Tender For Repair/Maintenance Of Lt Ug Cable , Mccbs , Apfc Panel And Other Allied Works At Tech Area Afs Digaru ., DIG-Assam

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Lt Ug Cable , Mccbs , Apfc Panel And Other Allied Works At Tech Area Afs Digaru .. Submission Date for this Tender is 10-09-2019. Power Factor Panel Tenders in DIG Assam. Bidders can get complete Tender details and download the document.




Tender Notice

21593609
Tender For Repair/Maintenance Of Lt Ug Cable , Mccbs , Apfc Panel And Other Allied Works At Tech Area Afs Digaru .
Open Tender
Indian
Assam
DIG
10-09-2019

Tender Details

Tender For Repair / Maintenance Of Lt Ug Cable , Mccbs , Apfc Panel And Other Allied Works At Tech Area Afs Digaru .

Key Value

Document Fees
INR 500 /-
EMD
INR 19800.0 /-
Tender Value
INR 9.90 Lakhs /-

BOQ Items

Name of Work: Repair / Maint of LT UG cable, MCCBs, APFC panel and other allied works at tech Area AFS Digaru
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Maintenance of existing APFC panel and cleaning of dust inside with blower, cleaning of moving part /contacts from CT cleaner, tightening of loose parts /electrical wires, cleaning of contractors, relays and capacitors junction points, servicing/oiling to cooling fan, complete testing of APFC relay with necessary settings with CTs /load adjustments to match with the APFC load management system complete with replacement of worn out unserviceable components /burnt wires thimbles /lugs complete tested of cap 60 KVAR to 100 KVAR all as directed (i) Parts /components for replacement shall be measured and paid for seperately. (ii) replacement of small nuts /screws, burnt copper wires /lugs or thimbles /cleaning materials or CTC shall not be paid seperately the cost of these are deemed to include the Schedule 'A' item rate (iii) The parts should be of the same make and capacity of existing one which is required to be replaced. 1 Each job
2 2 Replacement of following spare part in maintencance carried out under item no 1 above in existing APFC panels Rate for fixing charges are deemed to be included in the srl item No 1 above)
3 2.01 Supply only 10 KVAR Capacitor (QHHTCC5010 X 0) Make-Havells / L & T /HPL 3 Each
4 2.02 Supply only MCB TP 450 Volts 10 KA of capacity 25 Amps Make-Havells / L & T /HPL 1 Each
5 2.03 Supply only MCB TP 450 Volts 10 KA of capacity 32 Amps Make-Havells / L & T /HPL 1 Each
6 2.04 Supply onlyMCB TP 450 Volts 10 KA of capacity 63 Amps Make-Havells / L & T /HPL 1 Each
7 2.05 Supply only Contractor heavy duty suitable for APFC panel TP 450 Volts of capacity 12.5 Amps of Make-Havells / L & T /HPL 1 Each
8 2.06 Supply only Contractor heavy duty suitable for APFC panel TP 450 Volts of capacity 25 Amps of Make-Havells / L & T /HPL 1 Each
9 2.07 Supply only Contractor heavy duty suitable for APFC panel TP 450 Volts of capacity 63 Amps of Make-Havells / L & T /HPL 1 Each
10 2.08 Supply only Contractor heavy duty suitable for APFC panel TP 450 Volts of capacity 80 Amps of Make-Havells / L & T /HPL 1 Each
11 2.09 Supply only Electric cooling fan single phase 240 Volts suitable for APFC panel complete all as specified and directed. 1 Each
12 2.1 Supply only APFC relay square flush type with Intelligent Power Factor Controller (IPFC - 11003) (Smart Relay) 3ø, 3 x 230V, (L-N), 50Hz of Havells /EPCOS make suitable for 6 to 8 stage. Make-Havells / L & T /HPL 1 Each
13 2.11 Supply only LED and Toggle switch indicator lamps (RYB) set of three complete.Make-Havells /AE 1 Each set
14 2.12 Supply only Indicator lamps (RYB) set of three complete.Make-Havells /AE 2 Set of 03
15 3 Supply only replacement of MCCB 4 pole 250 Amp, 415 Volt 35 KA inthe main controle panel board with replacing the unserviceable including disconnecting /connecting all the cable /bus bars connections for input and out put supply with necessary all jointing materials all as directed Make- /HAVELS /L&T /Legrand complete of capacity 2 Each
16 4 All as per item No 15 here-in-before but of Capacity 4 pole 160 Amps, 415 Volts 25KA complete all as directed Make- /HAVELS /L&T /Legrand 3 Each
17 5 Supply and Laying in repair XLPE insulated, Armoured heavy duty electric cable with aluminum conductor, 1100 volt grade of cross sectional area in trenches/through pipes/ducts or on poles/walls jointing to O/H conductor/ LT panels, main switch with suitable size of Aluminium lugs complete all as specified & directed by Engr-in-Charge including taking down of following sizes given below . ((i) Note: Excavation shall be measures and paid separately under respective items of Sch 'A' (ii) Rate of Aluminium lugs deemed to be included in the qouted Rate of item)
18 5.01 (a) 10 Sqmm 2 core 190 RM
19 5.02 (b) 16 Sqmm 4 core 100 RM
20 5.03 (c) 25 Sqmm 3.5 core 120 RM
21 5.04 (d) 50 Sqmm 3.5 core 160 RM
22 5.05 (e) 70 Sqmm 3.5 core 180 RM
23 5.06 (f) 95 Sqmm 3.5 Core 110 RM
24 6 Excavation in trenches, not exceeding 1.50m wide and not exeeding 1.50m in depth for foundations, trenches of cable or pipe lines etc or and getting out in soft / loose soil complete all as specified and as directed. 160 Cum
25 7 Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil complete all specified and as directed. 100 Cum
26 8 Removing excavated materials (soil) to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point complete all specified and as directed. 60 Cum
27 9 M & L for sand cushioning with coarse sand in trenches for protection of underground electric cable, spread to uniform 23 cm thickness and punned down gently to 18 cm .(Note :- Compacted thickness shall be measured and paid) . 56 Cum
28 10 Supply and laying well burnt sub class B bricks old size bricks, laid flat dry, in trenches with width of the bricks laid to the axis of cable for cable protection complete all as specified and as directed. 5.6 Per 1000 Nos
29 11 Supply and laying(in replacement) GI pipe 40 mm dia “Light Grade” in trenches/under floors or roads/along poles or wall for protection of cables/wire incl sealing ends all as specified & directed. 20 RM
30 12 Earthing complete with copper earth plate electrode 60cm x60cm x3.15mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level ) with top edge of plate not less than 1.5m below ground level, connecting to the 20x3mm copper strip , by means of nuts, bolts, check nuts and washer etc of galvanised iron and earth lead protected by provision of GI pipe light grade 32mm bore light grade from earthing test point or main controling switch as directed including providing funnel with 20mm bore GI pipe light grade, wire mesh,charcoal or coke andcommon salt in alternative layer of 15 Cm (compactedd thickness) all round the earth electrode,concrete earth pit in PCC (1:2:4) type B-1 using 20mm graded stone agagregates with 50mm thick cover of RCC (1:2:4) (re-inforced with 8mm dia TMT bar @15 cm C/C bothways and MS bar handle made of 10mm dia bar) including necessary earth work in excavation,returning in and removal of surplus soil to a distance not exceeding 50mtr, all as per electrical plate No 3 of MES Schedule Part-I including earthing pit cover etc. complete all as directed. 3 Each
31 13 S & F in repair 45 watt new generation energy saving roadway strret light luminairewith complete all as specified and as directed. (Make - HPL, cat part No-HPLLEDSL4560S or equiv of Bajaj/Havells/ Wipro). 5 Each
32 14 Supply, installing, testing and commissioning LT distribution panel board of of size 1.20 m (L) x 0.60 m (H) x 0.50 Mtr (D) ,factory made, cubical, out door type with slant top at least 20cm projection all around, Feeder pliller type fabricated with angle iron / flat iron frame work , enclosed with 3.15 mm thick with independent door for each feeder , bus Bar chamber, cable tray on both sides fully comparted type, front openable hinged door for each compartment with locking arrangement and common openable hinged door from rear side, floor mouting type, dust & vermin proof conforming to IP-54 protection and as per IS, including painting the panel with two coat of synthitic enamel paint over a coat of red oxide primer , including providing Aluminium bus bar three phase 300Amp and half neutral mounted on porcelain insulator with PVC sleeves having RYB & N colour code and making adequate provision to accommodate the following accessories (i) incoming MCCB 200 Amps, 4-pole 415 volts-01 No & outgoing MCCB 160 Amps, 4 pole - 01 No & 63 Amps 01 No( Make-Havells/L&T/Scheneider),Voltmeter & Ammeter- 01 No , indication LED Lamps - 03 Nos,fixed by means of nuts,bolts and washers of suitable size complete , including connecting cables with the incoming / out going feeders by providing cable glands and cable lugs, fixing of earth lead to earth terminal of panel complete, all as specified and directed, including neccesery excavation, PCC foundation not less than 0.5mtr deep x 0.75 mtr wide along the length of panel complete all as specified & as directed.( Note:- Rate of Earth work & PCC work is deemed to be included in the quoted rate) 1 Each \nSet