Indian Oil Corporation Limited-IOCL has published Design , Supply , Installation , Testing And Commissioning Of Tank Farm Management System Along With Associated Works At Raxaul Depot Under Bihar State Office. Submission Date for this Tender is 30-09-2019. Application Software Tenders in Raxaul Depot Bihar. Bidders can get complete Tender details and download the document.
Name of Work: Design, Supply, Installation, Testing & Commissioning of Tank Farm Management System along with associated works at Raxaul Depot under Bihar State Office | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Supply Part | BI01010001010000000000000515BI0100001112 | ||
2 | 2 | Tank Farm Management System | BI01010001010000000000000515BI0100001113 | ||
3 | 3 | Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001114 | ||
4 | 4 | For Cone Roof Vertical tanks (Primary and Secondary Radar Gauges) | BI01010001010000000000000515BI0100001115 | 14 | EA |
5 | 5 | For Internal Floating Roof Vertical tanks (Primary and Secondary Radar Gauges -) | BI01010001010000000000000515BI0100001116 | 6 | EA |
6 | 6 | For underground horizontal product tanks (Ethanol - 2 nos) | BI01010001010000000000000515BI0100001117 | 2 | EA |
7 | 7 | Supply of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001118 | ||
8 | 8 | For Water Tanks (4 nos.) | BI01010001010000000000000515BI0100001119 | 4 | EA |
9 | 9 | Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. | BI01010001010000000000000515BI0100001120 | ||
10 | 10 | With minimum 8 elements temperature sensor (for above ground tanks - MS, HSD, Ethanol) | BI01010001010000000000000515BI0100001121 | 10 | EA |
11 | 11 | With minimum 2 elements temperature sensor (for U/G horizontal tanks - 2 nos.) | BI01010001010000000000000515BI0100001122 | 2 | EA |
12 | 12 | Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001123 | ||
13 | 13 | For A/G Tanks with 3 elements | BI01010001010000000000000515BI0100001124 | 10 | EA |
14 | 14 | For U/G Tanks with 1 elements (Ethanol -2 nos) | BI01010001010000000000000515BI0100001125 | 2 | EA |
15 | 15 | Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001126 | ||
16 | 16 | For Vertical Product tanks - (Primary & Secondary Radar Gauges) | BI01010001010000000000000515BI0100001127 | 20 | EA |
17 | 17 | For U/G Product tanks (2 nos) | BI01010001010000000000000515BI0100001128 | 2 | EA |
18 | 18 | For Water Tanks (4 no) | BI01010001010000000000000515BI0100001129 | 4 | EA |
19 | 19 | Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document | BI01010001010000000000000515BI0100001130 | ||
20 | 20 | For Vertical Product tanks | BI01010001010000000000000515BI0100001131 | 10 | EA |
21 | 21 | For U/G Product tanks (2 nos) | BI01010001010000000000000515BI0100001132 | 2 | EA |
22 | 22 | Supply of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. | BI01010001010000000000000515BI0100001133 | ||
23 | 23 | For Primary Radar gauges installed on A/G product tanks, under ground product tank, water tank & Sludge tank | BI01010001010000000000000515BI0100001134 | 1 | EA |
24 | 24 | For Secondary Radar Gauges installed on A/G product tanks | BI01010001010000000000000515BI0100001135 | 1 | EA |
25 | 25 | Supply of TFMS Server(Redundant Type) (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 18.5" suitable for 24x7 operation, keyboard drawer, optical mouse, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. | BI01010001010000000000000515BI0100001136 | 2 | EA |
26 | 26 | Supply of TFMS Workstation with minimum 23" LED colour monitor, standard keyboard, mouse, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. | BI01010001010000000000000515BI0100001137 | ||
27 | 27 | 19" Rack type at Control Room, form factor - Rack, CPU height - 2U | BI01010001010000000000000515BI0100001138 | 1 | EA |
28 | 28 | Tower type at TM's room | BI01010001010000000000000515BI0100001139 | 1 | EA |
29 | 29 | Push Buttons Outside Dyke Walls | BI01010001010000000000000515BI0100001140 | ||
30 | 30 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, TBs, mounting structure, accessories etc complete as per specifications and tender document. | BI01010001010000000000000515BI0100001141 | ||
31 | 31 | For ROSOVs (A/G product tank's inlet & outlet line- 20 nos. ) | BI01010001010000000000000515BI0100001142 | 20 | EA |
32 | 32 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, TBs, mounting structure, accessories etc complete as per specifications and tender document. | BI01010001010000000000000515BI0100001143 | ||
33 | 33 | S/F of FLP Push Button for DBBVs | BI01010001010000000000000515BI0100001144 | 20 | EA |
34 | 34 | Control Room equipments | BI01010001010000000000000515BI0100001145 | ||
35 | 35 | Supply of Redundant SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: The offered safety PLC shall be of the same make family of the integrated Distributed Control System. | BI01010001010000000000000515BI0100001146 | 1 | SET |
36 | 36 | Supply of Complete Terminal Automation Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for TAS Management Server, Distributed Control System, Operator work stations, fire fighting OIC, Alarm display and annunciation OIC, Engineering Work Stations(for safety PLC & DCS), Web Server, OPC Server, Historian Server / work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nTAS software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- TAS- Management Server\n- TLF Automation System (TT reporting, registration & entry system, TT Queuing, FAN generation, Bay allocation, Additive Dosing system, Ethanol blending System, Interface with TLF equipments like BCU, MFM, Barrier Gates, Bay Queue Display, Bay allocation Display, Invoice generated display, rack monitors, Proximity card readers etc)\n-Tank Wagon loading Automation system\n-Tank Wagon unloading Automation system\n-Tank Lorry Decantation System\n-TT calibration System\n-Bio Diesel Blending system | BI01010001010000000000000515BI0100001147 | 1 | LS |
37 | 37 | Supply of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. | BI01010001010000000000000515BI0100001148 | ||
38 | 38 | For mounting of TFMS Server along with associated rack mounted monitors, rack mounted keyboard, mouse, power adapters, networking & OFC components, CIUs MCBs etc as per specification and tender document. | BI01010001010000000000000515BI0100001149 | 1 | EA |
39 | 39 | For mounting of Rack mounted Master Control Stations for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. | BI01010001010000000000000515BI0100001150 | 1 | EA |
40 | 40 | Supply of Operator Interface Console Computer (OIC) minimum 23" colour LED monitor, standard keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. | BI01010001010000000000000515BI0100001151 | ||
41 | 41 | 19" Rack type at Control Room, form factor - Rack, CPU height - 2U | BI01010001010000000000000515BI0100001152 | 2 | EA |
42 | 42 | Tower mounted type in TM's Cabin | BI01010001010000000000000515BI0100001153 | 1 | EA |
43 | 43 | Supply of Engineering Workstation (EWS) with minimum 23" colour LED monitor, standard keyboard, mouse, PLC & DCS software, HMI software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. (Locations: 1 no. in CR for both DCS and Safety PLC) - 19" Rack type at Control Room, form factor - Rack, CPU height - 2U | BI01010001010000000000000515BI0100001154 | 1 | EA |
44 | 44 | Supply of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like CCTV System, TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers, Access Control Server, Web Server Access over IOCL Intranet, connecting to OIC/ work stations etc which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices which needs OPC for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. | BI01010001010000000000000515BI0100001155 | 2 | EA |
45 | 45 | Supply of 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, TTES, EWS, OPC Servers, Fire fighting OICs, Alarm Display OIC, DCS, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. | BI01010001010000000000000515BI0100001156 | 2 | EA |
46 | 46 | Supply of Wall mounted Network Rack-minimum 15U 19" Rack for mounting of Terminal Server/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room, S&D for TAS equipments | BI01010001010000000000000515BI0100001157 | 2 | EA |
47 | 47 | UPS: Supply & Installation of appropriate capacity of UPS based on actual\r\nload calculation plus 20% spare or 20 kVA, whichever is greater Indoor type\r\nSuitable for input 3phase, 415Volts and out-put 220V A.C.,\r\n1-Ph, 50 Hz, and 3-phase N 415 Volts A.C. UPS with Parallel Redundant system with bypass Transformer, A.C. Distribution Board, VRLA SMF\r\nBattery Bank for both Inverter system [with 30 min battery\r\nback-up] and accessories in accordance with this\r\nrequisition, and UPS SLD attached. Complete as per\r\nspecifications / tender documents. | BI01010001010000000000000515BI0100001158 | 1 | SET |
48 | 48 | Supply of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader with accessories for powering DCS Panel, Safety PLC Panel, TAS-MS, OIC, EWS, TFMS System, TTES, printers, Bay Instruments other control room equipments, Tank Farm Instruments, CCTV system, Fire Detection System, Access control system, Bay Queue Display boards, other display boards, ROSOV ESD port, header line instruments and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. | BI01010001010000000000000515BI0100001159 | 1 | LS |
49 | 49 | Supply of IP based Redundant GSM modem suitable for 24x7 operation along with accessories for auto SMS as per specification and tender document. | BI01010001010000000000000515BI0100001160 | 1 | Set |
50 | 50 | Supply of minimum 42" HD LED monitor along with 1 no. of hooter, ACK push button, mounting accessories, cables etc for critical alarms display & annunciation complete as per specifications and tender document. | BI01010001010000000000000515BI0100001161 | 1 | EA |
51 | 51 | CABLING,JB,EARTHING | BI01010001010000000000000515BI0100001162 | ||
52 | 52 | Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc | BI01010001010000000000000515BI0100001163 | ||
53 | 53 | Supply of FRLS Armoured Copper Power cable as per tender specifications. | BI01010001010000000000000515BI0100001164 | ||
54 | 54 | 3C x 2.5 sqmm | BI01010001010000000000000515BI0100001165 | 1500 | RM |
55 | 55 | 12C x 2.5 sqmm | BI01010001010000000000000515BI0100001166 | 200 | RM |
56 | 56 | 24C x 2.5 sqmm | BI01010001010000000000000515BI0100001167 | 800 | RM |
57 | 57 | Supply of FRLS Armoured Copper Control cable as per tender specifications. | BI01010001010000000000000515BI0100001168 | ||
58 | 58 | 2C x 1.5 sqmm | BI01010001010000000000000515BI0100001169 | 1500 | RM |
59 | 59 | 4C x 1.5 sqmm | BI01010001010000000000000515BI0100001170 | 500 | RM |
60 | 60 | 8C x 1.5 sqmm | BI01010001010000000000000515BI0100001171 | 50 | RM |
61 | 61 | 10C x 1.5 sqmm | BI01010001010000000000000515BI0100001172 | 50 | RM |
62 | 62 | 12C x 1.5 sqmm | BI01010001010000000000000515BI0100001173 | 50 | RM |
63 | 63 | 16C x 1.5 sqmm | BI01010001010000000000000515BI0100001174 | 50 | RM |
64 | 64 | 18C x 1.5 sqmm | BI01010001010000000000000515BI0100001175 | 50 | RM |
65 | 65 | 20C x 1.5 sqmm | BI01010001010000000000000515BI0100001176 | 50 | RM |
66 | 66 | 24C x 1.5 sqmm | BI01010001010000000000000515BI0100001177 | 800 | RM |
67 | 67 | 32C x 1.5 sqmm | BI01010001010000000000000515BI0100001178 | 50 | RM |
68 | 68 | 36C x 1.5 sqmm | BI01010001010000000000000515BI0100001179 | 50 | RM |
69 | 69 | 48C x 1.5 sqmm | BI01010001010000000000000515BI0100001180 | 500 | RM |
70 | 70 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. | BI01010001010000000000000515BI0100001181 | ||
71 | 71 | 1P x 1.5 sqmm | BI01010001010000000000000515BI0100001182 | 1500 | RM |
72 | 72 | 2P x 1.5 sqmm | BI01010001010000000000000515BI0100001183 | 1500 | RM |
73 | 73 | 3P x 1.5 sqmm | BI01010001010000000000000515BI0100001184 | 50 | RM |
74 | 74 | 4P x 1.5 sqmm | BI01010001010000000000000515BI0100001185 | 500 | RM |
75 | 75 | 6P x 1.5 sqmm | BI01010001010000000000000515BI0100001186 | 50 | RM |
76 | 76 | 12P x 1.5 sqmm | BI01010001010000000000000515BI0100001187 | 500 | RM |
77 | 77 | Supply of FS Armoured Copper Power cable as per tender specifications. | BI01010001010000000000000515BI0100001188 | ||
78 | 78 | 3C x 2.5 sqmm | BI01010001010000000000000515BI0100001189 | 500 | RM |
79 | 79 | Supply of FS Armoured Copper Control cable as per tender specifications. | BI01010001010000000000000515BI0100001190 | ||
80 | 80 | 2C x 1.5 sqmm | BI01010001010000000000000515BI0100001191 | 500 | RM |
81 | 81 | 4C x 1.5 sqmm | BI01010001010000000000000515BI0100001192 | 500 | RM |
82 | 82 | 6C x 1.5 sqmm | BI01010001010000000000000515BI0100001193 | 50 | RM |
83 | 83 | 8C x 1.5 sqmm | BI01010001010000000000000515BI0100001194 | 50 | RM |
84 | 84 | 10C x 1.5 sqmm | BI01010001010000000000000515BI0100001195 | 50 | RM |
85 | 85 | 12C x 1.5 sqmm | BI01010001010000000000000515BI0100001196 | 50 | RM |
86 | 86 | Supply of FS Armoured Copper Signal cable as per tender specifications. | BI01010001010000000000000515BI0100001197 | ||
87 | 87 | 1P x 1.5 sqmm | BI01010001010000000000000515BI0100001198 | 500 | RM |
88 | 88 | 2P x 1.5 sqmm | BI01010001010000000000000515BI0100001199 | 500 | RM |
89 | 89 | 3P x 1.5 sqmm | BI01010001010000000000000515BI0100001200 | 50 | RM |
90 | 90 | 4P x 1.5 sqmm | BI01010001010000000000000515BI0100001201 | 50 | RM |
91 | 91 | Supply of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. | BI01010001010000000000000515BI0100001202 | ||
92 | 92 | 50mm | BI01010001010000000000000515BI0100001203 | 500 | RM |
93 | 93 | 100 mm | BI01010001010000000000000515BI0100001204 | 500 | RM |
94 | 94 | 150 mm | BI01010001010000000000000515BI0100001205 | 2000 | RM |
95 | 95 | 300 mm | BI01010001010000000000000515BI0100001206 | 500 | RM |
96 | 96 | 600 mm | BI01010001010000000000000515BI0100001207 | 50 | RM |
97 | 97 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. | BI01010001010000000000000515BI0100001208 | ||
98 | 98 | 24 ways JB | BI01010001010000000000000515BI0100001209 | 4 | EA |
99 | 99 | 18 ways JB | BI01010001010000000000000515BI0100001210 | 4 | EA |
100 | 100 | 12 ways JB | BI01010001010000000000000515BI0100001211 | 4 | EA |
101 | 101 | 8 ways JB | BI01010001010000000000000515BI0100001212 | 4 | EA |
102 | 102 | 6 ways JB | BI01010001010000000000000515BI0100001213 | 4 | EA |
103 | 103 | 4 ways JB | BI01010001010000000000000515BI0100001214 | 4 | EA |
104 | 104 | Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | BI01010001010000000000000515BI0100001215 | 1000 | RM |
105 | 105 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document | BI01010001010000000000000515BI0100001216 | 1000 | RM |
106 | 106 | Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | BI01010001010000000000000515BI0100001217 | 1500 | RM |
107 | 107 | Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | BI01010001010000000000000515BI0100001218 | 1000 | RM |
108 | 108 | Earth Pit | BI01010001010000000000000515BI0100001219 | ||
109 | 109 | Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length T45 model/equivalent safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation \nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) | BI01010001010000000000000515BI0100001220 | ||
110 | 110 | Tank dyke | BI01010001010000000000000515BI0100001221 | 4 | EA |
111 | 111 | Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | BI01010001010000000000000515BI0100001222 | 500 | RM |
112 | 112 | Supply of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc | BI01010001010000000000000515BI0100001223 | 2 | MT |
113 | 113 | Supply of hot dip galvanised Structural steel (MS) including civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc required for complete Terminal Automation System | BI01010001010000000000000515BI0100001224 | 1 | MT |
114 | 114 | Hydrocarbon Detection system | BI01010001010000000000000515BI0100001225 | ||
115 | 115 | Supply of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, canopy/sunshade etc as per specification and tender document. | BI01010001010000000000000515BI0100001226 | ||
116 | 116 | Point type Infrared detector\n(Indicative location: Each tank dyke sump pit inside dyke wall - 4 nos., Near ROSOVs of MS tanks- 2 nos., TLF and TW MS & Ethanol pump seal - 3 nos., Pump house drain pit - 1 no.; | BI01010001010000000000000515BI0100001227 | 10 | EA |
117 | 117 | Open path type Infrared detector (0-40m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks covering ROSOVs -3 nos.; ) | BI01010001010000000000000515BI0100001228 | 3 | EA |
118 | 118 | Supply of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification. ( Tentative location : Each product tank dyke-2 nos., Near Pump House - 1 no..) | BI01010001010000000000000515BI0100001229 | 3 | EA |
119 | 119 | Supply of one no. of Portable Hydrocarbon vapour detector along with accessories complete as per specification and tender document. | BI01010001010000000000000515BI0100001230 | 1 | EA |
120 | 120 | INSTALLATION OF EQUIPMENTS- | BI01010001010000000000000515BI0100001231 | ||
121 | 121 | Installation, Integration, Testing and Commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001232 | ||
122 | 122 | For Cone Roof Vertical tanks (Primary and Secondary Radar Gauges - HSD-3x2) | BI01010001010000000000000515BI0100001233 | 14 | EA |
123 | 123 | For Internal Floating Roof Vertical tanks (Primary and Secondary Radar Gauges - MS-3x2, Ethanol - 2x2) | BI01010001010000000000000515BI0100001234 | 6 | EA |
124 | 124 | For underground horizontal product tanks (Ethanol - 2 nos) | BI01010001010000000000000515BI0100001235 | 2 | EA |
125 | 125 | Installation, Integration, Testing and Commissioning of Non- Contact type Radar level gauges with instrument accuracy of +/-3 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001236 | ||
126 | 126 | For Water Tanks (4 no) | BI01010001010000000000000515BI0100001237 | 4 | EA |
127 | 127 | Installation, Integration, Testing and Commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. | BI01010001010000000000000515BI0100001238 | ||
128 | 128 | With minimum 8 elements temperature sensor (for above ground tanks - MS, HSD, Ethanol) | BI01010001010000000000000515BI0100001239 | 10 | EA |
129 | 129 | With minimum 2 elements temperature sensor (for U/G horizontal tanks - Ethanol -2 nos) | BI01010001010000000000000515BI0100001240 | 2 | EA |
130 | 130 | Installation, Integration, Testing and Commissioning of Density probe along with accessories etc for density measurement of the product complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001241 | ||
131 | 131 | For A/G Tanks with 3 elements | BI01010001010000000000000515BI0100001242 | 10 | EA |
132 | 132 | For U/G Tanks with 1 elements ( Ethanol -2 nos) | BI01010001010000000000000515BI0100001243 | 2 | EA |
133 | 133 | Installation, Integration, Testing and Commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tanks inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | BI01010001010000000000000515BI0100001244 | ||
134 | 134 | For Vertical Product tanks - (Primary & Secondary Radar Gauges) | BI01010001010000000000000515BI0100001245 | 20 | EA |
135 | 135 | For U/G Product tanks | BI01010001010000000000000515BI0100001246 | 2 | EA |
136 | 136 | For Water Tanks (4 no) | BI01010001010000000000000515BI0100001247 | 4 | EA |
137 | 137 | Installation, Integration, Testing and Commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment etc complete as per specification and tender document | BI01010001010000000000000515BI0100001248 | ||
138 | 138 | For Vertical Product tanks | BI01010001010000000000000515BI0100001249 | 10 | EA |
139 | 139 | For U/G Product tanks (Ethanol -2 nos) | BI01010001010000000000000515BI0100001250 | 2 | EA |
140 | 140 | Installation of Paraller Redundant Communiaction Unit(For Primary & Secondary gauge) | BI01010001010000000000000515BI0100001251 | ||
141 | 141 | Primary Gauge | BI01010001010000000000000515BI0100001252 | 1 | EA |
142 | 142 | Secondary Gauge | BI01010001010000000000000515BI0100001253 | 1 | EA |
143 | 143 | Installation, Integration, Testing and Commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, TBs, mounting structure, accessories etc complete as per specifications and tender document. | BI01010001010000000000000515BI0100001254 | ||
144 | 144 | For ROSOVs (A/G product tank's inlet, outlet and recirculation line- 10 nos.) | BI01010001010000000000000515BI0100001255 | 20 | EA |
145 | 145 | Installation, Integration, Configuration, Testing and Commissioning of TFMS Server(Redundant Type) (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 18.5" suitable for 24x7 operation, keyboard drawer, optical mouse, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. | BI01010001010000000000000515BI0100001256 | 2 | SET |
146 | 146 | Installation, Integration, Configuration, Testing and Commissioning of TFMS Workstation with minimum 23" LED colour monitor, standard keyboard, mouse, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. | BI01010001010000000000000515BI0100001257 | ||
147 | 147 | 19" Rack type at Control Room, form factor - Rack, CPU height - 2U | BI01010001010000000000000515BI0100001258 | 1 | EA |
148 | 148 | Tower type at TM's room | BI01010001010000000000000515BI0100001259 | 1 | EA |
149 | 149 | Design, Engineering, Installation, Setup, Configuration, Integration, Testing & Commissioning of Redundant, SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Redundant host communication ports, Serial Interface Modules, any other communication module, HMI, wirings, glands, plugs, other modules/ hardware required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: The offered safety PLC shall be of the same make family of the integrated Distributed Control System. | BI01010001010000000000000515BI0100001260 | 1 | SET |
150 | 150 | Design, Installation, Configuration, Testing & Commissioning of Complete Terminal Automation Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete funtional and technical requirements of the tender document. \nVendor to provide required softwares, licences, dongle/keys, GUI, SCADA etc for TAS Management Server, Distributed Control System, Operator work stations, Fire Fighting OIC, Alarm display and annunciation OIC, Engineering Work Stations(for safety PLC & DCS), Web Server, OPC Server, Historian Server / work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document. \nTAS software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- TAS Management Server\n- TLF Automation System (TT reporting, registration & entry system, TT Queuing, FAN generation, Bay allocation, Additive Dosing system, Ethanol blending System, Interface with TLF equipments like BCU, MFM, Barrier Gates, Bay Queue Display, Bay allocation Display, Invoice generated display, rack monitors, Proximity card readers etc)\n-Tank Wagon loading Automation system\n-Tank Wagon unloading Automation system\n-Tank Lorry Decantation System\n-TT calibration System\n-Bio Diesel Blending system | BI01010001010000000000000515BI0100001261 | 1 | LS |
151 | 151 | Installation of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments | BI01010001010000000000000515BI0100001262 | ||
152 | 152 | For mounting of TFMS Server along with associated rack mounted monitors, rack mounted keyboard, mouse, power adapters, networking & OFC components, CIUs, MCBs etc as per specification and tender document | BI01010001010000000000000515BI0100001263 | 1 | EA |
153 | 153 | For mounting of Rack mounted Master Control Stations for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document | BI01010001010000000000000515BI0100001264 | 1 | EA |
154 | 154 | Installation, Configuration, Integration, Testing and Commissioning of Operator Interface Console Computer (OIC) minimum 23" colour LED monitor, standard keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. | BI01010001010000000000000515BI0100001265 | ||
155 | 155 | 19" Rack type at Control Room, form factor - Rack, CPU height - 2U | BI01010001010000000000000515BI0100001266 | 2 | EA |
156 | 156 | Tower mounted type in TM's Cabin | BI01010001010000000000000515BI0100001267 | 1 | EA |
157 | 157 | Installation, Integration, Testing and Commissioning of Engineering Workstation (EWS) with minimum 23" colour LED monitor, standard keyboard, mouse, PLC & DCS software, HMI software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. (Locations: 1 no. in CR for both DCS and Safety PLC) - 19" Rack type at Control Room, form factor - Rack, CPU height - 2U | BI01010001010000000000000515BI0100001268 | 1 | EA |
158 | 158 | Installation, Integration, Configuration, Testing and Commissioning of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) with SFP, copper, fiber modules/ports along with accessories for connecting Plant management LAN equipments like CCTV System, TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers, Access Control Server, Web Server Access over IOCL Intranet, connecting to OIC/ work stations etc which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices which needs OPC for interfacing with DCS etc. \nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. | BI01010001010000000000000515BI0100001269 | 2 | EA |
159 | 159 | Installation, Integration, Configuration, Testing and Commissioning of 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) along with SFP, copper, fiber modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, TTES, EWS, OPC Servers, Fire fighting OICs, Alarm Display OIC, DCS, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. | BI01010001010000000000000515BI0100001270 | 2 | EA |
160 | 160 | Installation of Wall mounted Network Rack-minimum 15U 19" Rack for mounting of Terminal Server/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room, S&D for TAS equipments. | BI01010001010000000000000515BI0100001271 | 2 | EA |
161 | 161 | Installation, Testing and Commissioning of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader with accessories for powering DCS Panel, Safety PLC Panel, TAS-MS, OIC, EWS, TFMS System, TTES, printers, Bay Instruments other control room equipments, Tank Farm Instruments, CCTV system, Fire Detection System, Access control system, Bay Queue Display boards, other display boards, ROSOV ESD port, header line instruments and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. | BI01010001010000000000000515BI0100001272 | 1 | LS |
162 | 162 | Installation, Integration, Configuration, Testing and Commissioning of IP based Redundant GSM modem suitable for 24x7 operation along with accessories for auto SMS as per specification and tender document. | BI01010001010000000000000515BI0100001273 | 1 | EA |
163 | 163 | Installation, Integration, Configuration, Testing and Commissioning of minimum 42" HD LED monitor along with 1 no. of hooter, ACK push button, mounting accessories, cables etc for critical alarms display and annunciation complete as per specifications and tender document. | BI01010001010000000000000515BI0100001274 | 1 | EA |
164 | 164 | Note: Laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners, OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc | BI01010001010000000000000515BI0100001275 | ||
165 | 165 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. | BI01010001010000000000000515BI0100001276 | ||
166 | 166 | 3C x 2.5 sqmm | BI01010001010000000000000515BI0100001277 | 1500 | RM |
167 | 167 | 12C x 2.5 sqmm | BI01010001010000000000000515BI0100001278 | 200 | RM |
168 | 168 | 24C x 2.5 sqmm | BI01010001010000000000000515BI0100001279 | 800 | RM |
169 | 169 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. | BI01010001010000000000000515BI0100001280 | ||
170 | 170 | 2C x 1.5 sqmm | BI01010001010000000000000515BI0100001281 | 1500 | RM |
171 | 171 | 4C x 1.5 sqmm | BI01010001010000000000000515BI0100001282 | 500 | RM |
172 | 172 | 8C x 1.5 sqmm | BI01010001010000000000000515BI0100001283 | 50 | RM |
173 | 173 | 10C x 1.5 sqmm | BI01010001010000000000000515BI0100001284 | 50 | RM |
174 | 174 | 12C x 1.5 sqmm | BI01010001010000000000000515BI0100001285 | 50 | RM |
175 | 175 | 16C x 1.5 sqmm | BI01010001010000000000000515BI0100001286 | 50 | RM |
176 | 176 | 18C x 1.5 sqmm | BI01010001010000000000000515BI0100001287 | 50 | RM |
177 | 177 | 20C x 1.5 sqmm | BI01010001010000000000000515BI0100001288 | 50 | RM |
178 | 178 | 24C x 1.5 sqmm | BI01010001010000000000000515BI0100001289 | 800 | RM |
179 | 179 | 32C x 1.5 sqmm | BI01010001010000000000000515BI0100001290 | 50 | RM |
180 | 180 | 36C x 1.5 sqmm | BI01010001010000000000000515BI0100001291 | 50 | RM |
181 | 181 | 48C x 1.5 sqmm | BI01010001010000000000000515BI0100001292 | 500 | RM |
182 | 182 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. | BI01010001010000000000000515BI0100001293 | ||
183 | 183 | 1P x 1.5 sqmm | BI01010001010000000000000515BI0100001294 | 1500 | RM |
184 | 184 | 2P x 1.5 sqmm | BI01010001010000000000000515BI0100001295 | 1500 | RM |
185 | 185 | 3P x 1.5 sqmm | BI01010001010000000000000515BI0100001296 | 50 | RM |
186 | 186 | 4P x 1.5 sqmm | BI01010001010000000000000515BI0100001297 | 500 | RM |
187 | 187 | 6P x 1.5 sqmm | BI01010001010000000000000515BI0100001298 | 50 | RM |
188 | 188 | 12P x 1.5 sqmm | BI01010001010000000000000515BI0100001299 | 500 | RM |
189 | 189 | Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. | BI01010001010000000000000515BI0100001300 | ||
190 | 190 | 3C x 2.5 sqmm | BI01010001010000000000000515BI0100001301 | 500 | RM |
191 | 191 | Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. | BI01010001010000000000000515BI0100001302 | ||
192 | 192 | 2C x 1.5 sqmm | BI01010001010000000000000515BI0100001303 | 500 | RM |
193 | 193 | 4C x 1.5 sqmm | BI01010001010000000000000515BI0100001304 | 500 | RM |
194 | 194 | 6C x 1.5 sqmm | BI01010001010000000000000515BI0100001305 | 50 | RM |
195 | 195 | 8C x 1.5 sqmm | BI01010001010000000000000515BI0100001306 | 50 | RM |
196 | 196 | 10C x 1.5 sqmm | BI01010001010000000000000515BI0100001307 | 50 | RM |
197 | 197 | 12C x 1.5 sqmm | BI01010001010000000000000515BI0100001308 | 50 | RM |
198 | 198 | Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. | BI01010001010000000000000515BI0100001309 | ||
199 | 199 | 1P x 1.5 sqmm | BI01010001010000000000000515BI0100001310 | 500 | RM |
200 | 200 | 2P x 1.5 sqmm | BI01010001010000000000000515BI0100001311 | 500 | RM |
201 | 201 | 3P x 1.5 sqmm | BI01010001010000000000000515BI0100001312 | 50 | RM |
202 | 202 | 4P x 1.5 sqmm | BI01010001010000000000000515BI0100001313 | 50 | RM |
203 | 203 | Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. | BI01010001010000000000000515BI0100001314 | ||
204 | 204 | 50mm | BI01010001010000000000000515BI0100001315 | 500 | RM |
205 | 205 | 100 mm | BI01010001010000000000000515BI0100001316 | 500 | RM |
206 | 206 | 150 mm | BI01010001010000000000000515BI0100001317 | 2000 | RM |
207 | 207 | 300 mm | BI01010001010000000000000515BI0100001318 | 500 | RM |
208 | 208 | 600 mm | BI01010001010000000000000515BI0100001319 | 50 | RM |
209 | 209 | Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. | BI01010001010000000000000515BI0100001320 | ||
210 | 210 | 24 ways JB | BI01010001010000000000000515BI0100001321 | 4 | EA |
211 | 211 | 18 ways JB | BI01010001010000000000000515BI0100001322 | 4 | EA |
212 | 212 | 12 ways JB | BI01010001010000000000000515BI0100001323 | 4 | EA |
213 | 213 | 8 ways JB | BI01010001010000000000000515BI0100001324 | 4 | EA |
214 | 214 | 6 ways JB | BI01010001010000000000000515BI0100001325 | 4 | EA |
215 | 215 | 4 ways JB | BI01010001010000000000000515BI0100001326 | 4 | EA |
216 | 216 | Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | BI01010001010000000000000515BI0100001327 | 1000 | RM |
217 | 217 | Laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document | BI01010001010000000000000515BI0100001328 | 1000 | RM |
218 | 218 | Fabrication, cutting, laying and connecting of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | BI01010001010000000000000515BI0100001329 | 1500 | RM |
219 | 219 | Fabrication, cutting, laying and connecting of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | BI01010001010000000000000515BI0100001330 | 1000 | RM |
220 | 220 | Installation, Testing and Commissioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length T45 model/equivalent safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos. and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) | BI01010001010000000000000515BI0100001331 | ||
221 | 221 | Tank Dyke | BI01010001010000000000000515BI0100001332 | 4 | EA |
222 | 222 | Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | BI01010001010000000000000515BI0100001333 | 500 | RM |
223 | 223 | Design, Fabrication, erection, weld, painting, cutting, drilling, grinding etc of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc | BI01010001010000000000000515BI0100001334 | 5 | MT |
224 | 224 | Design, Fabrication, erection, weld, cutting, drilling, grinding etc of hot dip galvanised Structural steel (MS) including civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc required for complete Terminal Automation System | BI01010001010000000000000515BI0100001335 | 1 | MT |
225 | 225 | Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc including any hardware modification as addition of modules, ports etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per direction of EIC. | BI01010001010000000000000515BI0100001336 | ||
226 | 226 | Product tank addition | BI01010001010000000000000515BI0100001337 | 10 | per tank |
227 | 227 | Hydrocarbon Detection system | BI01010001010000000000000515BI0100001338 | ||
228 | 228 | Installation, integration, Calibration, Testing, and Commissioning Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon gas detectors along with calibration kit, accessories and structural supports etc as per specification and tender document. | BI01010001010000000000000515BI0100001339 | ||
229 | 229 | Point type Infrared detector\n(Indicative location: Each tank dyke sump pit inside dyke wall - 4 nos., Near ROSOVs of MS tanks- 2 nos., TLF and TW MS & Ethanol pump seal - 3 nos., Pump house drain pit - 1 no.; | BI01010001010000000000000515BI0100001340 | 10 | EA |
230 | 230 | Open path type Infrared detector (0-40m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks covering ROSOVs -3 nos.; ) | BI01010001010000000000000515BI0100001341 | 3 | EA |
231 | 231 | Supply of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification. ( Tentative location : Each product tank dyke-2 nos., Near Pump House - 1 no..) | BI01010001010000000000000515BI0100001342 | 3 | EA |
232 | 232 | Other Miscellaneous Items | BI01010001010000000000000515BI0100001343 | ||
233 | 233 | Providing training to IOCL employee as per schedule/Module for 2 days as per tender document | BI01010001010000000000000515BI0100001344 | 1 | EA |
234 | 234 | Submission of Final Detailed system design, Engineering, Documentations, as built drawings etc complete as per tender | BI01010001010000000000000515BI0100001345 | 1 | EA |
235 | 235 | SIL verification / Validation | BI01010001010000000000000515BI0100001346 | ||
236 | 236 | SIL verification from approved third party agencies. (For SIFs as per SIL Assessment study report/detail engg). All required documentation as per specs and other documentation mentioned elsewhere in tender scope has to be submitted. Complete as per specification / tender documents. | BI01010001010000000000000515BI0100001347 | 1 | LS |
237 | 237 | Validation of entire Safety System (SIS) for SIFs (for e.g. AOPS -SIF) shall be carried out from approved third party agency prior to trial period. Automation contractor shall bear the responsibility of its co-ordination and logistics. The third party has to submit a detailed report along with certification for SIS which is to be approved by IOCL along with all other required documentation as per specification and tender documents. | BI01010001010000000000000515BI0100001348 | 1 | LS |
238 | 238 | Supply of Master Control Station | BI01010001010000000000000515BI0100001349 | 1 | EA |
239 | 239 | WBM Road, Dyke cutting, concrete breaking for cable trenches including shoring, strutting etc, if required and repairing of the road and restoration of same using PCC 1:2:4 with 20mm down stone chip, dyke to original condition and disposing off excess materials within the work site as per direction of site engineer. Breaking the existing RCC work and disposing off the malba to an unobjectionable place as per the instruction of the site engineer. Job shall be complete in all respect including the cost of all labour, tools, materials, load lift hire charges of equipments if any. | BI01010001010000000000000515BI0100001350 | 300 | M2 |
240 | 240 | Sand FILLING | BI01010001010000000000000515BI0100001351 | 100 | M3 |
241 | 241 | Supply, installation, testing and commissioning of cubicle type power and motor control centre with 6nos of LED type (RYB) indicating lamps, 3 Nos. of ammeters,1No.of voltmeter with selector switch, 3nos. of 100/5A CTs, control fuses, control wiring etc., and to be fabricated out of 16 SWG MS sheet undergone 7 tank process and painted with anticorrosive primer and two coats of grey enamel paint and having following specific components complete as per enclosed standard drawings: 125A FP SFCOS with 125A HRC fuse as incomer-1 No 125A TPN busbar chamber with Aluminium bus 63A TPN SDFU with 50A HRC fuse as outgoings - 4 Nos 63A 100mA RCBO (MCB+ELCB) - 3 Nos. 63A 300mA RCBO (MCB+ELCB) - 1 No. 6-32A SP MCB - 40 Nos. 10A DP MCB - 12 Nos. 25A TP MCB - 3 Nos. Dummy plates - 23 Nos. | BI01010001010000000000000515BI0100001352 | 1 | EA |
242 | 242 | Providing & laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments,pillars,posts,struts, buttresses,string or lacing courses, parapets,coping, bed blocks, anchor blocks, plain window sills, fillets etc. UP TO FLOOR V LEVEL excluding the cost of centering, shuttering and finishing : | BI01010001010000000000000515BI0100001353 | ||
243 | 243 | iii) PCC 1 Cement:2 Coarse Sand:4 Graded Stone Aggregate 20mm | BI01010001010000000000000515BI0100001354 | 25 | M3 |
244 | 244 | Comprehensive Annual Maintenance Contract for a period of Seven years for entire Terminal Automation System after successful completion of SAT as described in Technical Bid. \nCost of all the required spares, hardwares, software modification, tools and tackles, ladders, labours, Preventive & Breakdown maintenance Service, calibration of instruments, proving & stampings of metering equipments, rectification/ replacement of faulty TAS equipment etc required for running and maintenance of the entire Terminal Automation System to the desired performance level throughout the contract period of CAMC is included in the item rates and the same has to be borne by the Vendor. \nThe scope also includes posting of Resident Engineer (s) to take care of running and maintenance of the entire Automation System complete as per the tender document. | BI01010001010000000000000515BI0100001355 | ||
245 | 245 | First Year @4% of the basic CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001356 | 1 | EA |
246 | 246 | Second Year @4% of the CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001357 | 1 | EA |
247 | 247 | Third Year @7% of the CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001358 | 1 | EA |
248 | 248 | Fourth Year @7% of the CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001359 | 1 | EA |
249 | 249 | Fifth Year @10% of the CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001360 | 1 | EA |
250 | 250 | Sixth Year @6% of the CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001361 | 1 | EA |
251 | 251 | Seventh Year @12% of the CAPEX cost excluding GST @ 18% | BI01010001010000000000000515BI0100001362 | 1 | EA |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail