Tender For Repair Maintenance And Improvement To Electromechanical Installation Repair To Diesel Generator Sets Pump Motor And Miscellaneous Electromechanical Equipments And Plants At Alhilal Mil Stn, Alhilal-Himachal Pradesh

Military Engineer Services-MES has published Tender For Repair Maintenance And Improvement To Electromechanical Installation Repair To Diesel Generator Sets Pump Motor And Miscellaneous Electromechanical Equipments And Plants At Alhilal Mil Stn. Submission Date for this Tender is 19-09-2019. Diesel Generators Tenders in Alhilal Himachal Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

21593926
Tender For Repair Maintenance And Improvement To Electromechanical Installation Repair To Diesel Generator Sets Pump Motor And Miscellaneous Electromechanical Equipments And Plants At Alhilal Mil Stn
Open Tender
Indian
Himachal Pradesh
Alhilal
19-09-2019

Tender Details

Tender For Repair Maintenance And Improvement To Electromechanical Installation Repair To Diesel Generator Sets Pump Motor And Miscellaneous Electromechanical Equipments And Plants At Alhilal Mil Stn

Key Value

Document Fees
INR 500 /-
EMD
INR 29000.0 /-
Tender Value
INR 14.50 Lakhs /-

BOQ Items

Name of Work : REPAIR/MAINTENANCE AND IMPROVEMENT TO E/M INSTALLATION, REPAIR TO DG SETS, PUMP MOTOR AND MISC E/M EQUIPMENTS & PLANTS AT ALHILAL MIL STN.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches in any type of soil not exc. 1.5m wide and not exc. 1.5m deep for laying cables, foundation of poles, stays etc and getting out, complete all as specified. 160 Cum
2 2 All as per the description of serial item No 01 above but depth exc 1.5 mtr but not exc 3.00 mtr 0.24 Cum
3 3 Returning filling in including spreading leveling, watering and well ramming in layers n.exc 25cm thick, complete all as specified 85 Cum
4 4 Removal of excavated material to be distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5m above the starting point, complete all as specified. 75 Cum
5 5 Sand cushioning to under ground cable with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable (10 cm punned thickness above the top of the upper most cable, total 18 cm), complete all as specified and directed. 48 Cum
6 6 Sub class “B” brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal, to length of the brick, complete all as specified and directed. 5200 Each
7 7 M&L PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) for coping etc as mass concrete complete and all as specified and directed. 0.2 Cum
8 8 M&L PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) for foundation of pole, stay assembly etc as mass concrete complete and all as specified and directed. 3 Cum
9 9 Supplying in replacement of PCC pole by erecting truly to vertical position steel tubular swaged pole complete with cast iron base plate welded with pole, finial taper plug, bolt, nut and screws as specified type 410 SP-31 (9 metre long) including one coat of red-oxide zinc chrome primer and two coats aluminium paint on surfaces, exposed to view and making 30cm wide strips (Total 5 Nos) with yellow and black paint alternately on external surface above PCC benching including with writing of pole No with letters/ figures of size not exc 30 mm with black paint on a yellow circle of dia 75 mm after painting, complete all as specified and directed. \nNote:- PCC, earth work shall be measured and paid separately under respective items. 4 Nos
10 10 M & L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engr-in-Charge.\n\n 1 Qtl
11 11 M & L for Painting to existing PCC/Steel tubular LT poles, 9 m long including cross arms, channels, angle iron support, bracings, clamps etc, with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping including writing MES LT/HT feeder No and pole No (in capital letters ) stencil cut decorative manner on pole using fluorescent paint etc complete all as specified and directed. 150 Nos
12 12 M &L for Aluminium conductor, steel reinforced (ACSR) conductor for LT lines on PCC/steel tubular poles, stretching without kinks and bends including binding wire including taking down old conductor of any type shape and size complete all as specified. 1 Qtl
13 13 Trimming of tree branches from HT/LT overhead line to branch 2 mtr up to both side & re-stretching of ACSR conductor and earth wire of any size and type on HT/LT poles including disconnecting and rebinding with insulators with suitable size of binding wire after restretching, connecting jumpers, adjusting line deviders etc, complete including removing and refixing of UG cable /service wires to the ACSR conductor, complete all as specified and directed by Engr-in-charge.\nNote:- Single length of the conductor shall be mesured. 800 RM
14 14 S&Replacement of PVC LT line separators 4/5 way, complete all as specified and directed. 12 Each
15 15 S&Replacement of PVC LT line separators 2/3 way, complete all as specified and directed. 12 Each
16 16 M & L for Stay Assembly using stay rod of 20 mm dia complete with accessories as shown in Electrical Plate No 5 of SSR 2009 Part- I with galvanized steel stranded wire of size specified, complete all as specified and directed.\nNote:- Loop insulator, earth work and PCC shall be measured and paid separately under respective items. 3 Each
17 17 M &L for Galvanized steel wire 4mm dia for guard/earth wire on LT poles stretched without kinks, bends and binding with wire including fabrication of cradles, spacers road crossing etc, complete all as specified including taking down old wire of any type shape and size complete all as specified. 0.5 Qtl
18 18 Taking down insulators any size/type including galvanised mild steel spindle. 21 Each
19 19 Supply and fixing Loop type insulator, porcelain, vitreous white, brown or green, large size with over all dimensions 90x140mm clearance of hole 25.5 mm, complete all as specifed 3 Each
20 20 Renewal of pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100 mm height, 65 mm dia for 1100 volts, complete all as specified and directed. 3 Each
21 21 Replacement of shackle type insulator porcelain vitreous white, brown or green 75 mm high and 90 mm dia for conductor of working pressure 1100 volts including galvanised mild steel straps of 31x3mm size, 12 mm dia insulator bolts, washers and nuts, complete all as specified and directed. 15 Each
22 22 Supply, laying, testing and commissioning XLPE insulated heavy duty armoured cable of cross-sectional area 120 Sqmm 3.5 core, 1100 volts grade with aluminium conductor including lugs, glands joints, and taking out UG cable of any type/size compete all as specified and directed. \nNote:- Earth work, sand cushioning, bricks will be measured and paid separately. 100 RM
23 23 All as per the description of serial item No 22 above but 95 Sqmm 3.5 core. 100 RM
24 24 All as per the description of serial item No 22 above but 70 Sqmm 3.5 core. 125 RM
25 25 All as per the description of serial item No 22 above but 50 Sqmm 3.5 core. 100 RM
26 26 All as per the description of serial item No 22 above but 35 Sqmm 3.5 core. 120 RM
27 27 All as per the description of serial item No 22 above but 25 Sqmm 3.5 core. 100 RM
28 28 All as per the description of serial item No 22 above but 16 Sqmm 4 core. 200 RM
29 29 All as per the description of serial item No 22 above but 10 Sqmm 4 core. 100 RM
30 30 All as per the description of serial item No 22 above but 16 Sqmm 2 core. 100 RM
31 31 All as per the description of serial item No 22 above but 10 Sqmm 2 core. 250 RM
32 32 Suppy & laying 80mm bore dia steel tubes, Light grade, ISI Marked as per IS-1239 Part-I galvanised with all fitting and fixed complete to walls and ceilings, on pole or laid in floors or in trences etc for protection of under ground cable complete all as specified and directed. 18 RM
33 33 All as per the description of serial item No 32 above but 50mm bore dia. 24 RM
34 34 All as per the description of serial item No 32 above but 40mm bore dia. 12 RM
35 35 Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hungers not more that 1m apart including 4mm dia suspension GI wire with stranded conductor 10 Sqmm twin core cable flat or circular, including taking down old unserviceable cable and stacking at site, complete all as specified. 200 RM
36 36 All as per item No 24 above but for 16 Sqmm 100 RM
37 37 S&F danger notice plate 1.6 mm thick mild steel sheet vitreous enameled white, with letter figures & incoventional skull and bones in signal red colour and fixed with MS clamps and bolts of approved size for HT poles size 25 x20cm, complete all as directed. 8 Each
38 38 M&L for site clearance of electrical installation/four pole by cleared of shurbs, Vegetation cutting of grass, bush, wood trees not exceeding 30 cm dia branches and roots and leveling of area and removal of same outside MD land all as directed. 2000 Sqm
39 39 Supply & replacement discharge and earthing rod assembly complete in 3 or 4 section (18 to 20 ft) long with screw handed jaw contact, earth wire etc complete. 1 Each
40 40 S&F MCCB 63 amps rupturing capacity 16 KA 4 pole 415 volts AC with fixed thermal magnetic release including taking out old unserviceable MCCB of any capacity and store in safe custody for credit complete all as specified and directed. 2 Each
41 41 S&F MCCB 125 amps rupturing capacity 16 KA 4 pole 415 volts AC with adjustable thermal and adjustable magnetic setting including taking out old unserviceable MCCB of any capacity and store in safe custody for credit complete all as specified and directed. 2 Each
42 42 S&F MCCB 160 amps rupturing capacity 36 KA 4 pole 415 volts AC with adjustable thermal and adjustable magnetic setting including taking out old unserviceable MCCB of any capacity and store in safe custody for credit complete all as specified and directed. 2 Each
43 43 S&F MCCB 200 amps rupturing capacity 36 KA 4 pole 415 volts AC adjustable thermal and adjustable magnetic setting including taking out old unserviceable MCCB of any capacity and store in safe custody for credit complete all as specified and directed. 2 Each
44 44 S&F MCCB 250 amps rupturing capacity 36 KA 4 pole 415 volts AC adjustable thermal and adjustable magnetic setting including taking out old unserviceable MCCB of any capacity and store in safe custody for credit complete all as specified and directed. 2 Each
45 45 S&F MCCB 400 amps rupturing capacity 50 KA 4 pole 415 volts AC adjustable thermal and adjustable magnetic setting including taking out old unserviceable MCCB of any capacity and store in safe custody for credit complete all as specified and directed. 1 Each
46 46 Supply and replacement MCB TPN 63 Amps 415 volts AC, C curve complete all as specified and directed. 2 Each
47 47 Supply and replacement MCB SPN 6-32 Amps 240 volts AC complete all as specified and directed. 8 Each
48 48 Supply & spreading graded coarse aggregate 40mm thick spreading under/over sand for two pole/four pole structure making bed 150 mm thick including brick edging as directed at site complete all as specified and directed. 5 Cum
49 49 Supply & fix lightening arrestor, expulsion type complete with all fittings, transmission class, discharge capacity 65 KA with all connecting lead and fittings, horn gap and chocking soil suitable for maximum working pressure 11000 Volts including taking down existing unserviceable lightening arrestor all as specified and directed. 2 Set of three
50 50 M & L for painting to internal/external surfaces of all sides for fencing, gate, iron posts etc with coat of superior quality of synthetic enamel paint of approved make at various (transformer) sub station complete all as specidfied and directed. 20 Sqm
51 51 Preparation of old plastered or treated surfaces of wall and applying one coat of white washing complete all as specified and directed. 18 Sqm
52 52 Taking down old unserviceable post top lantern any type/size, supply and fixing 30 W LED Post Top lantern with die cast aluminium spigot and lid cover, high efficient LEDs and clear acrylic cover IP65 complete all as specified and directed. 2 Each
53 53 M & L for Air termination, single pointed, aluminium rod 12mm dia and 300mm long including taking down old unserviceable air termination rod and kept in safe custody for reuse or credit all as specified and directed. 10 Each Set
54 54 S&F epoxy base insulator of size 40 mm height fixed on walls/PCC block/on floor/on MS angle/on towers etc including taking down old unserviceable epoxy base insulator and kept in safe custody for reuse or credit all as specified & directed by Engr -in-Charge. 30 Each
55 55 Supply, lay and fix aluminium strip 25 x 3.15mm as roof/down conductor burried in ground/fix on wall with epoxy based insulator and screws/bolts, nuts & leads washers fixed on roof/wall. Epoxy insulators shall be propoerly fixed/grouted on roof/wall/PCC block of size 15x15x15 cm at every distance of 100cm apart including taking down old unserviceable aluminium strip and kept in safe custody for reuse or credit all as specified and directed. \nNote:- 40mm size epoxy insulator will be measured & paid seperately. 50 RM
56 56 Earthing with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground (earth pit less than 2.25 mtr deep below normal ground level) with top edge of the earth plate not less than 1.5 mtr deep below normal ground level, connected to 4mm dia galvanized iron wire as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel complete with 15mm dia light grade protection pipe, 20mm dia GI light grade watering pipe with funnel including char coal dust, salt, PCC 1:2:4 in pit with precast RCC M-15 cover reinforced with XPM not less then 4.00 Kg per sqm including necessary earth work in any type of soil, removal of surplus soil to a distance not exc 50m, returning filling in complete as shown in electrical plate No 3 of SSR Part-I (2009), and connected to earthing test point all as specified or indicated, including testing on completion.\nNOTE: The rates for earthing includes the cost of earth lead and protection pipe upto 7.50m length. 1 Each
57 57 Earthing with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground (earth pit less than 2.25 mtr deep below normal ground level) with top edge of the earth plate not less than 1.5 mtr deep below normal ground level, connected to galvanized iron strip of size 32x6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel complete with 40mm dia light grade protection pipe, 20mm dia GI light grade watering pipe with funnel including char coal dust, salt, PCC 1:2:4 in pit with precast RCC M-15 cover reinforced with XPM not less then 4.00 Kg per sqm including necessary earth work in any type of soil, removal of surplus soil to a distance not exc 50m, returning filling in complete as shown in electrical plate No 3 of SSR Part-I (2009), and connected to earthing test point all as specified or indicated, including testing on completion.\nNOTE: The rates for earthing includes the cost of earth lead and protection pipe upto 7.50m length. 2 Each
58 58 M&L for carrying out periodical maintenance of DG set of capacity 63 KVA/ 40 KVA installed at Alhilal water supply installation / `F' area for STP and check as per recommendations of manufacturer including replacement of necessary filters any type such as oil filters, fuel filters , screen filter, Eng lubricating oil, topping up radiator coolent and battery water etc. all as directed. 2 Each Job
59 59 Supply and fix in repair asbastus rope, ( 8mm dia of superior quality) wrapping to the cylincer pipe of DG set of cap 63 KVA including binding with 2mm dia GI binding wire and providing white cement/ plaster of paris to the asbastus rope for smooth finishing all as directed. 1 Each Job
60 60 Taking out FIP from the DG set carefully for repair and calibration of Fuel Injection pump as per standard calibration procedure and norms for 63 KVA/ 40 KVA DG set including pressure cleaning of fuel nozzles , replacement of minor spares, gasket etc and refixing serviceable items including transportation the pump set from site to workshop and workshop to site alongwith testing at site complete all as specified and directed. 1 Each Job
61 61 Taking out unsv self starter from DG set of cap 63 KVA/ 40 KVA for repair and servicing of the self starter including replacement/rewinding of commutator, carbon brush set with holder king pin holder, armature, choke nut body screen clutch plate assembly and solenoid coil etc incl transportation of the same from site to workshop and workshop to site alongwith testing at site complete all as specified and directed by Engr-in-Charge. 1 Each Job
62 62 Taking out dynmo assy from the DG set of Cap 63 KVA/ 40 KVA and transporting to wksp, strip opening , rewinding of the same and replacement of unsv parts such as carbon brush set, brush holder , refixing of the same with DG set and testing for smooth functioning complete all as specified and as directed.\nNote:- Cost of any other minor spare required is deemed to be included in the quoted rates 1 Each Job
63 63 Taking out unsv water pump after disconnecting of radiator assy and M&L for complete repair and servicing of water pump including replacement of repair kit , bearing etc for 63 KVA DG set incl transporting from site to workshop and workshop to site alongwith testing at site complete all as specified and directed. 1 Each Job
64 64 M&L for de-scaling of radiator including soldering and welding as required and renewal of gaskets, nuts, bolts including supply and fixing mounting pads, hoses, clips etc for 63 KVA/ 40 KVA DG set from site to workshop and workshop to site alongwith testing at site complete all as specified and directed. 2 Each Job
65 65 Taking out of self starting system of DG set of capacity 63 KVA and replacement of the unserviceable Battery 12V, 180 AH from the DG set and supply and fix 12V 180 AH 25 plate maintenance free battery with terminal clamps copper lead of suitable length including testing and commisioning complete all as specified and directed. 2 Each
66 66 S&F Battery charger 12V comprising transformer rectifier DC Ammeter, DC voltmeter and charge rate selector switch with OFF/TRICKLE/BOOST complete all as specified and directed. 1 Each
67 67 Taking out old unsv radiator fan blade complete and S&F new radiator fan blade as pe sample suitable for DG set of cap 63 KVA/ 40 KVA of make Kirloskar Green/Kirloskar Bliss complete all as specified and directed. 1 Each
68 68 S&F in repair Change Over switch 4 pole flush mounting,front operated on - load type 125 Amps 415 Volts complete all as specified and directed. 1 Each
69 69 Supply anf fix in repair Volt meter 0-500 volts digital type. 1 Each
70 70 Supply and fix in repair Amps meter 0-100 Amps digital type. 1 Each
71 71 Supply and fix in repair Frequency meter digital type 1 Each
72 72 Supply and fix in repair indicating lamps 22.5 mm dia LED type, 230 V AC to show three phase availability complete as specified. 3 Set of three
73 73 Making all arrangement and taking up/out submersible pump of capacity 7.5HP, 3 phase from Bore well including column pipe after disconnecting the complete electrical connection and transporting to wksp for repairing/overhauling. Staking of MS column pipes properly for reuse complete all as directed. 1 Each Job
74 74 Strip opening of submersible motor of capacity 7.5 HP and taking out burnt out windings . Cleaning of motor rotor and stator with cleaning material. Rewinding of motor with stove enamelled copper wire of existing gauge . Repalcement of unserviceable parts as required. Assembling of motor duly tested and transporting the same from workshop to site complete all specified and directed. \nNote:- The cost of spares required is deemed to be included in the quoted rate. 1 Each Job
75 75 M&L for Submersible flat copper conductor 1100 Volts grade conf to IS- 694/1990 size 6 sqmm 3 core complete all as specified and as directed. 150 RM
76 76 Supply and fix in repair Panel Mounting type automatic Star delta starter for 22KW motor of size 600mm (L) x 600mm (W) x 250mm (D) with overload relay of range 20-32 Amps , power contractors of suitable capacity , timer range and single phase preventer , ON/OFF actuators etc with MCCB 100Amp, 4 Pole, 25KA as main switch complete all as specified and directed. 1 Each
77 77 Supply and fix in repair automatic Star delta starter for 12.5 HP motor with overload relay of range 10-16 Amps , power contractors ML-1 and suitable capacity timer range , single phase preventer complete all as specified and directed. 1 Each
78 78 Supply & fix DOL starter, 3 phase, 415 volts for 5 HP electric motor complete all as specified and directed. 1 Each
79 79 Supply & fix DOL starter, 3 phase, 415 volts for 7.5 HP electric motor complete all as specified and directed. 2 Each
80 80 Dismantling of centrifugal pump sets any make any type of cap 5.0 to 15 HP carefully after disconnecting electrical connection and pipes etc and taking out/transporting to workshop for repairs complete all as specified and directed. 3 Job
81 81 Strip opening of induction motor of capacity 12.5 to 15 HP and taking out burnt out windings . Cleaning of motor rotor and stator with cleaning material. Rewinding of motor with stove enamelled copper wire of existing gauge . Assembling of motor and testing complete to the satisfaction of Engineer-in -Charge. . 2 Each
82 82 Strip opening of induction motor of capacity 5 to 7.5 HP and taking out burnt out windings . Cleaning of motor rotor and stator with cleaning material. Rewinding of motor with stove enamelled copper wire of existing gauge . Assembling of motor and testing complete to the satisfaction of Engineer-in -Charge. . 1 Each
83 83 Transporting pump set from workshop to pump house(site) and making all arrangement for re-assembling the pump set and motor of capacity 5HP/15 HP and re-installed the same carefully after connecting the complete electrical connection and pipes etc after cleaning and testing the same complete all as directed. 3 Job
84 84 Supply and fix Cast iron non return valve double flanged conforming to IS, class PN-1.0 of size 80mm bore, provision of carbon steel nuts,bolts & washers, rubber gaskets etc fixed to GI water mains complete all as specified and directed. 2 Each
85 85 Supply and fix Cast iron foot valve of size 80mm bore complete all as specified and directed. 2 Each
86 86 Supply and fix Coupling Bolt ( as per sample) for induction motor 22 HP complete all as specified and directed. 30 Each
87 87 Supply and fix Coupling suitable for induction motor 22 HP (as per sample) complete all as specified and directed. 2 Each set
88 88 Supply, installation, connecting and testing 80mm bore dia sluice valve, cast iron body (long body) class PN- 1.6 with flanged ends drilled, ISI marked having stainless steel spindle with iron wheel at top complete with and including nuts, bolts, washers, rubber gasket etc including taking down complete all as specified and directed. 2 Each
89 89 All as per the description of serial item No 88 above but 150mm bore dia. 2 Each
90 90 All as per the description of serial item No 88 above but 200mm bore dia. 2 Each
91 91 M&L for preparation of existing old painted steel surfaces of any description such as panels at any height and painted inside and outside (strictly as per existing shade) complete after scratching existing rusted surface then applying one coat of red oxide primer (superior quality) and two coats of synthetic enamel paint (blue color) all around the panels and plinth complete all as specified and directed. 8 Each
92 92 Suply and fix in replacement of rubber matting , 19 mm thick 1100 Volts of size 2 m x 1 m x 10 mm ISI marked complete. 6 Each
93 93 Supply and fix in replacement of U/s copper Bus Bar of any size of exisiting LT Panel mounted on insulators incl cutting /welding /drilling, making connection and testing all as directed at site. 2 KG
94 94 M&L for in replacement MS sheet cover made out of 3mm thick and angle iron frame 40 x 40 x 6 mm around edge duly welded as per existing with locking arrangement and lifting handle including two coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and directed. 200 Kg
95 95 Supply and laying 100mm bore dia steel water tubing medium grade (ISI marked), galvanized iron with and including all fitting (ISI marked) laid in trenches/fixed to wall/fixed on pillars etc complete all as specified and as directed. 50 RM
96 96 All as per the description of serial item No 95 above but 80mm bore dia. 40 RM
97 97 All as per the description of serial item No 95 above but 50mm bore dia. 50 RM
98 98 Taking up or down 100mm bore dia cast iron/GI steel tubing with connection from trenches, walls, floors etc including removal from site complete all as specified and as directed. 50 RM
99 99 All as per the description of serial item No 98 above but 80mm bore dia. 40 RM
100 100 All as per the description of serial item No 98 above but 50mm bore dia. 50 RM
101 101 Suply and fix in repair monobloc pump set ,single phase head 18 mtr capacity 2250 LPH & Power Rating 1.0 HP . Complete all as specified and and as directed \nMake : Kirloskar, Model MINI 40S / CG /Havells or equivalent. 1 Each
102 102 Material and labour for replacement for motor pump foundation including angle iron frame , breaking existing PCC foundation ,new PCC foundation ,grouding nut bolt all as directed Engineer in charge at site 2 Each Job
103 103 M & L for construction of valve pit of size 900mm x 900mm x 900mm, stone masonry construction complete with mild steel sheet cover 3 mm thick and angle iron frame of size 40 x 40 x 6 mm duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and including locking arrangement and lifting handle all as specified and shown on drawing. All internal surface and external surface upto 15 cm below normal ground level of stone masonry shall be plastered 15 mm thick in cement mortar 1:4, finish even and smooth including necessary excavation and earth work in any type of soil complete all as specified and as directed. 6 Each
104 104 M&L for welding existing broken panel doors and fixing good quality hinges(any size any number of hinges per panel) of suitable size for making open and close the panel doors and fixing/welding angle/notch to lock the door and including welding and making good any other broken portion of panel(double door also) complete all as specified and directed by Engr-In-Charge. 6 Each
105 105 S&F Energy Efficient 60W LED Street Light fixtures with sufficient number of LEDs, control gear and all other associated accessories and colour temperature more than 6500 ºK and conforming to the degree of protection IP - 66 suitable for pole dia Ø 35/40 mm on existing poles complete all as specified and directed. 8 Each
106 106 S&F Energy Efficient 200W LED fllod light with sufficient number of LEDs, control gear and all other associated accessories and colour temperature more than 6500 ºK and conforming to the degree of protection IP - 66 complete all as specified and directed. 4 Each