| 1 | 1 | COLD ROOMS:\n\nThe design parameters for the Chiller Room are:-\n\nExternal Chiller Room Size in Mtrs. :6.0 Mtrs. (External) X 4.0 Mtrs.(External) X 2.4 Mtrs. (External) (H)\nNumbers of Room :01\nRoom Temperature required :+ 9 Deg C (+/-) 2 & RH (=/<) 90%, Max Ambient Temperature :46°C\nMaterial Of Insulation :100 mm Polyurethane Foam (PUF) Your Scope of supply, Density of panels :40 +/- 2 Kg/cubic meter, Thickness Of Insulation for walls/Ceiling:100 mm, Thickness Of Insulation for floor:100 mm PUF Panels, Lamination for walls/Ceiling :PPGI- 0.5 mm Sheet on both sides Lamination for floor :Kota Flooring over the 100 mm PUF slabs – ( Kota shall be in your scope) Sliding Door Clear Opening (Meters ) : 1.5 meters x 2.1 meters, Insulation Thickness :90 mm, Type Of Door :Sliding Door, Number of doors :01 ( Each Room), Lamination for door: PP G.I. Sheet on both sides The design parameters for the Chiller Room are:- Product Exotic Flower and Fruits, Product Incoming, Temperature At temp + 30 0C, Room Temperature +9 Deg C To +15 Deg C, Pull Down Time 24 Hrs, Rate of, Loading 15 MT Per Day, No. of Units/ Chamber 01, Heat Load 74376 BTUH – (Heat load Attached for your reference), Offered Refrigeration Capacity 40000/ BTUH x 2 = 80000/BTUH, Total Refrigeration Units 02 Each Room, Type of condenser Air cooled, Type of compressor Hermetic Scroll Refrigerant 404A, Compressor Run Time 18 HRS., Air Volume 8891 CMH x 2 = 17782 CMH, Electricity Power Supply 415 V/ 3 phase/ 50hz, Temperature indicator Digital Temperature indicator cum controller, Defrost Cycle Air Defrost, Door Opening 1 / Per hours, Power consumption per machine : 5.6 KW x 2 = 12.2 KW. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/ Rinac. | | | |
|---|
| 2 | 1.1 | Exotic Flowers & Fruits - 15MT:\n(a) Supply and installation of eco friendly cyclopentane PUF Panels 100mm thick with CAM lock mechanism for chiller room,\nSize: 6M (External) X 4 M(External) X 2.4M (External) (H). Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item2 | 1 | Set |
|---|
| 3 | 1.2 | (b)Supply and installation of Floor insulation :- 100 mm PUF slab bitumen & tar felt for flooring . Makes of PUF panel are Jindal/Lloyd/Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item3 | 1 | set |
|---|
| 4 | 1.3 | (c) Supply and installation of sliding door size 1500mm x 2100mm made of 100mm PUF panel. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item5 | 1 | Set |
|---|
| 5 | 1.4 | (d) Supply, installation, testing and commissioning of Blue star/Emersion Copland/Bitzer/Thermo King/Arctic makes preassembled & tested refrigeration system to maintain a temp. of +9 deg C with a cir cooled condensing unit and separate evaporator of split type complete with hermetic scroll compressor capacity 40000/Btuh at +4 deg C room temp. & 43 deg C ambient temp. | item6 | 2 | Set |
|---|
| 6 | 2 | The design parameters for the Chiller Room:\n\nExternal Chiller Room Size in Mtrs. 6.0 Mtrs. (External) X 4.0 Mtrs.(External) X 2.4 Mtrs. (External) (H)\nNumbers of Room 01\nRoom Temperature required + 9 Deg C (+/-) 2 & RH (=/<) 90%\nMax Ambient Temperature 46°C, Material Of Insulation 100 mm Polyurethane Foam (PUF) Your Scope of supply, Density of panels 40 +/- 2 Kg/cubic meter, Thickness Of Insulation for walls/Ceiling 100 mm, Thickness Of Insulation for floor 100 mm PUF Panels, Lamination for walls/Ceiling PPGI- 0.5 mm Sheet on both sides, Lamination for floor Kota Flooring over the 100 mm PUF slabs – ( Kota shall be in your scope), Sliding Door Clear Opening (Meters ) 1.5 meters x 2.1 meters, Insulation Thickness 90 mm, Type Of Door Sliding Door, Number of doors 01 ( Each Room), Lamination for door PP G.I. Sheet on both sides, The design parameters for the Chiller Room are:-, Product Exotic Flower and Fruits, Product Incoming Temperature At temp + 30 0C, Room Temperature +2 Deg C To +8 Deg C, Pull Down Time 24 Hrs, Rate of, Loading 15 MT Per Day, No. of Units/ Chamber 01, Heat Load 99268 BTUH – (Heat load Attached for your reference), Offered Refrigeration Capacity 40000/ BTUH x 3 = 120000/BTUH, Total Refrigeration Units 03 Each Room, Type of condenser Air cooled, Type of compressor Hermetic Scroll, Refrigerant 404A, Compressor Run Time 18 HRS., Air Volume 8891 CMH x 2 = 17782 CMH, Electricity Power Supply 415 V/ 3 phase/ 50hz, Temperature indicator Digital Temperature indicator cum controller, Defrost Cycle Air Defrost, Door Opening 1 / Per hours, Power consumption per machine : 5.6 KW x 3 = 16.8 KW. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac . | | | |
|---|
| 7 | 2.1 | Exotic Flowers & Fruits - 15MT:\n(a) Supply and installation of eco friendly cyclopentane PUF Panels 100mm thick with CAM lock mechanism for chiller room,\nSize: 6M (External) X 4 M(External) X 2.4M (External) (H). Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac . | item9 | 1 | Set |
|---|
| 8 | 2.2 | (b) Supply and installation of Floor insulation :- 100 mm PUF slab bitumen & tar felt for flooring. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item10 | 1 | Set |
|---|
| 9 | 2.3 | (c)Supply and installation of sliding door size 1500mm x 2100mm of 100mm PUF panel. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item12 | 1 | Set |
|---|
| 10 | 2.4 | (d) Supply, installation, testing and commissioning of Blue star/Emersion Copland/Bitzer/Thermo King/Arctic makes preassembled & tested refrigeration system to maintain a temp. of +2 deg C with a cir cooled condensing unit and separate evaporator of split type complete with hermetic scroll compressor capacity 40000/Btuh at +4 deg C room temp. & 4 | item13 | 3 | Set |
|---|
| 11 | 3 | External Chiller Room :\nSize in Mtrs. : 7.6 Mtrs. (External) X 9.6 Mtrs.(External) X 2.4 Mtrs. (External) (H)\nNumbers of Room : 01\nRoom Temperature required : + 9 Deg C to 15 Deg C\nMax Ambient Temperature : 46°C, Material Of Insulation : 100 mm Polyurethane Foam (PUF) Your Scope of supply, Density of panels : 40 +/- 2 Kg/cubic meter, Thickness Of Insulation for walls/Ceiling : 100 mm, Thickness Of Insulation for floor : 100 mm PUF Panels, Lamination for walls/Ceiling : PPGI- 0.5 mm Sheet on both sides, Lamination for floor : Kota Flooring over the 100 mm PUF slabs – ( Kota shall be in your scope), Sliding Door Clear Opening (Meters ) : 1.5 meters x 2.1 meters, Insulation Thickness : 100 mm, Type Of Door : Sliding Door, Number of doors : 01 ( Each Room), Lamination for door : PP G.I. Sheet on both sides, The design parameters for the Chiller Room are:-, Product : Exotic Flower and Fruits, Product Incoming Temperature : At temp + 30 0C, Room Temperature : +9 Deg C To 15 Deg C, Pull Down Time : 24 Hrs, Rate of Loading : 50 MT Per Day, No. of Units/ Chamber : 01, Heat Load : 223435/ BTUH, Offered Refrigeration Capacity : 80000/ BTUH X 3 = 240000/ BTUH, Total Refrigeration Units : 03 Each Room, Type of condenser : Air cooled, Type of compressor : Hermetic Scroll, Refrigerant : 404A, Compressor Run Time : 18 HRS., Air Volume : 19890 CMH x 3 = 59670 CMH, Electricity Power Supply : 415 V/ 3 phase/ 50hz, Temperature indicator : Digital Temperature indicator cum controller, Defrost Cycle : Air Defrost, Door Opening : 1 / Per hours, Power consumption per machine : 11.2KW x 3 = 33.6 KW. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic /Rinac. | | | |
|---|
| 12 | 3.1 | Exotic Flowers & Fruits - 15MT:\n(a) Supply and installation of eco friendly cyclopentane PUF Panels 100mm thick with CAM lock mechanism for chiller room, Size: 7.6M (External) X 9.6 M(External) X 2.4M (External) (H). Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item16 | 1 | Set |
|---|
| 13 | 3.2 | (b) Supply and installation of floor insulation: 100mm PUF slab bitumen & Tar felt for flooring . Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item17 | 1 | set |
|---|
| 14 | 3.3 | (c ) Supply and installation of sliding door size 1500mm x 2100mm made of 100mm PUF panel. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item18 | 1 | Set |
|---|
| 15 | 3.4 | (d) supply, installation, testing and commisioning of Blue star/Emersion Copland/Bitzer/Thermo King/Arctic makes pre assembled & tested refrigeration system to maintain a temp of +9 deg Celcius with air cooled condensing unit and separate evaporator of split type complete with hermetic scroll compressor capacity 80000/Btuh at +4 deg C room temperature & 43 degC ambient temp. | item19 | 3 | Set |
|---|
| 16 | 4 | The design parameters for the freezer Room:\nExternal Chiller Room Size in Mtrs. : 6.0 Mtrs. (External) X 4.0 Mtrs.(External) X 2.4 Mtrs. (External) (H)\nNumbers of Room : 01\nRoom Temperature required : - 4 Deg C to -20 Deg C, Max Ambient Temperature : 46°C, Material Of Insulation : 100 mm Polyurethane Foam (PUF) Your Scope of supply, Density of panels : 40 +/- 2 Kg/cubic meter, Thickness Of Insulation for walls/Ceiling : 100 mm, Thickness Of Insulation for floor : 100 mm PUF Panels, Lamination for walls/Ceiling : PPGI- 0.5 mm Sheet on both sides, Lamination for floor : Kota Flooring over the 100 mm PUF slabs – ( Kota shall be in your scope), Sliding Door Clear Opening (Meters ) : 1.5 meters x 2.1 meters, Insulation Thickness : 100 mm, Type Of Door : Swing Door along with Heters, Number of doors : 01 ( Each Room), Lamination for door : PP G.I. Sheet on both sides, The design parameters for the Chiller Room are:-Product : Pharma and Food, Product Incoming Temperature : At temp -4 Deg C, Room Temperature : -20 Deg C (+-2 Deg C), Pull Down Time : 24 Hrs, Rate of Loading : 15 MT Per Day, No. of Units/ Chamber : 01, Heat Load : 34774/ BTUH, Offered Refrigeration Capacity : 18000/ BTUH x 2 = 36000 /BTUH, Total Refrigeration Units : 02 Each Room, Type of condenser : Air cooled, Type of compressor : Hermetic Recip Refrigerant : 404A, Compressor Run Time : 18 HRS., Air Volume : 9344 CMH x 2 = 18688 CMH, Electricity Power Supply : 415 V/ 3 phase/ 50hz, Temperature indicator : Digital Temperature indicator cum controller, Defrost Cycle : Air Defrost, Door Opening : 1 / Per hours, Power consumption per machine : 11.3 x 2= 22.6 KW. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | | | |
|---|
| 17 | 4.1 | Pharma & Food - 15MT:\n(a) supply and installation of eco friendly cyclopentane PUF panels 100mm thick with cam lock mechanism for chiller room, size 6M(External) X 4M(External) X 2.4M(External (H)). Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item21 | 1 | set |
|---|
| 18 | 4.2 | (b) Supply and installation of floor insulation: 100mm PUF slab bitumen & Tar felt for flooring. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac. | item22 | 1 | Set |
|---|
| 19 | 4.3 | (c) Supply and installation of sliding door size 1500mm x 2100mm made of 100mm PUF panel. Makes of PUF panel are Jindal/Lloyd /Metacno/Sintex/Suchi/Alaska/Arctic/Rinac . | item23 | 1 | Set |
|---|
| 20 | 4.4 | (d) supply, installation,testing and commisioning of Blue star/Emersion Copland/Bitzer/Thermo King/Arctic makes pre assembled & tested refrigeration system to maintain a temp of -20 deg Celcius with air cooled condensing unit and separate evaporator of split type complete with hermetic scroll compressor capacity 18000/Btuh at -20 deg C room temp. | item24 | 2 | Set |
|---|
| 21 | 5 | HVAC WORKS:\n\nAir Cooled Ductable type Split units:\nSupply, installation, testing and commissioning of Carrier/Hitachi/Daikin/Blue Star makes Air Cooled Ductable Split airconditioners each comprising an outdoor unit consisting of Rotary/hermetically sealed Scroll single or multi compressor, air cooled condensing unit, Condenser fan etc. with outer casing and indoor fan coil unit(s) consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with microprocessor based controller and full charge of gas & oil etc. both inter connected with communication wiring (6Cx1.5sqmm copper communication wire), M.S. base frame, Fire retardent canvas connection,supports etc. complete as per specifications and drawings. The cost shall also include angle iron(40x40x3) stands for outdoor units. The Copper Pipe and Electrical Cable connection up to 5 Mtr considered also in quoated cost. \n\nDuctable Splits Air-conditioners Equipment - Machine designed at 35°C ambient and machines workable at 50°C ambient and external static pressure is 10 mmwg. \n\nSupply of Ductable Split Air-conditioners Equipments Suitable for R- 22/410a Refrigerant and 415+/-10% Power Supply at Site Basis:(Note: All power supply at indoor or near by indoor units.) \nOutdoor Condensing Units:\nFully Factory assembled,wired and tested Indoor and Outdoor\nCondensing Units as per specifications ans as required to make the system complete. i. 11.0 TR/4400 with Multiple compressor (Ceiling Mounted Ductable). \n | item25 | 4 | No |
|---|
| 22 | 6 | Supply, Installation, Testing and Commissioning of Control cum Transmission wiring(4C x1.5sqmm.) in suitable conduits between indoor & outdoor units including supply of screened wires, supports, installation , saddles, ties, tags, ferrules, lugs, nuts/bolts/hardware etc. complete in all respects as per specifications and any other item required to make the system complete. | item26 | 150 | rmt |
|---|
| 23 | 7 | Supply, installation, testing and commissioning of Interconnected Copper Piping (Soft/Hard both) (1/2\",3/8\",5/8\",7/8\",11/8\") for Ductable/Packaged Split Air\nconditioners, the piping duly insulated with Nitrile insulation (13/19mm ) tubes of respective sizes and control cabling from Indoor to Outdoor units complete with supports & properly clamped and al. foil or tape on the top of tube surface as per design. | item27 | 130 | rmt |
|---|
| 24 | 8 | Supply, installation, testing and commissioning of Interconnected Electrical wiring between Isolator and condensing units including Power cables from Power supply switch/socket to condensing units , conduit, Fittings etc. as required complete as per design and specifications of the manufacturer 4 C x 10 sqmm. Copper (armoured) | item28 | 15 | rmt |
|---|
| 25 | 9 | Supply and filling of Gas for charging of ductable outdoor unit for additional piping length R-22 | item29 | 5 | kg |
|---|
| 26 | 10 | Providing & fixing rigid PVC piping complete with fittings, supports as per specifications and pre insulated with 6mm thick closed cell elastomeric nitrile rubber tubular insulation. | item30 | | |
|---|
| 27 | 10.1 | 50 mm dia | item31 | 5 | rmt |
|---|
| 28 | 10.2 | 40 mm dia | item32 | 5 | rmt |
|---|
| 29 | 10.3 | 32 mm dia | item34 | 10 | rmt |
|---|
| 30 | 10.4 | 25 mm dia | item35 | 10 | rmt |
|---|
| 31 | 11 | CANVASS CONNECTION:\n\nSupply,Installation,Testing and commissioning of doble layer canvas connection with 1/2 hr. fire rating as per specification.\nMakes Saiductfab/Vega Flex. | item36 | 4 | No |
|---|
| 32 | 12 | PROPELLER FAN :\nSupply,installation,testing and commissioning of Propeller fan of the following capacity of approved make and specification. Fan shall be supplied with aluminum gravity louver & bird screen and with three speed control 300 mm dia propeller fan, with single phase motor.\nMakes Flowline India Pvt Ltd/Nadi Airtechnics Pvt Ltd/ Servogear. | item37 | 7 | No |
|---|
| 33 | 13 | AIR CURTAIN:\nSupply,installation testing and commissioning of AIR CURTAIN of following size with auto sensor/ door switch as per approved make. (At ground entrance 1500 mm long (High flow type).\nMakes Euronics/Orchids/Eureka. | item38 | 6 | No |
|---|
| 34 | 14 | Supply, fabrication, installation, and testing of sheet metal ducts in accordance with the approved shop drawings and as per specifications (Duct shall be fabricated at site as per followings): | item39 | | |
|---|
| 35 | 14.1 | 24 gauge galvanized sheet steel (0.63mm) | item40 | 300 | sqm |
|---|
| 36 | 14.2 | 22 gauge galvanized sheet steel (0.80mm) | item41 | 50 | sqm |
|---|
| 37 | 15 | Supplying, installing, testing and balancing of aluminium supply/return air grills of various sizes. Each grill shall be with fixed horizontal front bar at Zero/15 Deg deflection through the collar and register. | item42 | | |
|---|
| 38 | 15.1 | Aluminium supply air grilles with damper. | item43 | 4 | sqm |
|---|
| 39 | 15.2 | Supply and installation of Aluminium Exhaust/return air grilles without damper. | item44 | 4 | sqm |
|---|
| 40 | 15.3 | Supply and installation of AI Volume control dampers for ducts | item45 | 1 | rmt |
|---|
| 41 | 16 | Fresh Air/Exhaust Air Louvers:\n\nSupply, Installation, Testing and Commissioning of extruded aluminium louvres with frame bird screeen, mounting arrangement etc. as per specifications and drawings. Fresh Air/Exhaust Louvers | item46 | 0.5 | sqm |
|---|
| 42 | 17 | Acoustic Insulation:\n\nSupply and Application of Acoustic Insulation Inside the Duct with Engineered Nitrile Rubber open cell foam with Density 140 - 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in EPA approved antimicrobial protection; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents. 19mm thick | item47 | 40 | sqm |
|---|
| 43 | 18 | External Thermal Insulation:\n\nSupply & Installation of Thermal Insulation with pre laminated 7 mil Glass cloth covering over Closed Cell Class O Nitrile Rubber Elastomeric Insulation & built-in EPA approved antimicrobial protection of Density 40 - 55 Kg/m3, Thermal Conductivity of 0.033 W/mk at 0 Deg Celcius Mean Temp. and µ=10000 (without any additional vapour barrier), to be applied on Ducts using manufacturer's recommended Rubber based Adhesive in a blend of solvents, 9 MM Thick | item48 | 325 | sqm |
|---|
| 44 | 19 | Exposed Roof Insulation\n\nSupply,application of under deck insulation of roof exposed to direct sun , with elastomeric Nitrile Rubber with Alu foil faced.Rubber based contact adhesive recommended by the manufacturer shall be used. The foam sheets shall be cut to, required size and a thin layer of adhesive shall be applied to both the surfaces; ceiling and insulation,it is applied / stuck with enough pressure to the walls/ceiling. Minimum, 5 fasteners with washer (of G.I Sheet 2.5 inch x 2.5 inch) / square meter, 4 at corners, & 1 at centre shall be put immediately after sticking with the help of adhesive. The length of the fastener shall be minimum 75 mm. \n(i) 25 mm thick: | item49 | 600 | sqm |
|---|