH
20 20 Taking out unserviceable heating element and supply and fix new heating element 1.5 KW Dual clip type with rubber gasket suitable for geysers up to 25 Ltr capacity all as specified and directed. 40 EACH
21 21 Taking out unserviceable heating element and supply and fix new heating element 1.5 KW Round type with rubber gasket suitable for geysers up to 50 Ltr capacity all as specified and directed. 30 EACH
22 22 Taking out unserviceable heating element and supply and fix new heating element 1.5 KW Triangle type with rubber gasket suitable for geysers up to 50 Ltr capacity all as specified and directed. 30 EACH
23 23 Taking out unserviceable thermostat and supply and fix new thermostat suitable for 25 Ltr capacity geyser , range 30° C to 80° C and acting at 70° C all as specified and directed. 80 EACH
24 24 Taking out unserviceable PVC connections and supply and fix new PVC connection up to 600 mm in length suitable to connect GI pipe 15 mm dia to hot water outlet of geyser all as specified and directed. 50 EACH
25 25 Servicing / Repairs to DG Set 35 KVA Capacity Kirloskar Make by checking all running parameters and adjusting / calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Primary Element - 1 No\n(b) Secondary Element - 1 No\n(c) Spin on filter for lubricating oil - 1 No\n(d) Copper Washer 14x20 - 4 Nos\n(e) Copper Washer 10x16 - 4 Nos\n(f) K Oil Super - 15 Ltrs 1 JOB
26 26 Servicing/ Repairs to DG Set 63 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Fuel Filter Element - 2 Nos\n(b) Spin on filter for lubricating oil - 2 Nos\n(c) K Oil Super - 30 Ltrs 1 JOB
27 27 Servicing/ Repairs to DG Set 25 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Primary Element - 2 Nos\n(b) Spin on filter for lubricating oil - 1 No\n(c) Main Element for Air Cleaner - 1 No\n(d) K Oil Premium - 15 Ltrs 1 JOB
28 28 Servicing/ Repairs to DG Set 45 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/ calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Primary Element - 1 No\n(b) Secondary Element - 1 No\n(c) Fuel Filter Element - 2 Nos\n(d) Spin on filter for lubricating oil - 1 No\n(e) Primary element for Air Cleaner - 1 No\n(f) K Oil Super - 20 Ltrs\n(g) K Cool Super plus - 10 Ltrs 1 JOB
29 29 Servicing/ Repairs to DG Set 15 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Primary Element - 1 No\n(b) Secondary Element - 1 No\n(c) Spin on filter for lubricating oil - 1 No\n(d) Main element for Air Cleaner - 1 No\n(f) K Oil Super - 20 Ltrs 1 JOB
30 30 Servicing/Repairs to DG Set 200 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/ calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Fuel Filter Element Pre - 1 No\n(b) Fuel Filter Element Micro - 1 No\n(c) Spin on filter for lubricating oil - 2 Nos\n(d) K Oil Premium - 30 Ltrs \n(e) K Cool Super plus - 15 Ltrs 1 JOB
31 31 Labour free Servicing to DG Set 10 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/ calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Fuel Filter Element - 2 Nos\n(b) Spin on filter for lubricating oil - 1 No\n(c) K Oil Premium (Engine oil) - 15 Ltrs \n(d) Copper Washer 10x16 - 4 Nos 1 JOB
32 32 Labour free Servicing to DG Set 30 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/ calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Fuel Filter Element - 2 Nos\n(b) Spin on filter for lubricating oil - 1 No\n(c) K Oil Premium (Engine oil) - 20 Ltrs \n(d) Copper Washer 14x20 - 4 Nos\n(e) Copper Washer 10x16 - 4 Nos 1 JOB
33 33 Labour free Servicing to DG Set 50 KVA Capacity Kirloskar Make by checking all running parameters and adjusting/ calibrating for smooth functioning including cleaning of diesel tank and supply and replacing the following items complete \n(a) Primary Element - 1 No\n(b) Secondary Element - 1 No\n(c) Fuel Filter Element - 2 Nos\n(d) Spin on filter for lubricating oil - 1 No\n(e) Primary element for Air Cleaner - 1 No\n(f) K Oil Super (Engine oil) - 20 Ltrs\n(g) K oil Super plus - 10 Ltrs\nNote for item No 25 to 33: Servicing / repair to DG set for item sl No. 25 to 33 is to be carried out through authorised service centre of OEM duly approved by accepting officer and test report of the same has to be submitted on completion of work. 1 JOB
34 34 Servicing / Repairs and testing of AMF Panel of DG set 15 KVA to 45 KVA by replacement of unserviceable spares including re-doing the cable termination with new lugs.\nNote: (i) Spares will be measured and paid separately.\n(ii) Spares to be replaced shall be of same make as per existing. 5 JOB
35 35 Servicing / Repairs and testing of AMF Panel of DG set 50 KVA to 200 KVA by replacement of unserviceable spares including re-doing the cable termination with new lugs.\nNote: (i) Spares will be measured and paid separately.\n(ii) Spares to be replaced shall be of same make as per existing. 4 JOB
36 36 Supply and replace SQ-A-800 timer suitable for AMF panel all as specified and directed. 4 EACH
37 37 Supply and replacing SQ-A-800 timer and relay suitable for AMF panel all as specified and directed. 6 EACH
38 38 Supply and replacing ADD ON Block MNX-A1 415V 50/60 HZ suitable for AMF panel all as specified and directed. 6 EACH
39 39 Supply and replace relay with base 230V suitable for AMF panel all as specified and directed. 4 EACH
40 40 Supply and replace MCX 11 contactor suitable for AMF panel all as specified and directed. 4 EACH
41 41 Servicing / repairs and testing of solar street light of any model including removing electrical connection and checking panel, battery, replacement of spares etc.\nNote: (i) Spares will be measured and paid separately.\n(ii) Spares to be replaced shall be of same make as per existing. 20 JOB
42 42 Supply and replace 12 Amps charge control unit 12 volts all as specified and directed. 6 EACH
43 43 Supply and fix 12 volts 100AH tubular battery all as specified and directed. 15 EACH
44 44 Supply and fix 22W solar LED fitting with CCU all as specified and directed. 16 EACH
45 45 Servicing / repairs and testing of solar water heater and checking panel and replacement of spares etc all as specified and directed.\nNote: (i) Spares will be measured and paid separately.\n(ii) Spares to be replaced shall be of same make as per existing. 5 JOB
46 46 Supply and replace EDPM open washer for solar water heater all as specified and directed. 4 EACH
47 47 Supply and replace Bolt Nut GI (1set - 4 Nos) for solar water heater all as specified and directed. 4 EACH
48 48 Supply and replace Dummy washer SS for solar water heater all as specified and directed. 4 EACH
49 49 Supply and replace Heating coil for solar water heater all as specified and directed. 5 EACH
50 50 Supply and replace Toughened glass for solar collector for solar water heater all as specified and directed. 5 EACH
51 51 Supply and fill distilled water for solar water heater all as specified and directed. 100 LTRS
52 52 Air termination, single pointed aluminium rod 12mm dia and 300mm long all as specified and directed. 45 EACH
53 53 Test point terminal block made out of gun metal or phosphorus bronze size 75 x75 x25mm drilled and screwed including 3 Nos, 8mm dia 25mm long hex head screw complete all as specified and directed 30 EACH
54 54 Aluminium strip 25x 3.15 mm with saddles and fixing screws etc for down conductors complete all as specified and directed 250 RM
55 55 Galvanised iron strip 32 x 6mm buried in ground all as specified and directed 80 RM
56 56 Earthing complete with galvanised steel earth plate electrode 60x60x6mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below the ground level with top edge of the plate not less than 1.5 mtr below the normal ground level connected to the galvanised earth strip 25mm x 4mm by means of bolts, nuts, hook nuts and washers of galvanised steel all as shown in electrical plate No 3 of SSR Part I connected to earthing testing point all as specified or indicated including testing on completion. 30 EACH