| 1 | 1 | Dismantling of burner assembly of CHS and removing of side cover and repairing the same by removing the old burnt fire refractory cement plastering, replastering the same as per existing with fire refractory cement for boiler capacity 4 lakh kilo/cal/hr and complete servicing the boiler by removing the complete carbon/oil deposits with suitable coil shine chemical including repair to coil assembly by welding if there is any leakage found or any other repair required at site and reassembling/ testing the same, complete all as specified and as directed. | | 3 | Each |
|---|
| 2 | 2 | Supply and fixing sequence controller suitable for 4 lakh kilo/hr with burner rod assembly, complete all as specified and as directed. Make- Seimens or equivalent. | | 2 | Each |
|---|
| 3 | 3 | Supply and fixing in replacement ignition rod suitable for 4 lakh kilo/Cal/hr burner rod assembly, complete all as specified and as directed. | | 1 | Pair |
|---|
| 4 | 4 | Supply and fixing in replacement of ignition Transformer electronic type suitable for 4 lakh kilo/Cal/hr burner rod assembly, complete all as specified and as directed.Make: Siemens or equivalent. | | 2 | Each |
|---|
| 5 | 5 | Supply and fixing temp controller digital type DTC 503 with sensor suitable for 4 lakh kilo/Cal/hr LAL 2.25 burner rod assembly, complete all as specified and as directed.Make: Siemens or equivalent. | | 2 | Each |
|---|
| 6 | 6 | Supply and fixing in replacement photo cell as per existing suitable for 4 lakh kilo/Cal/hr burner rod assembly, complete all as specified and as directed. Make- DANFOSS or equivalent. | | 1 | Each |
|---|
| 7 | 7 | Supply and fixing in replacement burner nozzle suitable for 4 lakh K/Cal/Hr, complete all as specified and as directed. | | 2 | Each |
|---|
| 8 | 8 | Supply and fixing in replacement of Electrode suitable for burner of capacity 4 lakh K/Cal/Hr , complete all as specified and as directed. | | 2 | Each |
|---|
| 9 | 9 | Dismantling of burner assembly of CHS and removing of side cover and repairing the same by removing the old burnt fire refractory cement plastering, replastering the same as per existing with fire refractory cement for boiler capacity 1-2 lakh kilo/cal/hr and complete servicing the boiler by removing the complete carbon/oil deposits with suitable coil shine chemical including repair to coil assembly by welding if there is any leakage found or any other repair required at site and reassembling/ testing the same, complete all as specified and as directed by Engr-in Charge. | | 3 | Each |
|---|
| 10 | 10 | Supply and fixing sequence controller suitable for 1 to 2 lakh kilo/hr with burner rod assembly, complete all as specified and as directed. Make- SeImens or equivalent. | | 2 | Each |
|---|
| 11 | 11 | Supply and fixing in replacement ignition rod suitable for 1 to 2 lakh kilo/Cal/hr burner rod assembly, complete all as specified and as directed. | | 1 | Pair |
|---|
| 12 | 12 | Supply and fixing in replacement ignition Transformer electronic type suitable for 1 to 2 Lakhkilo/Cal/hr burner rod assembly, complete all as specified and as directed.Make: Siemens or equivalent. | | 2 | Each |
|---|
| 13 | 13 | Supply and fixing temp controller digital type DTC 503 with sensor suitable for 1 to 2 lakh kilo/Cal/hr LAL 2.25 burner rod assembly, complete all as specified and as directed.Make: Siemens or equivalent. | | 2 | Each |
|---|
| 14 | 14 | Supply and fixing in replacement photo cell as per existing suitable for 1 to 2 lakh kilo/Cal/hr burner rod assembly, complete all as specified and as directed. Make- DANFOSS or equivalent. | | 2 | Each |
|---|
| 15 | 15 | Supply and fixing in replacement burner nozzle suitable for1 to 2 lakh K/Cal/Hr , complete all as specified and as directed. | | 1 | Each |
|---|
| 16 | 16 | Supply and fixing in replacement Electrode suitable for burner of capacity 1 to 2 lakh K/Cal/Hr , complete all as specified and as directed. | | 2 | Each |
|---|
| 17 | 17 | Supply and fixing in replacement pressure gauage 0 to 20 Kg/cm sq as per existing, complete all as specified and as directed. | | 2 | Each |
|---|
| 18 | 18 | Supply and fixing in replacement of Bridge rectifire , complete all as specified and as directed. | | 3 | Each Job |
|---|
| 19 | 19 | Supply and fixing in replacement of hooter round type , complete all as specified and as directed. | | 3 | Each |
|---|
| 20 | 20 | Supply and fixing in replacement of thermostate assembly tail type as per existing suitable for 0 TO 30 degree centrigrade temprature, complete all as specified and as directed. Make- Honeywell or equivalent. | | 3 | Each |
|---|
| 21 | 21 | Supply and fixing in replacement of Fuel filter 1/2 ltr, complete as specified and as directed. Make- Kirloskar, micro | | 6 | Each |
|---|
| 22 | 22 | Material & Labour for repair of exaust pipe by welding, complete all as specified and as directed. | | 4 | Job |
|---|
| 23 | 23 | Supply and fixing in replacement auto air pressure valve 3/8\" as per existing, complete all as specified and as directed. | | 6 | Each |
|---|
| 24 | 24 | Supply and fixing in replacement of High pressure fuel pipe 1.5 mtr as per existing, complete all as specified and as directed. | | 6 | Each |
|---|
| 25 | 25 | Material and labour for rewinding of electric motor 3 phase 415 volts of capacity 7.5HP with superior quality super enameled copper winding wire of appropriate size and gauge as existing including varnishing , cotton tape, PVC sleeves etc, complete all as specified and directed. | | 2 | Each |
|---|
| 26 | 26 | Material and labour for rewinding of electric motor 3 phase 415 volts of capacity 3 HP with superior quality super enameled copper winding wire of appropriate size and gauge as existing including varnishing , cotton tape, PVC sleeves etc, complete all as specified and directed. | | 4 | Each |
|---|
| 27 | 27 | Material and labour for servicing to the glycol pump and motor of capacity 7.5HP, 2870 RPM including replacement of bearings, oil seals or any other spares / work required for smooth functioining of pump, complete all as specified and as directed. | | 3 | Each |
|---|
| 28 | 28 | S & F 1 HP motor electric driven, single phase 230Volt 50 Hz, complete all as specified and as directed. Make L & T, Havells,Crompton Greaves | | 1 | Each |
|---|
| 29 | 29 | Material and labour for disconnecting the all connection in existing panel board complete and re-fixing the same after removing the burnt lugs/thimbles complete including replacing the U/S MCCBS, Contactors, relay, bus bar indicator lamps etc., all as specified and as directed. Note: MCCBS, Contactors, relay, indicator lamps, S/Switches, voltmeter, Ammeter are to be measured and paid separately. | | 8 | Each Job |
|---|
| 30 | 30 | Supply only dol starter MK-1, 1 to 3 HP as per existing, complete all as\nspecified and as directed. Make: Siemens, L & T , Havells. | | 3 | Each |
|---|
| 31 | 31 | Supply only contactor type 3 TF 33, 415 volts complete all as specified\nand as directed. Make: Siemens, L & T , Havells. | | 4 | Each |
|---|
| 32 | 32 | Supply only contactor type ML 1.5, 220 volts, complete all as speified and as directed.Make:Siemens, L & T , Havells. | | 4 | Each |
|---|
| 33 | 33 | Supply only over load relay 8 to 12.5 Amps for contactor matching ser No 48 series 3 TF 33 complete all as specified and as directed.Make: Siemens, L& T, Havells. | | 6 | Each |
|---|
| 34 | 34 | Supply only over load relay 1.25 to 2 Amps for contactor matching ser no 49 series 3 TF 33 , complete all as specified and as directed.Make: Siemens. | | 6 | Each |
|---|
| 35 | 35 | Supply only MCCB with current rating 160 Amps 415 V 4 Pole 36 KA with thermally adjustable, complete all as specified and as directed. Make: L&T/Havells /Standard. | | 4 | Each |
|---|
| 36 | 36 | Supply only MCCB with current rating 200 Amps 415 V 4 Pole 36 KA with thermally adjustable, complete all as specified and as directed. Make: L&T/Havells /Standard. | | 3 | Each |
|---|
| 37 | 37 | Supply only MCCB with current rating 100 Amps fixed type 415 V 4 Pole 16 KA complete all as specified and as directed. Make: L&T/Havells /Standard. | | 6 | Each |
|---|
| 38 | 38 | Supply only digital type volt meter 0-500 volts, complete all as specified and as directed. | | 8 | Each |
|---|
| 39 | 39 | Supply only digital type Amp meter complete with suitable CTs 0-300 Amps, complete all as specified and as directed. | | 9 | Each |
|---|
| 40 | 40 | Supply only indicating lamps RYB , complete all as specified and as directed. | | 14 | Each |
|---|
| 41 | 41 | Supply only rotary type ON/OFF switches, 22mm dia, complete all as specified and as directed. | | 11 | Each |
|---|
| 42 | 42 | Supply only push button switch in RED or GREEN colours, 22mm dia, complete all as specified and as directed. | | 14 | Each |
|---|
| 43 | 43 | Supply only Rotery type switch, complete all as specified and as directed. | | 12 | Each |
|---|
| 44 | 44 | Supply and fixing in replacement PVC flexible copper multistrand wire 3 core of 6 sqmm, complete all as specified and as directed. | | 260 | RM |
|---|
| 45 | 45 | Servicing & maint of AHU unit cap 26000 CFM including rectifiction of leakage if any found welding/bracing/ Greasing & oiling bearings, servicing of electric motors, removing of all Air filters & cleaning the same with air compresser and refixing in the same loction for smooth functioning & testing, complete all as specified and as directed. | | 4 | Each Job |
|---|
| 46 | 46 | Supply and fixing in replacement Lagging all around with 80 mm thick sections bonded mineral wool of density 144 kg /cum conforming to IS 9842 for heating circulation pipe lines of 80mm over chicken wiremesh complete and as directed. Note : Retrieved glass wool to be disposed off by the contractor, complete all as specified and as directed.\nNote : Retrieved glass wool to be disposed off by the contractor. | | 175 | RM |
|---|
| 47 | 47 | Supply and fixing in replacement Lagging all around with 80 mm thick sections bonded mineral wool of density 144 kg /cum conforming to IS 9842 for heating circulation pipe lines of 50mm over chicken wire mesh complete and as directed. Note : Retrieved glass wool to be disposed off by the contractor, complete all as specified and as directed.\nNote : Retrieved glass wool to be disposed off by the contractor. | | 170 | RM |
|---|
| 48 | 48 | Welding the leakage portion of MS pipe line including earthwork complete and materials as required for welding the pipe line of size 25 mm to 200 mm including testing on full pressure complete all as specified and directed. | | 8 | Each Job |
|---|
| 49 | 49 | Cast iron gun metal butterfly valve of size 100 mm dia with CI drilled flanged ends (integrally cast) class PN-I.6, conforming to IS : 13095 / BS: 5155 with stainless steel spindle and iron wheel non rising type including jointing material complete such as rubber or fibre board insertion packing rings with requisite numbers of nuts, bolts & washers etc including taking out existing unserviceable valve complete all as specified and directed.\nMake : KIRLOSKAR/BIR/LEADER | | 3 | Each |
|---|
| 50 | 50 | Cast iron gun metal butterfly valve of size 80 mm dia with CI drilled flanged ends (integrally cast) class PN-I.6, conforming to IS : 13095 / BS: 5155 with stainless steel spindle and iron wheel non rising type including jointing material complete such as rubber or fibre board insertion packing rings with requisite numbers of nuts, bolts & washers etc including taking out existing unserviceable valve complete all as specified and directed.\nMake : KIRLOSKAR/BIR/LEADER | | 6 | Each |
|---|
| 51 | 51 | Cast iron gun metal butterfly valve of size 50 mm dia with CI drilled flanged ends (integrally cast) class PN-I.6, conforming to IS : 13095 / BS: 5155 with stainless steel spindle and iron wheel non rising type including jointing material complete such as rubber or fibre board insertion packing rings with requisite numbers of nuts, bolts & washers etc including taking out existing unserviceable valve complete all as specified and directed.\nMake : KIRLOSKAR/BIR/LEADER | | 4 | Each |
|---|
| 52 | 52 | Cast iron gun metal butterfly valve of size 40 mm dia with CI drilled flanged ends (integrally cast) class PN-I.6, conforming to IS : 13095 / BS: 5155 with stainless steel spindle and iron wheel non rising type including jointing material complete such as rubber or fibre board insertion packing rings with requisite numbers of nuts, bolts & washers etc including taking out existing unserviceable valve complete all as specified and directed.\nMake : KIRLOSKAR/BIR/LEADER | | 4 | Each |
|---|
| 53 | 53 | Cleaning of MS diesel storage tanks of capacity 1000 ltrs by removing of sludge from tanks and scrapping the side walls by means of wire brush or emery paper and wash the same with castic soda and clear water and painting the internal wall with two coats of black rubber emulsion paint and painting the complete tank from out side with two coats of synthetic enamel paint, complete all as specified and as directed. | | 4 | Each Job |
|---|
| 54 | 54 | Supply and filling of Methy/Ethylene Glycol (MEG) of 99% purity and minus forty degree centigrade freezing temperature in Central heating plant complete all as specified and as direced. Make: India Glycol Ltd,BPL,Hindustan or Equivalent. | | 1800 | Litre |
|---|
| 55 | 55 | Supply, fixing and testing in replacement of MS ERW tubing 50 mm bore heavy grade class, 'C' with welded ends laid in ducts over the angle iron supports/ fixed on the walls including fittings complete all as specified and directed. (Note :The rate include cutting to any levels/shapes like elbows, tees, bends etc, welding joints wherever necessary as per the site requirement) | | 110 | RM |
|---|
| 56 | 56 | Supply, fixing and testing in replacement of MS ERW tubing 100mm bore heavy grade class, 'C' with welded ends laid in ducts over the angle iron supports/ fixed on the walls including fittings complete all as specified and directed. (Note :The rate include cutting to any levels/shapes like elbows, tees, bends etc, welding joints wherever necessary as per the site requirement) | | 130 | RM |
|---|
| 57 | 57 | Servicing & maint of AHU unit cap 15000 CFM including rectifiction of leakage if any found welding/bracing/ Greasing & oiling bearings, servicing of electric motors, removing of all Air filters & cleaning the same with air compresser and refixing in the same loction for smooth functioning & testing, complete all as specified and as directed. | | 1 | Each Job |
|---|