| 1 | 1 | Diesel Generator set- Acoustic | | | |
|---|
| 2 | 1.01 | Supply of 315 KVA Diesel Generator Set, developing 1500RPM with an overloading capacity of 10% for one hour in any 12 continuous hours opeartion Generally confirms to BS:5514, directly coupled to 315 KVA at 0.8 Power factor, 415V, 3 Phase , 4 wires, 50 cycles per second self excited, self regulated, with brushless excitation, Alternator generally confirms to BS:5000/ IS:4722. DG set shall be complete with radiator, residential type silencer, electronic governor, cable termination box , MS mounting frame, fuel piping, diesel day tank, Battery mounting frame, oil level indicator with guage board, and all other accessories as per specifications and schedule. Diesel Generator set shall be mounted on cushy foot or similar type of vibration Isolators. The cost of Exhaust pipe shall be excluded in this item. The cost shall include fuel oil required for testing of DG Set at full load. | | 1 | Nos |
|---|
| 3 | 1.02 | Engine\n6 cylinder, In-line 4 stroke, radiator cooled engine complete with Diesel Engine suitable for Generator application\nAir to air cooling\nIntegral set-mounted radiator system\nElectrical starter motor with soft start\nBattery charging alternator, ƒ 2 x 12 V DC batteries\n | | | |
|---|
| 4 | 1.03 | Alternator\nSelf excited alternator conforming to IS/IEC 60034-1 \nSpecial Windings to Reduce Harmonics\nEpoxy gel coating on the winding\n | | | |
|---|
| 5 | 1.04 | Controller\nMicroprocessor based Graphical LCD display\nIntegrable with AMF, synch & communication configuration\n | | | |
|---|
| 6 | 1.05 | Canopy\nConforming to UL94-HF1 class for flammability\nNoise absorbant and fire-retardant grade acoustic insulation material (Rockwool) complying to IS 8183\nMoEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions\n | | | |
|---|
| 7 | 1.06 | Monitor Display\nPhase Voltages & Currents, Frequency, Reverse power, Genset kVA, kW, kWh, kVAr, Power Factor, Canopy Temperature\nLube oil Pressure, Engine Temperature, RPM, Run Hours, Number of starts, Fuel Level, Auto / Manual Stop\nBattery charge condition\n | | | |
|---|
| 8 | 1.07 | Outgoing Breaker\n630 A, FP MCCB with thermal magnetic and electronic release 36kA rating, Conform to IEC 60947-2 - Sealable adjustment, Thermal adjustable from 0.8 to 1 In, Magnetic adjustable from 5 to 10 In.\n | | | |
|---|
| 9 | 2 | Acceptable Make - Cummins Engine , Caterpilar Engine & Kirloskar Engine | | | |
|---|