| 1 | 1 | Attending complaints of no supply in light or power circuit due to burning/ disconnecting of any wire i.e. neutral phase or tripping of MCB or un-serviceability of any item such as switch socket MCB etc, rectification of fault including any petty repair required to restore the electric supply for checking of existing electrical items for continuous electric supply including carrying out minor repairs such as changing of fuse, small pieces of wires etc, carrying out repairs such as tightening of loosen electric connections, nuts, bolts screws or switches, sockets, switch board, ceiling fans/ exhaust fans etc., required to make the item functional during 0900 Hrs to 1800 Hrs by deploying electrician alongwith helper including necessary tools complete all as specified and directed.\nNotes:-\n(a) Replacement of electrical fittings/ fixtures shall be measured and paid for separately under respective item of BOQ.\n(b) Repairs/ faults in any one quarter/ one occupancy shall be considered as one complaint (one measuring unit) even if repair is involved in more than one light point or fitting. However, all fitting/ fixtures replaced shall be measured & paid. | | 1600 | Each |
|---|
| 2 | 1.01 | (c) Number of complaints may vary day to day. Contractor shall quote his rates accordingly. \n(d) In case of failure on the part of contractor for attending complaints a penalty shall be imposed and recovered as specified in Particular Specifications. \n(e) Contractor shall ensure that the deployed electrician & helper will carry functional and live mobile phone while on duty and will be on contact with JE/ Engineer-in-Charge. \n(f) Contractor shall be responsible for collection of all ON LINE complaints and handing over the same to JE E/M after rectification duly signed by user with details of stores fixed and to put the status ON LINE after attending/ complete of the job.\n | | | |
|---|
| 3 | 2 | Supply & Fixing in repairs switch piano flush type, 5 Amps, 240 Volt AC single pole, one way including taking down existing switch complete all as specified. | | 850 | Each |
|---|
| 4 | 3 | Supply & Fixing in repairs switch piano flush type, 5 Amps, 240 Volt AC single pole, two way including taking down existing switch complete all as specified. | | 25 | Each |
|---|
| 5 | 4 | Supply & Fixing in repairs switch piano flush type, 15 Amps, 240 Volt AC single pole, one way including taking down existing switch complete all as specified. | | 550 | Each |
|---|
| 6 | 5 | Supply & Fixing in repairs socket out let 5 Amp, 5 pin flush type including taking down existing socket complete all as specified. | | 700 | Each |
|---|
| 7 | 6 | Supply & Fixing in repairs socket outlet multipurpose 3 in 1, 6 pin, 5 & 15 Amps, flush type including taking down existing socket complete all as specified | | 450 | Each |
|---|
| 8 | 7 | Supply & Fixing in repairs bell push switch flush type 5 Amps, SP, 240 volts including taking down existing bell complete all as specified | | 150 | Each |
|---|
| 9 | 8 | Supply & Fixing in repairs bell electric AC (Ding Dong) 240 volt SP including taking down existing bell complete all as specified | | 100 | Each |
|---|
| 10 | 9 | Supply & Fixing in repairs lamp holder insulated body with back plate suitable for batten fittings including taking down existing lamp holder complete all as specified. | | 200 | Each |
|---|
| 11 | 10 | Supply & Fixing in repairs fan step regulator, electronic type, single phase, 300 watt including connection complete after dismantling/ removing unserviceable regulator all as specified. | | 150 | Each |
|---|
| 12 | 11 | Supply & Fixing in replacement copper wire PVC insulated 1.5 Sqmm single core stranded complete including taking down existing wire all as specified. | | 250 | RM |
|---|
| 13 | 12 | Supply & Fixing in replacement copper wire PVC insulated 2.5 Sqmm single core stranded complete including taking down existing wire all as specified. | | 250 | RM |
|---|
| 14 | 13 | Supply & Fixing in replacement copper wire PVC insulated 4 Sqmm single core stranded complete including taking down existing wire all as specified. | | 150 | RM |
|---|
| 15 | 14 | S&F in repair energy saving bulk head light luminaire with opal diffuser LED 10 watt 6000 K, power factor more than 0.90, IP-65 class-I protection with high efficiency BIS marked LED electronic driver, surge protection 2 KV, operative on 140 volts to 270 volts AC supply complete prewired, connecting and testing complete all as specified and directed.\nNotes:-\n(i) Contractor shall provide 2 years written warranty for the LED fixture complete including driver from the certified date of completion from the local office bearer of manufacturers. \n(ii) Contractor shall produce LM-79 and LM-80 Report of NABL accredited Laboratory from manufacturer. \n(iii) Products must be made in India only.\n | | 25 | Each |
|---|
| 16 | 15 | M&L for sub main wiring with PVC insulated cable copper conductor FRLS two single core 6 Sqmm drawn through PVC rigid non metallic conduit including earth continuity FRLS copper conductor 64 Sqmm PVC insulated with green insulation complete all as specified. (PVC conduit shall be measured and paid separately). | | 250 | RM |
|---|
| 17 | 16 | M&L for sub main wiring with PVC insulated cable copper conductor FRLS two single core 4 Sqmm drawn through PVC rigid non metallic conduit including earth continuity FRLS copper conductor 4 Sqmm PVC insulated with green insulation complete all as specified. (PVC conduit shall be measured and paid separately). | | 200 | RM |
|---|
| 18 | 17 | M&L for PVC rigid non metallic conduit medium grade ISI mark 25mm dia surface or concealed including conduit accessories such as tee, elbow, bend, junction box complete all as specified. | | 70 | RM |
|---|
| 19 | 18 | S&F sheet metal enclosure for DBs when MCBs to be used, SPN 8 ways 240 V, with 200 Amps rated bus bar, double door, epoxy coated inside and outside complete all as specified | | 20 | Each |
|---|
| 20 | 19 | S&F DB's 4 way TPN double door suitable for MCCB FP 'A' frame of rating 100 Amps and having breaking capacity 16 KA complete all as specified.\nNote: MCCB shall be measured and paid for separately.\n | | 5 | Each |
|---|
| 21 | 20 | S&F MCB four pole, 415 volts of rating 63/100 Amps having breaking capacity 10 KA complete suitable for DB vertical TP&N 4 way complete all as specified. | | 4 | Each |
|---|
| 22 | 21 | Supply, fixing and connecting MCB SP 6 to 32 Amps, 240V, 10 KA including taking down existing MCB complete all as specified. | | 120 | Each |
|---|
| 23 | 22 | Supply, fixing and connecting MCB SPN 6 to 32 Amps, 240V, 10 KA including taking down existing MCB complete all as specified. | | 150 | Each |
|---|
| 24 | 23 | Attending complaints for non functional tube light/ wall security light 4 x 24 W/ 28 W/ 36 W/ 40 W fitting due to any reason such as loose connection or un-serviceability of any part such as ballast, side holders complete all as specified and directed.\nNote: Supply only of items such as ballast, side holders; if replaced shall be measured and paid under respective items. | | 1300 | Each |
|---|
| 25 | 24 | S&F in repair energy saving tube light LED luminaire with diffuser LED with & including CRCA MS box batten and 4 feet 18 to 20 watt (max) retro fit tube rod having terminally conductive material Lumen output 2100 lumens (min) 6200 K, power factor more than 0.90, IP-20 class-I protection, with built LED driver, surge protection upto 2 KV, operative on 140 volts to 270 volts AC supply, products must be made in India only, complete prewired, connecting and testing complete all as specified and directed. | | 900 | Each |
|---|
| 26 | 25 | Supply, fixing and connecting LED tube 4 feet 20 watt retro fit type wide distribution angle, self ballasted with built in driver including making connection of existing fluorescent fixture as suitable for LED tube, 2100 lumens 6000 K, power factor more than 0.90, IP-20 class-I protection, surge protection 2 KV, operative on 140 volts to 270 volts AC supply, having terminally conductive material for heat dissipation, products must be made in India only, complete all as specified and directed. | | 650 | Each |
|---|
| 27 | 26 | S&F in repair energy saving tube light LED luminaire with diffuser LED with & including CRCA MS box batten and 2 feet 9 to 12 watt (max) retro fit tube rod having terminally conductive material Lumen output 1000 lumens (min) 6200 K, power factor more than 0.90, IP-20 class-I protection, with built LED driver, surge protection upto 2 KV, operative on 140 volts to 270 volts AC supply, products must be made in India only, Complete prewired, connecting and testing complete all as specified and directed. | | 210 | Each |
|---|
| 28 | 27 | S&F energy saving & environmental friendly long life versatile pressure die-cast aluminium housing luminaire with heat resistant glass and suitable optics for uniform distribution of light 15 watt LED for bldg security lights with high efficiency electronic driver, having IP-65 protection, surge protection min 2 KV power factor more than 0.95 complete operative on AC supply 140 volts to 270 volts pre-wired and product should be made in India only complete all as specified.\nNotes for Srl item No. 24 to 27: \n(i) Contractor shall provide 2 years written warranty for the LED fixture complete including driver from the certified date of completion from the local office bearer of manufacturers. \n(ii) Contractor shall produce LM-79 & LM-80 Report of NABL accredited Laboratory duly signed by the office bearer of manufacturer. | | 50 | Each |
|---|
| 29 | 28 | S&F city 1 new decorative wall light fixture made up of polycarbonate, suitable for lamp type 1 x 9 watt retrofit LED lamp including 9 watt LED lamp of same make as fitting complete all as specified. | | 50 | Each |
|---|
| 30 | 29 | S&F integral post top LED light fitting with 25 W LED IP65 protection complete all as specified and directed. | | 24 | Each |
|---|
| 31 | 30 | Supply & fixing in repairs electronic ballast 36/ 40 watt including taking down existing ballast complete all as specified. | | 700 | Each |
|---|
| 32 | 31 | Supply & fixing in repairs electronic ballast 28 watt including taking down existing ballast complete all as specified. | | 400 | Each |
|---|
| 33 | 32 | Supply & fixing in repairs 24 watt pin type CFL suitable for 4 x 24 watt T5 security light including taking down existing lamp all as specified and directed. | | 150 | Each |
|---|
| 34 | 33 | Supply & fixing in repairs electronic ballast 2 x 24 watt suitable for 4 x 24 watt T5 security light including taking down existing ballast all as specified and directed. | | 120 | Each |
|---|
| 35 | 34 | Supply & fixing in repairs bipin holder suitable for 28/36 w tube light fitting including taking down existing holder complete all as specified. | | 200 | Each |
|---|
| 36 | 35 | Attending complaints of not working/ abnormal noise of fans/ exhaust fan due to loose connection of any wire i.e. neutral/ phase not working of circuits or un-serviceability of any item such as capacitor, rubber real, wire etc rectification of fault including any sort of petty repair required to make the fans functional during 0900 Hrs to 1800 Hrs by deploying electrician with helpers including necessary tools complete all as specified. | | 800 | Each |
|---|
| 37 | 36 | Supply & fixing in repairs condenser 2.50 MFD including taking down existing complete all as specified. | | 275 | Each |
|---|
| 38 | 37 | Supply & fixing in repairs condenser 3.15 MFD including taking down existing complete all as specified. | | 200 | Each |
|---|
| 39 | 38 | Supply & fixing in repairs condenser 4.0 MFD including taking down existing complete all as specified and directed. | | 70 | Each |
|---|
| 40 | 39 | Supply & fixing in repairs rubber real for ceiling fan including nut & bolt including taking down existing rubber real complete all as specified. | | 80 | Each |
|---|
| 41 | 40 | Supply & fixing in repairs flexible cord of size 23/ 0.0076 sqmm including taking down existing cable complete all as specified. | | 200 | RM |
|---|
| 42 | 41 | S&F metal clad industrial socket 20 Amps, 250 V, 2 pole with earth suitable for Geyser/ AC complete all as specified. | | 15 | Each |
|---|
| 43 | 42 | S&F metal clad industrial plug 20 Amps, 250 V, 2 pole with earth suitable for Geyser/ AC complete all as specified. | | 20 | Each |
|---|
| 44 | 43 | Supply & fixing in repairs tube rod 36 watt T-8 (Super bright), cool day light high output FTL, 6500K, operative on 140 volts to 270 AC complete all as specified. | | 850 | Each |
|---|
| 45 | 44 | Supply & fixing in repairs tube rod 28 watt T-5, HE, high output FTL, 6500K, operative on 140 volts to 270 AC complete all as specified. | | 500 | Each |
|---|