Tender For Providing Of Central Ac ( Strctural Workshop New Flight Complex Ejection Seat And Survival And Ejection Seat Arming And Disarming Engine And Apu Bay Mmpu-I And Mmpu-Ii ) For Development Of Infrastructure For Induction Of Mmrca At Af Stn Ambal, AMBALA-Haryana

Military Engineer Services-MES has published Tender For Providing Of Central Ac ( Strctural Workshop New Flight Complex Ejection Seat And Survival And Ejection Seat Arming And Disarming Engine And Apu Bay Mmpu-I And Mmpu-Ii ) For Development Of Infrastructure For Induction Of Mmrca At Af Stn Ambal. Submission Date for this Tender is 02-11-2019. Air Conditioner Tenders in AMBALA Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

22050328
Tender For Providing Of Central Ac ( Strctural Workshop New Flight Complex Ejection Seat And Survival And Ejection Seat Arming And Disarming Engine And Apu Bay Mmpu-I And Mmpu-Ii ) For Development Of Infrastructure For Induction Of Mmrca At Af Stn Ambal
Open Tender
Indian
Haryana
AMBALA
02-11-2019

Tender Details

Tender For Providing Of Central Ac ( Strctural Workshop New Flight Complex Ejection Seat And Survival And Ejection Seat Arming And Disarming Engine And Apu Bay Mmpu-I And Mmpu-Ii ) For Development Of Infrastructure For Induction Of Mmrca At Af Stn Ambala ( Tender-V )

Key Value

Document Fees
INR 3000 /-
EMD
INR 679750.0 /-
Tender Value
INR 7.09 Crore /-

BOQ Items

Name of Work: PROVN OF CENTRAL AIRCONDITIONING (STRUCTURAL WORKSHOP, NEW FLIGHT COMPLEX, EJECTION SEAT & SURVIVAL AND EJECTION SEAT ARMING & DISARMING, ENGINE & APU BAY, MMPU-I & MMPU-II) FOR DEVELOPMENT OF INFRASTRUCTURE FOR INDUCTION OF MMRCA AT AF STATION AMBALA (TENDER-V).
Srl No. Item Description Drg No. or ref to list of drgs Quantity Units
1 1 AIR CONDITIONING WORK (Part-I)
2 1.1 WATER-COOLED SCROLL TYPE CHILLER UNIT WITH R-407C/134a REFRIGERANT (2 working simultaneously & 1 standby)\nSupply, installation, testing and commissioning of factory designed, pre-fabricated and floor-mounted water vapour compression scroll-type water-cooled chiller machine complete with hermatic scroll compressors with independent refrigerant circuits, water-cooled S/T type condenser, S/T horizontal DX (Direct Expansion) type evaporator with carbon steel shell and seamless copper tubes with elastomeric insulation, common base frame, interconnected copper refrigerant piping and wiring, vibration isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser and ozone friendly CFC-free refrigerant gas 407C/134a.\nThe quoted price shall be inclusive of a unit mounted DOL starter (to ensure that the starting current does not exceed twice the full load current), victaulic coupling, system integrator capable of giving industry standard (modbus/bacnet) output to BMS for critical parameters. Mapping shall be required for all critical points displayed on the chiller control panel. The chiller shall be BMS compatible and shall have RS485/RS232 serial communication protocol; the motor shall be suitable for 3- Phase, 415 V + 10%, 50 Hz AC electric supply; electric panel shall have an IP 54 rating.\n
3 1.11 GENERAL NOTE:\n(i) The contractor is responsible to achieve the desired, temperature, humidity and air flow/throw in the conditioned areas. For efficient and smooth running of the plant and machinery if any additional spares and specialized workmanship is required the same shall be provided by the contractor without any extra cost to deptt.\n(ii) Cost for all the consumable like refrigerant, refrigerant oil, inert gases etc is deemed to be included in the quoted rates by the contractor.\n(iii) In case of mentioned capacity of chiller is not avialable in standard capacity as specified in the respective items the next higher capacity will be provided by the contractor without any extra cost to deptt.\n(iv) Necessary civil work viz. PCC foundation for placement of chillers shall be covered in the scope of work. The chiller shall be as per the approved particular technical specifications and shall meet the following design criteria:\n(a) Chiller: \n(i) Chilled Water IN: 53.6° F \n(ii) Chilled Water OUT: 44.6° F. \n(iii) Fouling Factor: 0.00050 Sq ft Hr oF/Btu(in FPS units)\n(iv) Water Flow Rate: 2.67 US-gpm/TR \n(b) Condenser\n(i) Condenser Water IN: 90° F\n(ii) Condenser Water OUT: 98.5° F\n(iii) Fouling Factor: 0.00100 Sq ft Hr oF/Btu(in FPS units)\n(iv) Water Flow Rate: 4.25 US-gpm/TR
4 1.12 STRUCTURAL WORKSHOP\nScroll-type water-cooled chiller of nominal capacity in standard manufacturer's range corresponding to actual capacity not less than 75 TR and suitable for ambient environmental conditions.\n 3 Each
5 1.13 NEW FLIGHT COMPLEX\nScroll-type water-cooled chiller of nominal capacity in standard manufacturer's range corresponding to actual capacity not less than 46TR and suitable for ambient environmental conditions.\n\n 3 Each
6 1.14 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nScroll-type water-cooled chiller of nominal capacity in standard manufacturer's range corresponding to actual capacity not less than 17 TR and suitable for ambient environmental conditions. 3 Each
7 1.15 ENGINE & APU BAY\nScroll-type water-cooled chiller of nominal capacity in standard manufacturer's range corresponding to actual capacity not less than 35TR and suitable for ambient environmental conditions.\n\n 3 Each
8 1.16 MMPU- I & MMPU- II\nScroll-type water-cooled chiller of nominal capacity in standard manufacturer's range corresponding to actual capacity not less than 87TR and suitable for ambient environmental conditions.\n\n 3 Each
9 2 CHILLED WATER PUMP HORIZONTAL END SUCTION LONG COUPLED TYPE WITH INSULATION (2 working simultaneously & 1 standby).\nSupply, installation, testing and commissioning of end-suction & top-discharge, non-self-priming, single-stage, centrifugal volute type pump having cast iron casing, enclosed type dynamically balanced phosphor-bronze/SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, TEFC squirrel cage high efficiency induction motor, star/delta starter panel, base plate, mounting channel frame as per manufacturer recommendations, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting, elastomeric thermal insulation of suitable thickness, etc. suitable for operation on 3 Phase, 415 V ± 10%, 50 Hz AC supply \nNote:- Necessary civil work viz. PCC foundation for placement of pump, mounting of star/delta starter panel and pump accessories shall be covered in the scope of work. The pump shall be as per the approved particular technical specifications.\n\n
10 2.1 STRUCTURAL WORKSHOP\nHorizontal End Suction Long Coupled type pump with insulation suitable for 207 US-gpm water flow rate and 25 m head.\n 3 Each
11 2.2 NEW FLIGHT COMPLEX\nHorizontal End Suction Long Coupled type pump with insulation suitable for 138 US-gpm water flow rate and 25 m head.\n 3 Each
12 2.3 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nHorizontal End Suction Long Coupled type pump with insulation suitable for 66 US-gpm water flow rate and 25 m head. 3 Each
13 2.4 ENGINE & APU BAY\nHorizontal End Suction Long Coupled type pump with insulation suitable for 105 US-gpm water flow rate and 25 m head.\n 3 Each
14 2.5 MMPU- I & MMPU- II\nHorizontal End Suction Long Coupled type pump with insulation suitable for 262 US-gpm water flow rate and 25 m head.\n 3 Each
15 3 FRP RECTANGULER SHAPE INDUCED DRAUGHT COOLING TOWER \nSupply, installation, testing and commissioning of FRP rectangular shape vertical induced draught counter flow cooling tower with uniform water distribution and optimal heat transfer, having tough fiberglass reinforced plastic (FRP) casing of sufficient structural strength to withstand vibrations and wind velocity upto 60 m/s, FRP basin, rigid honeycomb type PVC fill of suitable thickness, SS sprinklers and non-clogging sprinkler pipes, FRP drift eliminator, energy efficient induced draught axial type fans with factory set and dynamically balanced blades pitch, TEFC squirrel cage high efficiency induction motor with IP 65 protection suitable for 3- Phase, 415 ± 10% V, 50 Hz AC electric supply, inlet, outlet, drain and over flow nozzle connections, etc, complete all as specified and directed.\nNote:- Necessary civil work viz. PCC foundation for placement of cooling tower, etc. shall be covered in the scope of work. The cooling tower shall be as specified.
16 3.1 STRUCTURAL WORKSHOP\nFRP rectangular shape induced draught cooling tower suitable for 150 TR AC Plant capacity.\n 1 Each
17 3.2 NEW FLIGHT COMPLEX\nFRP rectangular shape induced draught cooling tower, suitable for 100 TR AC Plant capacity.\n 1 Each
18 3.3 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nFRP rectangular shape induced draught cooling tower suitable for 50 TR AC Plant capacity. 1 Each
19 3.4 ENGINE & APU BAY\nFRP rectangular shape induced draught cooling tower, suitable for 80 TR AC Plant capacity.\n 1 Each
20 3.5 MMPU- I & MMPU- II\nFRP rectangular shape induced draught cooling tower, suitable for 200 TR AC Plant capacity.\n 1 Each
21 4 CONDENSER WATER PUMP FOR COOLING TOWER- HORIZONTAL END SUCTION LONG COUPLED TYPE (2 working simultaneously & 1 standby)\nSupply, installation, testing and commissioning of end-suction & top-discharge, non-self-priming, single-stage, centrifugal volute type pump having cast iron casing, enclosed type dynamically balanced phosphor-bronze/SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, TEFC squirrel cage high efficiency induction motor, star/delta starter panel, base plate, mounting channel frame as per manufacturer recommendations, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting, elastomeric thermal insulation of suitable thickness, etc. suitable for operation on 3 Phase, 415 V ± 10%, 50 Hz AC supply, complete all as specified and directed.\nNote:- Necessary civil work viz. PCC foundation for placement of pump, mounting of star/delta starter panel and pump accessories shall be covered in the scope of work. The pump shall be as specified.\n\n
22 4.1 STRUCTURAL WORKSHOP\nHorizontal End Suction Long Coupled type pump with insulation suitable for 263 US-gpm water flow rate and 20 m head.\n 3 Each
23 4.2 NEW FLIGHT COMPLEX\nHorizontal End Suction Long Coupled type pump with insulation suitable for 175 US-gpm water flow rate and 20 m head.\n 3 Each
24 4.3 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nHorizontal End Suction Long Coupled type pump with insulation suitable for 84 US-gpm water flow rate and 20 m head. 3 Each
25 4.4 ENGINE & APU BAY\nHorizontal End Suction Long Coupled type pump with insulation suitable for 133 US-gpm water flow rate and 20 m head.\n 3 Each
26 4.5 MMPU- I & MMPU- II\nHorizontal End Suction Long Coupled type pump with insulation suitable for 333 US-gpm water flow rate and 20 m head.\n 3 Each
27 5 DOUBLE SKIN AIR HANDLING UNITS WITH 43 mm THICK CFC-FREE PUF INJECTED INSULATION PANEL, 10 MICRON PRE-FILTERS AND VFD \nSupply, installation, testing and commissioning of double-skin type horizontal, floor-mounted, top/side discharge air handling units having corrosion resistant extruded aluminium hollow profile with thermal break, heavy gauge galvanized steel channel base frame, 43 mm double skin panel with pressure injected CFC & HCFC free PUF with 'k' value of 0.02 W/°C m & density 40 kg/cum, pre-coated pre-plasticized galvanized outer and inner skin 0.60mm thick, air-tight casing using gaskets and self-adhesive tapes, AMCA certified energy efficient fans with double inlet double width forward or backward curved impellers for high static pressure mounted on aluminium extruded slide rail base frame, chilled water coils with combination of 6 rows deep and 2 row deep hot water coil with anti-corrosion Aluminium fins, PVC Nylon hinges & handles, view port and marine lamp, limit switch, SS-304 drain pan, 10 micron pre-filters, inspection windows/doors, mixing box and supply/return/fresh air dampers, complete all as specified and directed. \nNote:- Necessary civil work viz. PCC foundation for placement of AHU, mounting of VFD panel, etc. shall he covered in the scope of work. The AHU shall be as specified and the following design criteria.\n\n
28 5.01 (a) Suitable DIDW fan with AMCA certified blower having outlet velocity not exceeding 9.2 m/s.\n(b) 4 Pole, TEFC, high efficiency, squirrel cage induction motor drive having BHP rating 20% higher than the peak capacity, suitable for 415 V ±10%, 50 Hz, 3-Phase AC power supply.\n(c) V-belt drive assembly with pulleys, belt, guard, etc., double canvass connections with zip to discharge duct/plenum, etc.\n(d) 50 mm thick, washable HDPE, 90% down 10 micron pre-filters, filters, fixing framework, hinge type access doors, etc.\n(e) 6 row deep chilled water coil and 2 row deep hot water coil section with aluminium fins and copper tube tested on 21 kg/sq cm with SS sandwiched drain tray, etc.\n(f) 18 gauge MS CRCA duly powder coated AHU sub panel board in compartmentalized construction with incomer and outgoing feeders for AHU motor, 3-way valve actuator motor, fire damper actuator motor, etc. complete with required variable frequency drive, relays, timers, contactors, PT, push buttons, switches, internal wiring, etc.\n
29 5.1 STRUCTURAL WORKSHOP
30 5.11 40000 CFM; 80 mm WG static pressure\n 1 Each
31 5.12 13000 CFM ; 80 mm WG static pressure\n 1 Each
32 5.2 NEW FLIGHT COMPLEX
33 5.21 25000 CFM; 80 mm WG static pressure\n 1 Each
34 5.22 35000 CFM; 80 mm WG static pressure\n 1 Each
35 5.3 EJECTION SEAT & SURVIVAL PACK
36 5.31 12000 CFM; 80 mm WG static pressure\n 1 Each
37 5.4 EJECTION SEAT ARMING & DISARMING
38 5.41 4000 CFM; 80 mm WG static pressure\n 1 Each
39 5.5 ENGINE & APU BAY
40 5.51 22000 CFM; 80 mm WG static pressure\n 1 Each
41 5.52 13000 CFM; 80 mm WG static pressure\n 1 Each
42 5.6 MMPU- I
43 5.61 42000 CFM; 80 mm WG static pressure\n 1 Each
44 5.62 35000 CFM; 80 mm WG static pressure\n 1 Each
45 5.7 MMPU- II
46 5.71 22000 CFM; 80 mm WG static pressure\n 1 Each
47 6 PAN TYPE HUMIDIFIER\nSupply, installation, testing and commissioning of PAN-type humidifier made out of SS-304 sheet welded construction with unitized stainless steel reservoir, divided into two chambers from inside having 25 mm thick fiberglass insulation cladded with aluminium foil, snap-acting humidistat, support legs for free-standing or wall hanging brackets for wall-mounting, factory mounted & wired humidifier control cabinet, steam outlet nozzle, water make-up, drain, over-flow, quick fill connections, immersion heaters made of copper or stainless steel, terminal blocks suitable for field power and control wiring and safety thermostat, complete all as specified and as directed.\n
48 6.1 STRUCTURAL WORKSHOP
49 6.11 PAN-type humidifier suitable for 48 litre/hr evaporation rate (for 40000 CFM AHU)\n 1 Each
50 6.12 PAN-type humidifier suitable for 6 litre/hr evaporation rate (for 13000 CFM AHU)\n 1 Each
51 6.2 NEW FLIGHT COMPLEX
52 6.21 PAN-type humidifier suitable for 8 litre/hr evaporation rate (for 25000 CFM AHU)\n 1 Each
53 6.22 PAN-type humidifier suitable for 10 litre/hr evaporation rate (for 35000 CFM AHU)\n 1 Each
54 6.3 EJECTION SEAT & SURVIVAL PACK
55 6.31 PAN-type humidifier suitable for 6 litre/hr evaporation rate (for 12000 CFM AHU) 1 Each
56 6.4 EJECTION SEAT ARMING & DISARMING
57 6.41 PAN-type humidifier suitable for 2 litre/hr evaporation rate (for 4000 CFM AHU)\n 1 Each
58 6.5 ENGINE & APU BAY
59 6.51 PAN-type humidifier suitable for 16 litre/hr evaporation rate (for 22000 CFM AHU)\n 1 Each
60 6.52 PAN-type humidifier suitable for 5 litre/hr evaporation rate (for 13000 CFM AHU)\n 1 Each
61 6.6 MMPU- I
62 6.61 PAN-type humidifier suitable for 18 litre/hr evaporation rate (for 42000 CFM AHU)\n 1 Each
63 6.62 PAN-type humidifier suitable for 14 litre/hr evaporation rate (for 35000 CFM AHU)\n 1 Each
64 6.7 MMPU- II
65 6.71 PAN-type humidifier suitable for 12 litre/hr evaporation rate (for 22000 CFM AHU) 1 Each
66 7 HOT WATER GENERATOR \nSupply, installation, testing and commissioning of SS 304 shell type vertical electric hot water generator for hot water output at 82º F (28º C) tested for 350 psig pressure, having insulation of resin bonded with fiber glasswool with aluminium cladding, thermostat for individual step, digital thermometer for inlet & outlet pipes, pressure gauge with ball valve for inlet & outlet pipes, SCR based stepless linear controller, float switch, audio/visual alarm for low water level, audio/visual alarm for high temperature, pressure relief valve, door switch, safety thermostat, etc. including suitable pump, complete all as specified and directed.\n
67 7.1 STRUCTURAL WORKSHOP
68 7.11 Hot Water Generator suitable for 134 kW heat output (for 40000 CFM AHU)\n 1 Each
69 7.12 Hot Water Generator suitable for 53 kW heat output (for 13000 CFM AHU)\n 1 Each
70 7.2 NEW FLIGHT COMPLEX
71 7.21 Hot Water Generator suitable for 57 kW heat output (for 25000 CFM AHU)\n 1 Each
72 7.22 Hot Water Generator suitable for 74 kW heat output (for 35000 CFM AHU)\n 1 Each
73 7.3 EJECTION SEAT & SURVIVAL PACK
74 7.31 Hot Water Generator suitable for 30 kW heat output (for 12000 CFM AHU) 1 Each
75 7.4 EJECTION SEAT ARMING & DISARMING
76 7.41 Hot Water Generator suitable for 13 kW heat output (for 4000 CFM AHU)\n 1 Each
77 7.5 ENGINE & APU BAY
78 7.51 Hot Water Generator suitable for 111 kW heat output (for 22000 CFM AHU)\n 1 Each
79 7.52 Hot Water Generator suitable for 40 kW heat output (for 13000 CFM AHU)\n 1 Each
80 7.6 MMPU- I
81 7.61 Hot Water Generator suitable for 97 kW heat output (for 42000 CFM AHU)\n 1 Each
82 7.62 Hot Water Generator suitable for 99 kW heat output (for 35000 CFM AHU)\n 1 Each
83 7.7 MMPU- II
84 7.71 Hot Water Generator suitable for 64 kW heat output (for 22000 CFM AHU) 1 Each
85 8 STAINLESS STEEL EXPANSION TANK FOR CHILLED WATER MAKE-UP\nS & F stainless steel (gade SS- 304) closed expansion tank of 1000 liter capacity, pressure rating to suit the system pressure and sized adequately to compensate for water expansion due to operating temperature variations, conforming to IS: 2825- 1969 for 'non-fired pressure vessels' complete with inter-connection piping, non-return valve, safety relief valve and pressure gauge, insulated with 50 mm thick insulation and cladded with 26 G aluminium etc as required all as specified and directed. \nNote:- Necessary civil work viz. PCC foundation & staging for water tank shall be included in the rate quoted by the contractor \n 5 Each
86 9 HDPE EXPANSION TANK FOR COOLING TOWER\nS & F HDPE expansion tank of 5000 liter capacity, pressure rating to suit the system pressure and sized adequately to compensate for water expansion due to operating temperature variations, conforming to IS: 2825- 1969 for 'non-fired pressure vessels' with interchangeable EPDM-BUTYL rubber membrane complete with inter-connection piping, non-return valve, safety relief valve and pressure gauge etc. as required all as specified and directed. \nNote:- Necessary civil work viz. PCC foundation & staging for water tank shall be included in the rate quoted by the contractor \n\n\n 5 Each
87 10 STAINLESS STEEL EXPANSION TANK FOR CHILLED WATER MAKE-UP\nS & F stainless steel (gade SS- 304) closed expansion tank of 500 liter capacity, pressure rating to suit the system pressure and sized adequately to compensate for water expansion due to operating temperature variations, conforming to IS: 2825- 1969 for 'non-fired pressure vessels' complete with inter-connection piping, non-return valve, safety relief valve and pressure gauge, insulated with 50 mm thick insulation and cladded with 26 G aluminium etc as required all as specified and directed. \nNote:- Necessary civil work viz. PCC foundation & staging for water tank shall be included in the rate quoted by the contractor \n 11 Each
88 11 CONDENSER WATER PIPING\nSupply, installation, testing and commissioning of MS ERW Class 'C' condenser water piping of following size with all necessary fittings i.e. bends, tees, reducers, flanges, structural support, wooden blocks, air-purge valves, drain-valves, etc. including two coat of enameled paint over one coat of red oxide primer, as required all as specified and directed. \n
89 11.1 150 mm NB\n 75 RM
90 11.2 125 mm NB\n 95 RM
91 11.3 100 mm NB\n 70 RM
92 11.4 80 mm NB\n 21 RM
93 11.5 65 mm NB\n 12 RM
94 11.6 50 mm NB\n 53 RM
95 11.7 40 mm NB\n 42 RM
96 11.8 32 mm NB\n 53 RM
97 11.9 20 mm NB\n 340 RM
98 12 BUTTERFLY VALVE\nSupply, installation, testing and commissioning of PN 1.6 rated double flanged short & long body type butterfly valve designed, manufactured and tested as per IS: 13095 (1991), suitable for isolation and throttling services, having Cl body & disc, SS AISI 304 disc seal, CS clamping ring and SS AISI 410 shaft and flange drilling standard end connection with accessories etc. as required all as specified and directed. \n
99 12.1 150 mm NB\n 10 Each
100 12.2 125 mm NB\n 22 Each
101 12.3 100 mm NB\n 29 Each
102 12.4 80 mm NB\n 12 Each
103 12.5 65 mm NB\n 12 Each
104 12.6 50 mm NB\n 7 Each
105 12.7 40 mm NB\n 13 Each
106 12.8 32 mm NB (Ball Valve)\n 3 Each
107 13 NON RETURN VALVE (NRV)\nSupply, installation, testing and commissioning of PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS: 5312-2 (1986), suitable to handle clear water having turbidity up to 5000 ppm, having Cl body, door and diaphram, leaded tin bronze seat rings and flange drilling standard end connection with accessories etc. as required all as specified and directed. \n
108 13.1 125 mm dia\n 3 Each
109 13.2 100 mm dia \n 6 Each
110 13.3 80 mm dia\n 3 Each
111 13.4 65 mm dia \n 3 Each
112 14 POT STRAINER\nSupply, installation, testing and commissioning of PN 1.6 rated POT strainer, tested as per BS 6755 (Part-1), suitable high capacity flow throughout full size inlet/outlet, having Cl body & strainer bonnet, stainless steel perforated filter screen, black rubber body/bonnet gasket, SS- 410 ball valve and flange drilling standard end connection with accessories etc. as required all as specified and directed. \n
113 14.1 150 mm dia\n 2 Each
114 14.2 125 mm dia\n 2 Each
115 14.3 100 mm dia\n 1 Each
116 15 Y-STRAINER\nSupply, installation, testing & commissioning of Y-type strainer with Cl/MS body, bolted cover, flanged ends, basket of brass/ bronze/ SS wire mesh complete with flanges, nuts-bolts, gaskets and flange drilling standard end connection with accessories etc. as required all as specified and directed. \n
117 15.1 125 mm dia\n 3 Each
118 15.2 100 mm dia\n 6 Each
119 15.3 80 mm dia\n 3 Each
120 15.4 65 mm dia\n 3 Each
121 16 BALANCING VALVE\nSupply, installation, testing and commissioning of 2-way globe type S-1710 DZR brass variable orifice balancing valve having brass body, EPDM body/bonnet O-ring, steel retaining clip, brass adjustable stop, brass stem, brass bonnet, SS cone retaining nut, EPDM disc O-ring, handwheel, test point for 240 PSI non-shock cold working pressure and maximum temperature 250° F at 240 PSI, flow measurement accuracy ±5% all complete as specified and directed.\n
122 16.1 150 mm dia\n 2 Each
123 16.2 125 mm dia\n 5 Each
124 16.3 100 mm dia\n 7 Each
125 16.4 80 mm dia\n 3 Each
126 16.5 65 mm dia\n 3 Each
127 17 FLOW SWITCH \nSupply, installation, testing and commissioning of paddle type Water Flow Switch suitable to control maximum flow rate of 350 US-gpm, , having operating pressure 1000 kPa, withstand pressure 91750 kPa, insulation resistance over 100 ?, withstand voltage 1500 V AC for 1 minute, contact point life of 1000 k cycles and bellows life 500 k cycles complete with control wiring and accessories, etc. as specified and dirceted.\n\n 15 Each
128 18 DRAIN PIPE\nM & L for UPVC pipes and fittings, resistant to chemical & electromechanical corrosion, conforming to EN 1452-2, having specific gravity 1.43, shore hardness 70°C to 90° C, tensile strength 500 kg/sqcm, bending strength 950 kg/sqcm, modulus of elasticity 3.2 X 10 kg/sqcm and dielectric strength > 40 kV/mm complete with accessories etc. as required all as specified and directed. \n
129 18.1 40 mm NB\n 150 RM
130 18.2 32 mm NB\n 80 RM
131 18.3 25 mm NB\n 80 RM
132 19 CHILLED WATER PIPING\nSupply, laying/ fixing, testing and commissioning of MS ERW Class 'C of following nominal sizes of chilled water piping with all necessary fittings i.e. bends, tees, reducers, flanges, structural support, wooden blocks, air-purge valves, drain-valves, etc. duly insulated with 25mm thick closed cell elastometric nitrile rubber with aluminum foil laminated on one side of minimum 45 Kg/cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘O’ insulation applied by suitable rubber based adhesive confirming to standard OEM specifications, complete including repairing of damage to building etc. all as specified and directed. \nNote:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
133 19.1 150 mm NB\n 42 RM
134 19.2 125 mm NB\n 186 RM
135 19.3 100 mm NB\n 441 RM
136 19.4 80 mm NB\n 90 RM
137 19.5 65 mm NB\n 280 RM
138 19.6 50 mm NB\n 224 RM
139 19.7 40 mm NB\n 76 RM
140 20 Y-STRAINER\nSupply, installation, testing & commissioning of Y-type strainer of following size with Cl/MS body, bolted cover, flanged ends, basket of brass/ bronze/ SS wire mesh complete with flanges, nuts-bolts, gaskets and flange drilling standard end connection with accessories etc. duly insulated to the same specifications as the connected piping, as required all as specified and directed. \n
141 20.1 125 mm dia\n 1 Each
142 20.2 100 mm dia\n 6 Each
143 20.3 80 mm dia\n 6 Each
144 20.4 65 mm dia\n 8 Each
145 20.5 50 mm dia\n 6 Each
146 20.6 40 mm dia\n 5 Each
147 20.7 32 mm dia \n 4 Each
148 20.8 25 mm dia\n 1 Each
149 20.9 20 mm dia \n 1 Each
150 21 BUTTERFLY VALVE\nSupply, installation, testing and commissioning of PN 1.6 rated double flanged short & long body type butterfly valve designed, manufactured and tested as per IS: 13095 (1991), suitable for isolation and throttling services, having Cl body & disc, SS AISI 304 disc seal, CS clamping ring and SS AISI 410 shaft and flange drilling standard end connection with accessories etc. duly insulated to the same specifications as the connected piping, as required all as specified and directed. \n
151 21.1 125 mm dia\n 2 Each
152 21.2 100 mm dia\n 24 Each
153 21.3 80 mm dia\n 18 Each
154 21.4 65 mm dia\n 22 Each
155 21.5 50 mm dia\n 20 Each
156 21.6 40 mm dia\n 11 Each
157 21.7 32 mm dia \n 8 Each
158 21.8 25 mm dia\n 2 Each
159 21.9 20 mm dia \n 2 Each
160 22 NON RETURN VALVE (NRV)\nSupply, installation, testing and commissioning of PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS: 5312-2 (1986), suitable to handle clear water having turbidity up to 5000 ppm, having Cl body, door and diaphram, leaded tin bronze seat rings and flange drilling standard end connection with accessories etc. duly insulated to the same specifications as the connected piping, as required all as specified and directed. \n
161 22.1 100 mm dia \n 6 Each
162 22.2 80 mm dia \n 3 Each
163 22.3 65 mm dia \n 3 Each
164 22.4 50 mm dia \n 3 Each
165 23 BALANCING VALVE\nSupply, installation, testing and commissioning of 2-way, globe type, PN 1.6 rated, balanced/high rangeability control valve duly insulated to the same specifications as the connected piping as per following specification.\nNominal pressure PN16\nMedium Temperature -10oF~ +110oF Maximum\nBody Material IS:210, FG 220 CI\nStem Material ASTM A276,GR SS 410\nDisc Material Stainless steel Disc\nHand Wheel Cast Iron\nLeakage Rate No visible leakage\nMedium Type Water\nFlange standard ISO7005-1 (GB/T 9113)\nShell Test pressure 24bar\nSeal Test pressure 17bar\n
166 23.1 125 mm dia\n 1 Each
167 23.2 100 mm dia\n 6 Each
168 23.3 80 mm dia\n 6 Each
169 23.4 65 mm dia\n 8 Each
170 23.5 50 mm dia\n 3 Each
171 24 3-WAY TEMPERATURE CONTROL VALVE\nSupply, installation, testing and commissioning of cast iron 3-way mixing valve, suitable for operation upto 10 bar, with electronically operated actuator for AHUs. Water flow through the valve shall be regulated by rotation of brass slipper between the main and the bypass ports; it shall be possible to manually rotate the brass slipper through 360° and interchange the main and the common ports, to facilitate installation at site. All internals of the valve shall be rust-proof and the 'O' ring shall be of elastomeric insulation. The valve actuator shall be of electronic type with DC motor, the actuator's angle of rotation shall he 90°, it shall be without any limit switches and shall be overload-proof. It shall have an indicator to indicate the position and push-button to disengage the gear train for manual operation including duly insulated to the same specifications as the connected pipe, as required all as specified and directed. \n
172 24.1 125 mm \n 1 Each
173 24.2 80 mm \n 3 Each
174 24.3 65 mm\n 5 Each
175 24.4 50 mm \n 1 Each
176 24.5 40 mm \n 1 Each
177 25 WATER FLOW SWITCH\nSupply, installation, testing and commissioning of paddle type Water Flow Switch suitable to control maximum flow rate of 300 US-gpm, having operating pressure 1000 kPa, withstand pressure 91750 kPa, insulation resistance over 100 O, withstand voltage 1500 V AC for 1 minute, contact point life of 1000 k cycles and bellows life 500 k cycles complete with elastomeric thermal insulation of suitable thickness, control wiring and accessories, etc., as required all as specified and directed. \n\n\n 15 Each
178 26 HOT WATER PIPING\nSupply, laying/ fixing, testing and commissioning of MS ERW Class 'C of following nominal sizes of hot water piping with all necessary fittings i.e. bends, tees, reducers, flanges, structural support, wooden blocks, air-purge valves, drain-valves, etc. duly insulated with 25mm thick closed cell elastometric nitrile rubber with aluminum foil laminated on one side of minimum 45 Kg/cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘O’ insulation applied by suitable rubber based adhesive confirming to standard OEM specifications, complete including repairing of damage to building etc. all as specified and directed. \nNote:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
179 26.1 50 mm NB\n 60 RM
180 26.2 40 mm NB\n 50 RM
181 26.3 32 mm NB\n 80 RM
182 26.4 25 mm NB\n 10 RM
183 26.5 20 mm NB\n 10 RM
184 27 BALL VALVE\nS & F of ball valve 25 mm NB class 150, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- 1, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/packing/gasket, CS fasteners and lever and screwed /socket weld end connection with accessories etc., as required all as specified and directed. \n\n\n 100 Each
185 28 AUTO-AIR-VENT\nSupply, installation, testing and commissioning of Automatic air-vent having 19 mm end connections with Brass OT 58 body and cover, polyacetal lever, high density expanded polyethylene float, EPDM rubber plug, stainless steel spring, polyamide capm etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 115° C respectively, installed on all high points in the water piping system to automatically remove the trapped air, installed on all high points in the water piping system to automatically remove the trapped air etc., as required all as specified and directed.\n\n\n 20 Each
186 29 TEMPERATURE GAUGE\nSupply, installation, testing and commissioning of glycerin filled bimetallic thermometer temperature gauge of 150 mm dial size for temperature range 0° C to 100° C in compliance to EN 13190, having standard range 0° C to 60° C upto 400° C, IP 67 protection, bimetal coil sensing element, accuracy class 1 as per EN 13190, stainless steel casing, direct bottom mounted, SS- 304 case and bayonet type bezel, SS- 316 stem and connection, aluminum dial (white background with black marking) & pointer (black colour micrometer with zero adjustable), toughened glass window, neoprene filling plug and gasket complete with accessories, etc. as required all as specified and directed.\n\n\n 92 Each
187 30 PRESSURE GAUGE\nSupply, installation, testing and commissioning of glycerin filled Pressure gauge of 100 mm dial size for pressure range 0 psi to 200 psi in compliance to EN837-1, having standard range 15 to 0 psi and 16 psi to 10000 psi, IP 67 protection, accuracy class ±1.6% of FS, stainless steel casing and TIG argon welded socket to case, direct bottom mounted, SS- 304 case and bayonet type bezel, SS- 316 bourdon, socket, SS dial (white background with black marking) & pointer (black colour micrometer with zero adjustable), polycarbonate glass window, neoprene blow off disc and filling plug, silicon gasket complete with accessories, etc. as required all as specified and directed.\n\n\n\n 152 Each
188 31 S & F wall-mounted air quality monitor with big LCD display, audible/visible alarm and quick response sensor to monitor and log temperature and humidity having temperature range -40° C to 85° C and relative humidity range 0% to 100%, temperature accuracy ± 0.6° C and relative humdity accuracy ± 3%, including 1 logger, 1 USB cable, 4 X AA battery and 1 manual as specified and directed.\n\n\n\n 20 Each
189 32 S & F touchscreen 7-day programmable Thermostat with universal system compatibility, precise comfort control having large, clear display with backlight, menu-driven programming, touchscreen interaction, real-time clock to control air flow of diffusers via volume control dampers as specified and directed.\n\n\n\n 20 Each
190 33 AIR DISTRIBUTION (GALVANIZED STEEL SHEET DUCTING)\nSupply, installation, testing and commissioning of factory fabricated galvanized steel sheet (G.S.S.) square/rectangular ducting for supply/return air, fabricated from galvanized steel sheet, having zinc coating of 160 gm/sqm total on both sides complete with neoprene rubber gaskets, elbows, splitters, vanes, supports to installed /hangging the duct with suitable size of SS hole fasthner etc as per IS: 655/1963 with required scaffolding work to install the ducts at site of following sheet thickness complete all as specified and directed.
191 33.1 24 G (MS angle flanges)\n 1671 Sqm
192 33.2 22 G (MS angle flanges)\n 2607 Sqm
193 33.3 20 G (MS angle flanges)\n 1151 Sqm
194 33.4 18 G (MS angle flanges)\n 1043 Sqm
195 34 FIRE DAMPER\nSupply, installation, testing and commissioning of fire damper complete with smoke detector/thermister, fusible link etc. and actuator as required for operation. The fire dampers shall be spring activated on melting of fusible link having melting point 67.13° C. The fire damper shall be located in the SA/RA ducts, at all fire rated crossoevers (shafts, walls, etc.). The control panel shall be located in such a way that the reset can easily be done. These combination smoke and fire dampers shall be interlocked with the building management system for the fire detection or HVAC and shall trip/close in the event of fire/smoke in the respective zone. Fire damper shall be tested as per ULL- 555 and certified by CBRI. The fire-damper shall be of at least 120 minutes fire-rating as per the approved particular technical specifications and shall meet the following design criteria:\n(a) Bare fire dampers with 400 mm sleeve.\n(b) Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position.\n(c) Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers.\n(d) Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the recommendations of the manufacturer and specifications.\n\n
196 34.1 Motorized, spring return type, combination fire and smoke damper 68 Sqm
197 34.2 Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position\n 11 Each
198 35 ACOUSTIC INSULATION\nS & F 18mm thick open-cell engineered nitrile rubber foam acoustic insulation having good sound absorption, damping and barrier properties, antimicrobial product protection, thermal conductivity, as per EN 12667, not exceeding 0.047 W/mK at 20° C, density 140-180 kg/cum and conforming to class 1 rating for surface spread of flame in accordance with BS 476 Part 7 & UL 94 (HB, V-0). The acoustic insulation material shall be free of dust and fibre; it shall pass fungi/mould resistance as per DIN EN ISO 846 method A and bacterial resistance as per DIN EN ISO 846 method C and air erosion resistance test in accordance to ASTM Standard C 1071-05 without any laminate or covering (section 12.7) from an independent accredited testing agency, complete all as specified and directed. 750 Sqm
199 36 THERMAL INSULATION\nS & F closed cell elastomeric nitrile rubber with aluminum foil laminated on one side, having thermal conductivity not exceeding 0.037 W/mK at mean temperature of 20° C as per EN 12667, moisture diffusion resistance factor or ‘µ’ value of minimum 7,000 for base insulation material without the foil as per EN 12086, fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame and also fire performance of V0, HB as per UL 94, 1996, density without the foil between 40 to 55 kg/cum. The insulation material shall be FM (Factory Mutual) USA approved and dust & fibre free. The Aluminium foil shall be 60 microns thick and its weight shall be 193 gsm as per EN ISO 2286-2, tensile strength 90 N / 15 mm as per EN ISO 527-3 with elongation > 10% as per EN ISO 527-3, complete all as specified and directed.
200 36.1 19 mm thick thermal insulation \n 1043 Sqm
201 36.2 13 mm thick thermal insulation \n 3756 Sqm
202 36.3 9 mm thick thermal insulation \n 1671 Sqm
203 37 SUPPLY/RETURN AIR DIFFUSERS/ GRILLES/LOUVERS\nSupply, installation, testing & commissioning of removable supply/return air diffusers/ grilles of extruded aluminum sections duly powder coated with volume control damper, complete all as specified and directed.
204 37.1 4-way Supply air/Return air diffusers/grilles/louvers with volume control damper 306.7 Sqm
205 37.2 18 G galvanized sheet steel volume control duct damper\n 57.07 Sqm
206 38 ELECTRICAL WORKS\nAC PLANT ROOM PANEL\nSupply, installation, commissioning and testing of following AC Plant Room panel board of suitable size, factory made, CPRI type tested, indoor, cubical compartmental type, double door, both side openable with hinged doors & locking arrangement, made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of size 50 mm x 50 mm x 6 mm, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3 Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length size, including fixing lugs bolts, screws etc complete all as specified.\nThe panel shall be designed and wired in such a manner that the starter for condenser water pump is powered first, after that the cooling tower motor shall be powered, then the chilled water pumps shall be powered and the chiller units should get the supply only if the condenser water pumps, cooling tower motor, and chilled water pumps are in ON condition.\n
207 38.1 STRUCTURAL WORKSHOP\nSupply, installation, commissioning and testing of AC Plant Room LT Panel Board.\nBusbar Chamber: \n(i) Copper busbar of rated capacity 1000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (of 04 busbars)\nIncoming:\n(i) 630 A, 415 V, lcs = lcu = lcw = 50 kA, 50 Hz, electrical draw-out type FP ACB with microprocessor based ET trip system with thermal memory, zone selective interlocking, fully rated neutral with inbuilt protection, pre-trip alarm & individual fault indicating LEDs and overload, short-circuit, instantaneous & earth-fault protections- 01 Nos.\n(ii) LED phase indicators (Yellow, Blue, Red)- 01 Set\n(iii) Digital voltmeter 0-500 V with selector switch flush mounting square type- 01 Nos.\n(iv) Digital ammeter 0- 630 A with selector switch flush mounting square type with suitable CTs - 01 Nos.\n 1 Each
208 38.11 Outgoing:\n(i) 250 A, 415 V, lcs = lcu = 36 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for chillers and hot water generator- 3 Nos.\n(ii) 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for AHUs- 2 Nos.\n(iii) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for chilled water pumps and hot water generator- 5 Nos including fully automatic star/delta starter suitable for upto 8.2 HP chilled water circulation pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(iv) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for condenser water pumps- 3 Nos, including fully automatic star/delta starter suitable upto 8.4 HP condenser water pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(v) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for cooling tower pump- 1 Nos including fully automatic star/delta starter suitable for7.5 HP cooling tower pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-1Nos\n\n
209 38.2 NEW FLIGHT COMPLEX\nSupply, installation, commissioning and testing of AC Plant Room LT Panel Board.\nBusbar Chamber:\n(i) Copper busbar of rated capacity 1000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (of 04 busbars)\nIncoming:\n(i) 630 A, 415 V, Ics = leu = lew = 50 kA, 50 Hz, electrical draw-out type FP ACB with microprocessor based FT trip system with thermal memory, zone selective interlocking, fully rated neutral with inbuilt protection, pre-trip alarm & individual fault indicating LEDs and overload, short-circuit, instantaneous & earth-fault protections- 01 Nos.\n(ii) LED phase indicators (Yellow, Blue, Red)- 01 Set\n(iii) Digital voltmeter 0-500 V with selector switch flush mounting square type- 01 Nos.\n(iv) Digital ammeter 0- 630 A with selector switch flush mounting square type with suitable CTs - 01 Nos.\n 1 Each
210 38.21 Outgoing:\n(i) 160 A, 415 V, Ics = lcu = 25 kA, 50 Hz FP MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5 - 10 X Ir) and microprocessor based trip unit for chillers- 3 Nos.\n(iii) 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for AHUs- 2 Nos.\n(iv) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for chilled water pumps - 3 Nos including fully automatic star/delta starter suitable upto 5.5 HP chilled water circulation pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(v) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for condenser water pumps- 3 Nos including fully automatic star/delta starter suitable upto 5.6 HP condenser water pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(vi) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for cooling tower pump- 1 Nos including fully automatic star/delta starter suitable for 5 HP cooling tower pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-1Nos\n\n\n
211 38.3 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nSupply, installation, commissioning and testing of AC Plant Room LT Panel Board.\nBusbar Chamber:\n(i) Copper busbar of rated capacity 500 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (of 04 busbars)\nIncoming:\n(i) 320 A, 415 V, Ics = Icu = 36 kA, 50 Hz FP MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit for chillers- 3 Nos.\n(ii) LED phase indicators (Yellow, Blue, Red)- 01 Set\n(iii) Digital voltmeter 0-500 V with selector switch flush mounting square type- 01 Nos.\n(iv) Digital ammeter 0- 320 A with selector switch flush mounting square type with suitable CTs - 01 Nos.\n 1 Each
212 38.31 Outgoing:\n(i) 100 A, 415 V, Ics = lcu = 25 kA, 50 Hz FP MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5 - 10 X Ir) and microprocessor based trip unit for chillers- 3 Nos.\n(iii) 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for AHUs- 2 Nos.\n(iv) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for chilled water pumps - 3 Nos including fully automatic star/delta starter suitable upto 2.6 HP chilled water circulation pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(v) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for condenser water pumps- 3 Nos including fully automatic star/delta starter suitable upto 2.7 HP condenser water pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(vi) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for cooling tower pump- 1 Nos including fully automatic star/delta starter suitable for 2 HP cooling tower pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-1Nos\n\n\n
213 38.4 ENGINE & APU BAY\nSupply, installation, commissioning and testing of AC Plant Room LT Panel Board.\nBusbar Chamber:\n(i) Copper busbar of rated capacity 800 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (of 04 busbars)\nIncoming:\n(i) 630 A, 415 V, Ics = leu = lew = 50 kA, 50 Hz, electrical draw-out type FP ACB with microprocessor based FT trip system with thermal memory, zone selective interlocking, fully rated neutral with inbuilt protection, pre-trip alarm & individual fault indicating LEDs and overload, short-circuit, instantaneous & earth-fault protections- 01 Nos.\n(ii) LED phase indicators (Yellow, Blue, Red)- 01 Set\n(iii) Digital voltmeter 0-500 V with selector switch flush mounting square type- 01 Nos.\n(iv) Digital ammeter 0- 630 A with selector switch flush mounting square type with suitable CTs - 01 Nos.\n 1 Each
214 38.41 Outgoing:\n(i) 125 A, 415 V, Ics = lcu = 25 kA, 50 Hz FP MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5 - 10 X Ir) and microprocessor based trip unit for chillers- 3 Nos.\n(iii) 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for AHUs- 2 Nos.\n(iv) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for chilled water pumps - 3 Nos including fully automatic star/delta starter suitable upto 4.2 HP chilled water circulation pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(v) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for condenser water pumps- 3 Nos including fully automatic star/delta starter suitable upto 4.2 HP condenser water pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(vi) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for cooling tower pump- 1 Nos including fully automatic star/delta starter suitable for 5 HP cooling tower pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-1Nos\n\n\n
215 38.5 MMPU- I AND MMPU- II\nSupply, installation, commissioning and testing of AC Plant Room LT Panel Board.\nBusbar Chamber:\n(i) Copper busbar of rated capacity 1000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (of 04 busbars)\nIncoming:\n(i) 630 A, 415 V, Ics = leu = lew = 50 kA, 50 Hz, electrical draw-out type FP ACB with microprocessor based FT trip system with thermal memory, zone selective interlocking, fully rated neutral with inbuilt protection, pre-trip alarm & individual fault indicating LEDs and overload, short-circuit, instantaneous & earth-fault protections- 01 Nos.\n(ii) LED phase indicators (Yellow, Blue, Red)- 01 Set\n(iii) Digital voltmeter 0-500 V with selector switch flush mounting square type- 01 Nos.\n(iv) Digital ammeter 0- 2500 A with selector switch flush mounting square type with suitable CTs - 01 Nos.\n 1 Each
216 38.51 Outgoing:\n(i) 250 A, 415 V, Ics = lcu = 36 kA, 50 Hz FP MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5 - 10 X Ir) and microprocessor based trip unit for chillers- 3 Nos.\n(iii) 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for AHUs- 3 Nos.\n(iv) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for chilled water pumps - 3 Nos including fully automatic star/delta starter suitable upto 10.4 HP chilled water circulation pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(v) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for condenser water pumps- 3 Nos including fully automatic star/delta starter suitable upto 10.6 HP condenser water pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-3 Nos\n(vi) 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and microprocessor based trip unit for cooling tower pump- 1 Nos including fully automatic star/delta starter suitable for 10 HP cooling tower pump complete with connector push button, LED indicator auto/manual selector switch, over load protection, current sencing type single phase preventer including wiring-1Nos\n\n\n
217 39 VARIABLE FREQUENCY DRIVE\nSupply, installation, commissioning and testing of following Variable Frequency Drives with IP 55 enclosures and mains disconnect switch comprising of the following:\n(a) Built in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the Variable Frequency Drive.\n(b) Built in EMC filters (electromagnetic compatibility filters) for restriction of conducted emissions to comply with 61800:3 (un restricted distribution) :2004 Category C 1 (50 meter).\n(c) Three feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors for process optimization and accordingly control the speed of the AHUs or pumps.\n(d) Integral graphical keypad.
218 39.1 Variable frequency drive (VFD) of power size 7.5 kW 2 Each
219 39.2 Variable frequency drive (VFD) of power size 11 kW\n 2 Each
220 39.3 Variable frequency drive (VFD) of power size 15 kW\n 2 Each
221 39.4 Variable frequency drive (VFD) of power size 18.5 kW 4 Each
222 39.5 Variable frequency drive (VFD) of power size 22 kW\n 1 Each
223 40 ELECTRICAL CABLES\nSupply, laying, jointing and testing of XLPE cable of following cross sectional area insulated, screened, PVC bedded, galvanized steel wire or strip armoured electric power cable (heavy duty) with aluminium stranded conductor 1100 volts grade, laid in trenches, passing through ducts/pipes, fixing along poles, complete all as specified.\nNote : \na) Earth work, sand cushioning, brick protection, hume pipe and cable tray shall be measured and paid separately\nb) Pre despatch inspection by rep. of accepting officer shall be carried out within overall cost quoted for each cable size where length exceeds 500 RM.\nc) Color code for cable shall be finalised by G.E\n
224 40.1 25 sq mm, 3.5 core 100 RM
225 40.2 35 sq mm, 3.5 core\n 150 RM
226 40.3 50 sq mm, 3.5 core\n 200 RM
227 40.4 95 sq mm, 3.5 core 150 RM
228 40.5 150 sq mm, 3.5 core\n 250 RM
229 41 Supply, laying, jointing and testing of XLPE cable of size 4sqmm 4 core insulated, screened, PVC bedded, galvanized steel wire or strip armoured electric power cable (heavy duty) with copper stranded conductor 1100 volts grade, laid in trenches, passing through ducts/pipes, fixing along poles, complete all as specified.\nNote : \na) Earth work, sand cushioning, brick protection, hume pipe and cable tray shall be measured and paid separately\nb) Pre despatch inspection by rep. of accepting officer shall be carried out within overall cost quoted for each cable size where length exceeds 500 RM.\nc) Color code for cable shall be finalised by G.E 1375 RM
230 42 M & L for earthing complete with copper earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, filled around with alternate layers of charcoal dust and salt and connected to copper strip of size 20 mm x 3 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel and protected by galvanized iron pipe light grade 40 mm bore and watering pipe 20mm dia medium grade with funnel and wire mesh as specified and connected all as shown in electrical plate No 3 of SSR Part I including necessary earth work and excavation in any type of soil and PCC 1:2:4 type B - 1 in chamber of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep and 80 mm thick precast RCC 1:2:4 type B - 1 using XPM weighing not less than 4Kg/Sqm for cover slab, complete all as specified and directed. \nNote: The unit rate quoted by tendrer is deemed to be include for necessary excavation, removal of surplus soil, PCC foundation, RCC cover, XPM weighing not less than 4Kg/Sqm, earth lead protection up to 7.5 Metre etc complete.\n 20 Each
231 43 M & L for Copper strip of size 20 mm x 3 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed.\n\n 150 RM
232 44 M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, filled around with alternate layers of charcoal dust and salt and connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel and protected by galvanized iron pipe light grade 40 mm bore and watering pipe 20mm dia medium grade with funnel and wire mesh as specified and connected all as shown in electrical plate No 3 of SSR Part I including necessary earth work and excavation in any type of soil and PCC 1:2:4 type B - 1 in chamber of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep and 80 mm thick precast RCC 1:2:4 type B - 1 using XPM weighing not less than 4Kg/Sqm for cover slab, complete all as specified and directed. \nNote: The unit rate quoted by tendrer is deemed to be include for necessary excavation, removal of surplus soil, PCC foundation, RCC cover, XPM weighing not less than 4Kg/Sqm, earth lead protection up to 7.5 Metre etc complete. 11 Each
233 45 M & L for GI strip of size 32 mm x 6 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed.\n\n 70 RM
234 46 Excavation in trenches not exc. 1.5 mtr in deep and n.exc 1.5mtr in width for laying of cables or pipes and getting out in soft/loose soil all as specified and directed.\n 300 Cum
235 47 Excavation in trenches exc. 1.5 mtr in deep but n exc 3.0 mtr deep and n.exc 1.5mtr in width for laying of cables or pipes and getting out in soft/loose soil all as specified and directed.\n 2.57 Cum
236 48 Returning filling in, including spreading levelling, watering and well ramming in layers not exc 25 cm thick all as specified and directed.\n 198 Cum
237 49 Removal of surplus excavated soil to a distance not exceeding 50 mtr from the strarting point and depositing where directed at a level n.exc 1.5 mtr in height all as specified and directed.\n\n 102 Cum
238 50 M & L for sand cushioning with a layer of sand 80mm thick before laying of cable and 150mm thick after laying of cable in trenches (total punned depth of sand shall be 180 mm after punning down) complete all as specified and directed.\nNote: punned thickness of sand shall be measured.\n 90 Cum
239 51 M&L for sub class 'B' bricks old size, laid dry flat over the cable (Width wise) after sand cushioning, for cable protection all as specified and directed. 6.8 Per 1000 Nos
240 52 Supply, laying and fixing 80mm dia GI Tubing light grade with all fittings for cable protection laid in trenches or fixed to wall / laid in flooring, complete all as specified and directed. 24 RM
241 53 MANNING & OPERATION (Part-II)
242 53.1 M&O FOR 1st YEAR OF OPERATION
243 53.11 STRUCTURAL WORKSHOP\nOperation only for central AC plant of 150 TR capacity consisting of 3X75 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings): \n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
244 53.12 NEW FLIGHT COMPLEX\nOperation only for central AC plant of 92 TR capacity consisting of 3X46 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings)\n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
245 53.13 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nOperation only for central AC plant of 35 TR capacity consisting of 3X17.5 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings): \n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
246 53.14 ENGINE & APU BAY\nOperation only for central AC plant of 70 TR capacity consisting of 3X35 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings)\n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
247 53.15 MMPU- I & MMPU- II\nOperation only for central AC plant of 180 TR capacity consisting of 3X90 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings)\n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
248 53.2 M&O FOR 2ND YEAR OF OPERATION
249 53.21 STRUCTURAL WORKSHOP\nOperation only for central AC plant of 150 TR capacity consisting of 3X75 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings): \n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
250 53.22 NEW FLIGHT COMPLEX\nOperation only for central AC plant of 92 TR capacity consisting of 3X46 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings)\n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
251 53.23 EJECTION SEAT & SURVIVAL PACK AND EJECTION SEAT ARMING & DISARMING\nOperation only for central AC plant of 35 TR capacity consisting of 3X17.5 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings): \n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
252 53.24 ENGINE & APU BAY\nOperation only for central AC plant of 70 TR capacity consisting of 3X35 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings)\n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
253 53.25 MMPU- I & MMPU- II\nOperation only for central AC plant of 180 TR capacity consisting of 3X90 TR chiller units (2 working + 01 standby) round the clock including Sunday & holidays in 3 shift each shift of 8 hours of one operator per shift of the relevant trade having ITI certificate with minimum 2 years experience or having 5 years experience of similar trade (Shift timings)\n1st Shift 0600 hrs to 1400 hrs\n2nd Shift 1400 hrs to 2200 hrs\n3rd Shift 2200 hrs to 0600 hrs\n 11 Per Month
254 53.3 Note for Srl item No 53.10 to 53.25 : \ni. Records for daily & periodic checks to be maintained by the contractor duly signed by operator & concerned executive. The cost of required stationary & equipments etc. is deemed to be included in quoted rates.\nii. The Operation will be started from the next immediate day/date of completion of phase-I work. \niii. During contract liability period no extra cost will be paid against any spare required to be replaced and consumable used.\niv. Life insurance and ESI medical facilities of govt for all the personnel shall be done by the contractor and copy of the policy to be submitted to the deptt.\nv. Minimum T&P required for the operator to be provided by contractor.\nvi. All safety device required for the operator to be provided by contractor.\nvii. Any damages to the machinery/ operator occurred due to miss handling of Equipment will be compensated by contractor.\nviii. Minimum wages to be paid by contractor through nationalised bank ESC mode as per Labour Commission Act.\nix. Weekly ‘off’ as per Labour act to be given to the Operator & reliever to be Provided by the Contractor at no Extra cost.\nx. PPF should be necessary for all candidate.\nxi. Contractor has to provide 02 pair of protective clothing overall combination with leather shoes one pair (as approved by Department) to each operator.\nxii. In case of absenteeism of any Operator/ helper in a shift/ duty , double the amount of Shifts will be recovered from the contractor.\nxiii. After completion of work contractor shall return all the temporary passes to AF authorities and certificate to be obtained & the same be enclosed with final bill.\n
255 53.31 Note for Srl item No 53.10 to 53.25(Condt) : \nxiv. Contractor shall obtain a Affidavit from all deployed Operators/ Trademen/Helpers that they are deployed temporary by the contractor through outsourcing & they have no legal binding/ with department regarding/employment/permanency of job. Any court cases due to accident/ break of jobs/compensation occurring due to any labour conflict during the contract period is to be delt by contractor only.\nxv. The age of all deployed operators/ tradesmen/ helpers should be 18 to 60 years old.\nxvi. Operator/ helpers will use their own convegance to reach duty place/ locations.