| 1 | 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Make : Havells / Polycab / R R KABEL / Finolex make FRLS cable and Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic make switches) | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 1.01 | i) Group B | BI01010001010000000000000515BI0100001113 | 134 | Point |
|---|
| 3 | 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. (Make : Havells / Polycab / R R KABEL / Finolex ) | BI01010001010000000000000515BI0100001114 | 190 | metre |
|---|
| 4 | 3 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. (Make : Havells / Polycab / R R KABEL / Finolex ) | BI01010001010000000000000515BI0100001115 | 195 | metre |
|---|
| 5 | 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (Make : Havells / Polycab / R R KABEL / Finolex ) | | | |
|---|
| 6 | 4.1 | (i) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire | BI01010001010000000000000515BI0100001116 | 330 | metre |
|---|
| 7 | 4.2 | (ii) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire | BI01010001010000000000000515BI0100001117 | 36 | metre |
|---|
| 8 | 4.3 | (iii) 2 X 10 sq. mm + 1 X 10 sq. mm earth wire | BI01010001010000000000000515BI0100001118 | 3 | metre |
|---|
| 9 | 5 | Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (Make : Havells / Polycab / R R KABEL / Finolex ) | | | |
|---|
| 10 | 5.1 | i) 3 x 1.5 sq. mm | | 60 | metre |
|---|
| 11 | 5.2 | ii) 3 x 4 sq. mm | | 30 | metre |
|---|
| 12 | 6 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair (Make : Havells / Polycab / R R KABEL / Finolex ) | | 80 | metre |
|---|
| 13 | 7 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. (Make : Havells / Polycab / R R KABEL / Finolex ) | | 60 | metre |
|---|
| 14 | 8 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (Make : Havells / Polycab / R R KABEL / Finolex ) | | | |
|---|
| 15 | 8.1 | (i) 20 mm | | 80 | metre |
|---|
| 16 | 8.2 | (ii) 25 mm | | 60 | metre |
|---|
| 17 | 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (Make : Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | | | |
|---|
| 18 | 9.1 | i) 5/6 amps switch | | 17 | each |
|---|
| 19 | 9.2 | ii) 3 pin 5/6 amp socket outlet | BI01010001010000000000000515BI0100001119 | 17 | each |
|---|
| 20 | 9.3 | (i) Telephone socket outlet | BI01010001010000000000000515BI0100001120 | 8 | each |
|---|
| 21 | 9.4 | (ii) TV antena socket outlet | BI01010001010000000000000515BI0100001121 | 6 | each |
|---|
| 22 | 10 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. (Make : Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | BI01010001010000000000000515BI0100001122 | 17 | each |
|---|
| 23 | 11 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. (Make :Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | BI01010001010000000000000515BI0100001123 | 40 | each |
|---|
| 24 | 12 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. | BI01010001010000000000000515BI0100001124 | | |
|---|
| 25 | 12.1 | 1 or 2 Module (75 mmX75 mm) | BI01010001010000000000000515BI0100001125 | 14 | each |
|---|
| 26 | 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. | BI01010001010000000000000515BI0100001126 | 6 | each |
|---|
| 27 | 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. (Make : Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | | 14 | each |
|---|
| 28 | 15 | Supplying and fixing Ding dong suitable for DC/AC single phase 230 volts, complete as required as per the direction of engg -in- charges. | | 8 | Nos |
|---|
| 29 | 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/6 A modular switch, connections etc. as required. (Make : Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | | 30 | each |
|---|
| 30 | 17 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. (Make : Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | | 17 | each |
|---|
| 31 | 18 | Supplying and fixing PVC Battan/Angle holder including connection etc. as required. | | 3 | each |
|---|
| 32 | 19 | Supply, installation, testing and commissioning of 1200 mm (nominal size), 20 watt / 22 watt LED batten luminaire in aluminium housing with minimum light output 100 lumen/watt complete with all accessories, electronic driver, diffuser, directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.\n( Approved Makes : Philips / GE/ Havells/ Wipro/ Crompton/Jaquar /GM) | | 21 | each |
|---|
| 33 | 20 | Supply, installation, testing and commissioning of 18 Watt /22 Watt surface mounted LED downlighter luminaire complete with all accessories and electronic driver, directly on ceiling / wall, including connections etc. as required.\n (Approved Makes : Philips / GE/ Havells/ Wipro/ Crompton/Jaquar only ) | | 13 | each |
|---|
| 34 | 21 | Supply, installation, testing and commissioning of wall mounted light fixture complete with B22 base, diffuser and 10 watt LED blub etc as required directly on wall, including connections etc. as required.(Approved Makes:- Havells City 3 Wall light / or equivalent model Philips / GE/ Wipro/ Crompton / Osram/Jaquar/GM) | | 6 | each |
|---|
| 35 | 22 | Supply, installation, testing and commissioning of 34 to 40 watt 2' X 2' LED surface Mounted LED Panel Light, having lumen out put minimum 100 lumen/watt, complete with all accessories, diffuser and electronic driver in metallic housing directly on ceiling, including connections etc. as required. (Make : LHEWEIP7IW1W034 model of Havells or equivalent specification in phillips / GE /GM /Jaquar ) | | 19 | each |
|---|
| 36 | 23 | Supply, installation, testing and commissioning of 10 watt LED bulkhead fittings with IP 66 ingress protection complete with all accessories and electronic driver, etc as required directly on wall, including connections etc. as required. \n (Approved Makes : Philips / GE/ Havells/ Wipro/ Crompton/Jaquar /GMonly )\n | | 10 | each |
|---|
| 37 | 24 | Supply, installation, testing and commissioning of 600 mm (nominal size) 9/10 watt LED batten luminaire with minimum light output 100 lumen/watt complete with all accessories, electronic driver, diffuser, directly on ceiling/ wall, including connections etc. as required.( Approved Makes :- Wipro Garnet 10W LED Batten or equivalent model of Havells/ Crompton / Philpis / GE) | | 5 | each |
|---|
| 38 | 25 | Supplying and fixing suitable size GI box in recess, including providing and fixing of 3/4 watt 4 Module LED Footlight, connection etc. as required. (Make : Legrand / Anchor Roma / Havells /Crabtree /L&T/ ABB/Panasonic.) | | 11 | each |
|---|
| 39 | 26 | Supply, installation, testing and commissioning of 50 Watt LED Flood light luminaire made out of cast aluminium housing and toughened glass cover with IP65 degree of protection complete with all accessories, mounting bracket and electronic driver with minimum lumen efficacy of 100 Lm/W, directly on ceiling/ wall, including connection with 3 x 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required as per direction of engg-In-charge. (Make : Havells / Philips / GE ) | | 6 | each |
|---|
| 40 | 27 | Supplying and installation of fresh air fan with louver shutter 250 mm sweep in the existing opening including making the hole to suit the size of the above fan and making good the damage, connection, testing , commissioning etc as required.\n(Havells make Ventil Air-DX with self opening louvers or with similar specificationsC&G / Orient / Usha / Almonard) | | 5 | each |
|---|
| 41 | 28 | Supplying and installation of 300 mm sweep, 1400 RPM heavy duty exhaust fan complete with louvers/shutters in the existing opening, including making the hole to suit the size of the above fan and making good the damage, connection, testing, commissioning etc. as required. (Havells make ISI mark Turbo force Heavy Duty Exhaust Fan or with similar specifications C&G / Orient / Usha / Almonard) | | 7 | each |
|---|
| 42 | 29 | Supplying, Installation, testing and commissioning of 5 star rated, 1200 mm sweep ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. ( Approved Makes :- Usha/ Havells/ Crompton / Orient) | | 11 | each |
|---|
| 43 | 30 | Supplying, installation, testing and commissioning of BEE 5 star rating, 15 litres capacity water storage heater, with safety system for protection against dry heating, over heating and over pressure, external adjustable thermostat, 16 Amp, 3 Pin Plug Top and 02 nos 450mm length flexible connection pipe suitable for working with 230V AC, 50 Hz, 1 Phase supply etc as required. Top, . (Make: Puro plus of Havells or with similar specifications in Crompton/ AO Smith /Racold make) | | 5 | each |
|---|
| 44 | 31 | Supplying, installation testing and commissioning of BEE 5 star rating, 25 litres capacity water storage heater, with safety system for protection against dry heating, over heating and over pressure, external adjustable thermostat, suitable rating 3 Pin Plug Top and 02 nos 450mm lenghth flexiable connection pipe suitable for working with 230V AC, 50 Hz, 1 Phase supply etc as required.(Make: Puro plus of Havells or with similar specifications in Crompton/ AO Smith /Ra cold make) | | 2 | each |
|---|
| 45 | 32 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) \nMake: L&T /Legrand /ABB /Schneider | | | |
|---|
| 46 | 32.1 | 8 way (4 + 24), Double door | | 2 | each |
|---|
| 47 | 33 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) Make: L&T /Legrand /ABB /Schneider | | | |
|---|
| 48 | 33.1 | 16 way Double door | | 1 | each |
|---|
| 49 | 34 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. (Make: L&T /Legrand /ABB /Schneider ) | | | |
|---|
| 50 | 34.1 | For 14 way, Double door SPN MCBDB | | 1 | each |
|---|
| 51 | 35 | Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and· commissioning etc. as required. (Make: L&T /Legrand /ABB /Schneider) | | | |
|---|
| 52 | 35.1 | (i) For 8 way, Double door TPN MCBDB | | 2 | each |
|---|
| 53 | 36 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make: L&T /Legrand /ABB /Schneider ) | | | |
|---|
| 54 | 36.1 | Single pole | | 64 | each |
|---|
| 55 | 36.2 | Double pole | | 1 | each |
|---|
| 56 | 36.3 | Triple pole and neutral | | 2 | each |
|---|
| 57 | 37 | Supplying and fixing 63 A rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make: L&T /Legrand /ABB /Schneider ) | | 2 | each |
|---|
| 58 | 38 | Supply, Installation, Testing and Commissioning of double door, out door type totally enclosed, dust and vermin proof, pedestal mounted Main Feeder Pillar of suitable size but not less than 1500 mm wide X 1200 mm high X 400 mm (deep) fabricated from 2 mm thick CRCA sheet steel, having double door in the front, front and rearside openable hinged type door (double leaf), front and back tapered top, consisting of 300 Amps 4 strip aluminium bus bars with heat shrinkable coloured sleeves and including DMC / SMC bus bar supports at required intervals for complete cross section, complete with detachable cable gland plates made of 3 mm thick CRCA sheet, earthing studs, separators, supports and insulators. The feeder pillar should be provided with suitable size terminal blocks for incoming & outgoing cables. From MCCB to terminal blocks connection will be done with solid aluminium bus bar / conductor. Incoming / outgoing cables will be terminated in terminal blocks. Including pre paint treatment, phosphating and powder coating by approved Siemens grey paint, suitable for operation on 433 volt, 50 Hz, 3 phase, 4 wire A. C. supply system complete including providing and fixing the following mountings, switchgears and accessories therein, etc as required. The feeder pillar shall be supplied with suitable pedestal of 50mm x 50 mm x 6 mm angle iron frame with 900 mm long legs. The 4 legs of the above feeder pillar are to be grouted in cement concrete 1:3:6 (1 Cement :3 Coarse sand: 6 Graded Stone aggregate 40 mm nominal size) foundation 60 cms. below ground level and 30 cms. above ground including finishing etc (embedded legs, should not be less than 450 mm) including plastering complete as required as per specifications (drawing will be get approved before fabrication of panel) | | | |
|---|
| 59 | 38.1 | (i) 200 A, FP MCCB 35 KA, Ics = 100% Icu, with adjustable thermal and adjustable magnetic release (S/C & O/L) protection, with spreader terminals : 1 No (Make: L&T/ABB/Siemens/Schenider/Legrand)\n(ii) 125 A, TP MCCB, 35 KA, Ics = 100% Icu, with adjustable thermal and fixed magnetic release (S/C & O/L) protection, with spreader terminals : 1 No. (Make: L&T/ABB/Siemens/Schenider/Legrand)\n(iii) 80 A, TP MCCB, 35 KA, Ics = 100% Icu, with adjustable thermal and fixed magnetic release (S/C & O/L) protection, with spreader terminals : 5 No. (Make: L&T/ABB/Siemens/Schenider/Legrand)\n(iii) 63 A, TP MCCB, 35 KA, Ics = 100% Icu, with adjustable thermal and fixed magnetic release (S/C & O/L) protection, with spreader terminals : 1 No. (Make: L&T/ABB/Siemens/Schenider/Legrand)\n(iii) Indicator Lamp LED type 3 Nos\n(iv) 6A SP MCB 10kA (for Cont. Ckt.): 3 Nos.\nv) 1 No. M.V danger notice plate on front side.\n | | 1 | Nos |
|---|
| 60 | 39 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. | | | |
|---|
| 61 | 39.1 | 3.5 X 35 sq. mm (32 mm) | | 5 | Nos |
|---|
| 62 | 39.2 | 3.5 X 120 sq. mm (45 mm) | | 2 | Nos |
|---|
| 63 | 40 | Supplying and laying of G.I. pipe of 50 mm dia.(nominal), medium class, ISI marked in wall / floor including cutting chase, and making good the wall/ floor and finishing with matching surface after housing G.I. pipe in chase etc as required. ( for protection of UG cable) | | 19 | metre |
|---|
| 64 | 41 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. Direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc complete as required. (REX Polyextrusion / Jain Irrigation / Duraline / Avadh Polytube/ Gemini make) | | | |
|---|
| 65 | 41.1 | 90 mm dia (OD-90 mm & ID-76 mm nominal) | | 90 | metre |
|---|
| 66 | 42 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing HDPE/RCC/ HUME/ METAL pipe as required. (ISI marked Make Havells /Polycab/ Finolex /CCI /KEI /RR Kabel) | | | |
|---|
| 67 | 42.1 | i) 3.5 X 35 sqmm | | 40 | metre |
|---|
| 68 | 42.2 | ii) 3.5 X 120 sqmm | | 50 | metre |
|---|
| 69 | 43 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing masonry open duct , for loose connection etc as required. (ISI marked Make Havells /Polycab/ Finolex /CCI /KEI /RR Kabel) | | | |
|---|
| 70 | 43.1 | i) 3.5 X 35 sqmm | | 12 | metre |
|---|
| 71 | 43.2 | ii) 3.5 X 120 sqmm | | 4 | metre |
|---|
| 72 | 44 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.. | | 3 | sets |
|---|
| 73 | 45 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling etc as required. | | 6 | metre |
|---|
| 74 | 46 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required | | 6 | metre |
|---|
| 75 | 47 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required | | 190 | metre |
|---|