Indian Oil Corporation Limited-IOCL has published Design, Supply, Installation, Testing And Commissioning Of Tank Farm Management System Package Comprising Of Tank Farm Management System, Safety Plc System, Hydrocarbon Vapours Detection System Etc Along With Associated Works At Vishakhapatnam Terminal , . Submission Date for this Tender is 11-09-2019. Application Software Tenders in Visakhapatnam Terminal Andhra Pradesh. Bidders can get complete Tender details and download the document.
Name of Work: Design, supply, installation, testing and commissioning of Tank Farm Management System Package comprising of Tank Farm Management System, Safety PLC System, Hydrocarbon Vapours Detection System etc along with associated works at VISHAKHAPATNAM TERMINAL , ANDHRA PRADESH | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 10 | SUPPLY COMPONENTS | 10 | ||
2 | 20 | Tank Farm Management System | 20 | ||
3 | 30 | Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better, in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 30 | ||
4 | 40 | For Cone Roof Vertical tanks (Primary and Secondary Radar Gauges - HSD-2x5, FO-2X5, LVFO-2X1, LDO-2X1 ,SKO-2X1, PCK- 2X1, Jet fuel- 2x3, ATF-2X2, LSHFHSD- 2X2) | 40 | 42 | EA |
5 | 50 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges : MS-2X2,Transmix-2x2 ) | 50 | 8 | EA |
6 | 60 | For External Floating Roof Vertical tanks (Primary and Secondary Radar Gauges - MS-2x3) | 60 | 6 | EA |
7 | 70 | For A/G Horizontal tanks (Primary and Secondary Radar Gauges - Ethanol -2X3) | 70 | 6 | EA |
8 | 80 | Supply of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better, in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 80 | ||
9 | 90 | For water tanks : Water-2 Nos.;SLUDGE-1 Nos. | 90 | 3 | EA |
10 | 100 | Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. | 100 | ||
11 | 110 | With minimum 8 elements temperature sensor (for above ground tanks -MS-5,HSD-5, FO-5, LVFO-1, LDO-1 ,SKO-1, PCK- 1, Jet fuel- 3, ATF-2, LSHFHSD- 2, Transmix-2, Ethanol-3) | 110 | 31 | EA |
12 | 120 | Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 120 | ||
13 | 130 | ( 3 ELEMENTS for above ground tanks --MS-5,HSD-5, FO-5, LVFO-1, LDO-1 ,SKO-1, PCK- 1, Jet fuel- 3, ATF-2, LSHFHSD- 2, Transmix-2, Ethanol-3) | 130 | 31 | EA |
14 | 140 | Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 140 | ||
15 | 150 | For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) | 150 | 62 | EA |
16 | 160 | For water tanks : Water-2 Nos.;SLUDGE-1 Nos. | 160 | 3 | EA |
17 | 170 | Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document | 170 | ||
18 | 180 | For A/G Vertical Product tanks | 180 | 31 | EA |
19 | 190 | Supply of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. | 190 | ||
20 | 200 | For Primary Radar gauges installed on A/G vertical & horizontal product tanks, water tank & Sludge tank | 200 | 1 | SET |
21 | 210 | For Secondary Radar gauges installed on A/G vertical & horizontal product tanks, | 210 | 1 | SET |
22 | 220 | Supply of 2 Nos. of TFMS Server (Rack type ) along with 1 No. rack mounted colour LED monitor, standard keyboard, mouse, 4 port industrial grade KVM switch, Licensed OS (latest supported by TFMS software), Licenced Antivirus, Licenced latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. (Locations: 2 nos. in Control Room)\r\nNote: Original OEM TFMS software to be loaded in both of TFMS Servers in Control Room. | 220 | 1 | SET |
23 | 230 | Supply of TFMS Workstation with minimum 27" LED colour monitor, standard keyboard, mouse, KVM Switch, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. (Locations: 1 nos. in Control Room + 1 no. TM's cabin).\nOriginal OEM TFMS client software to be loaded in 2 nos of TFMS work station. | 230 | ||
24 | 240 | Rack type at Control Room, form factor - Rack, CPU height - 2U | 240 | 2 | EA |
25 | 250 | Tower type at TM Cabin | 250 | 1 | EA |
26 | 260 | Push Buttons Outside Dyke Walls | 260 | ||
27 | 270 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. | 270 | ||
28 | 280 | For ROSOVs ( 25 Tank x 3 nos.) | 280 | 75 | EA |
29 | 290 | for MOV's (6 tanks x3 nos.) | 290 | 18 | EA |
30 | 300 | For tank water draw off MOVs ( 31 Tank x 1 nos.) | 300 | 31 | EA |
31 | 310 | ESD PUSH BUTTON STATION | 310 | ||
32 | 320 | Supply of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. | 320 | ||
33 | 330 | Local ESD Push Button Station ( Each Battery of TLF -2 no., TLF pump house - 1 no., TW Unloading Area -14, TW Unloading Pump House-1) | 330 | 18 | EA |
34 | 340 | Plant ESD Push Button Station ( Each battery of TLF - 2 No., Main Entry/Exit of Tank Wagon Unloading Area-2) | 340 | 4 | EA |
35 | 350 | Supply of Plant ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) | 350 | 3 | EA |
36 | 360 | Control Room equipments | 360 | ||
37 | 370 | Supply of Triple / Quadruple Modular Redundant, SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels with Biometric Fingerprint cum contactless smart card reader and allied acessoriesand limit switches, Marshalling Panels with Biometric Fingerprint cum contactless smart card reader and allied acessoriesand limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI console, wirings, glands, plugs, other modules/ hardwares required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document. Safety PLC shall be designed with consideration of present IO's + future IO's or 2500 nos IO's whichever is minimum. | 370 | 1 | LS |
38 | 380 | Supply of redundant System Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 18.5" suitable for 24x7 operation along with High availability redundancy software working on redundant (Primary and Secondary) hot standby mode , keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document.\nOR\nSupply of Dual Mode Redundant Grade with built in redundancy TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 18.5" suitable for 24x7 operation, keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document. \n\nTAS Management Servers (TAS-MS) shall have either of the above mentioned configuration meeting the complete specification and tender requirements. \n\nIn addition, the TAS-MS shall be configured to have Zero Downtime to repair, Full data redundancy shall be provided using proven technology , it shall also provide port level redundancy.The system solution shall be capable of self fault detection and isolation, all necessary hardware/software configuration etc to achieve the same shall be included. | 380 | 1 | LS |
39 | 390 | Supply of Complete Sysyem Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for System Management Server, Operator work stations, fire fighting OIC, Engineering Work Stations, work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nThe supplied software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- System Management Server \n- Valve Automation System (ROSOVs, MOVs, DBBV, MCS Interface, SOVs, etc)\n-Tank Farm Management System ( TFMS Server, Primary & Secondary Radar Gauging, AOPS, Level transmitters, Level Switch, Density probes, MSTW, CIU etc)\n- MCC, Pump, Borewell, DG Sets, Air compressors, VFDs\n- HC Detection System Interface\n- Fire Fighting System,, Fire Engines, DG Set, Jockey pumps,\n- ESD System, Emergency panel, Power ESD, Local ESD, Wailing sirens\n-Pressure Transmitters\n- UPS & Power distribution boards etc\n- Interface with IOCL SAP through firewall\n- Any other Third Party Interface/ devices as per scope of the work order etc | 390 | 1 | LS |
40 | 400 | Supply of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader for front & back door seperately with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. | 400 | ||
41 | 410 | For mounting of CIU, redundant SYMS / TFMS server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, Ethernet switch, GSM modems, MCBs etc as per specification and tender document. (Location: Control Room Building) | 410 | 2 | LS |
42 | 420 | For mounting of ethernet switchs ,LIU & OFC componets along with required accessories like power sockets etc complete as per specification and tender document.\n(Location: Control Room) | 420 | 1 | LS |
43 | 430 | For mounting of Rack mounted Master Control Stations (4 sets of redundant MCS) for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. (Location: Control Room Building) | 430 | 1 | EA |
44 | 440 | Supply of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor, standard keyboard, mouse,KVM Switch, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. CPU shall be kept in Panel room in Rack. | 440 | ||
45 | 450 | 23" Rack Mounted type (1 nos. in Control Room, 1 EWS/OIC ) in CR, | 450 | 2 | EA |
46 | 460 | Supply of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor, standard keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. | 460 | ||
47 | 470 | Tower mounted type in TM's Cabin | 470 | 1 | EA |
48 | 480 | Supply of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) (rack mounted) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. | 480 | 2 | EA |
49 | 490 | Supply of minimum 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) (rack mounted) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, EWS, OPC Servers, Alarm Display OIC, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. | 490 | ||
50 | 500 | 24 ports ( 2 optical & 22 Copper ports) Location: Admin Building | 500 | 2 | EA |
51 | 510 | 24 ports ( 2 optical & 22 Copper ports) Location: Control Room | 510 | 2 | EA |
52 | 520 | 10 ports ( 2 optical & 8 Copper ports) Location: Plant manager room | 520 | 2 | EA |
53 | 530 | Supply of Monochrome Laser Printer along with accessories for PLC and TFMS report printing in control room (2 nos.) complete as per specifications and tender document. | 530 | 2 | EA |
54 | 540 | Supply of parallel redundant UPS of minimum capacity of 60 KVA or as per load calculation (whichever is higher) for entire TAS equipments and third party devices integrated with TAS and powered through TAS UPS with 30% spare capacity for future load connection. The scope also includes supply of parallel battery bank (2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries etc complete as per specification and tender document. The batteries shall be Sealed Maintenance free type Ni-Cd batteries. | 540 | 1 | SET |
55 | 550 | Supply of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader with accessories for powering Safety PLC Panel, SYMS, OIC, EWS, TFMS System, printers, other control room equipments, Tank Farm Instruments, other display boards, ROSOV ESD port and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. | 550 | 1 | LS |
56 | 560 | Supply of Open desk operator consoles, chairs, printer tables etc complete as per specification and tender document. | 560 | ||
57 | 570 | Open desk operator consoles for mounting of 2 nos. of 27" Rack mounted CPU, 2 Nos. of keyboard, 2 Nos. of optical mouse, 2 Nos. of monitor in two tiers etc. ( Each console will consists of nessary electrical wirring, 4 Nos. Sockets, 4 Nos. buttons, MCBs as required, LIght, Louvers & FAN number as required.) as shown in drawing attached in tender.\n(for mounting 1 OIC, 1 EWS, 1 TFMS workstation, ) | 570 | 3 | EA |
58 | 580 | Chairs (Godrej PCH 5002T or equivalent) | 580 | 4 | EA |
59 | 590 | Standard Printer Tables of Godrej or equivalent make (1 nos. in control room) | 590 | 1 | EA |
60 | 600 | Supply of minimum 55" 4K HD LED monitor along 1 Hooter, mounting accessories etc. for alarm display complete as per specifications and tender document | 600 | 1 | EA |
61 | 610 | Supply of minimum 75" 4K HD LED monitor mounting accessories etc. for TFMS display complete as per specifications and tender document | 610 | 1 | EA |
62 | 620 | Hydrocarbon Detection system | 620 | ||
63 | 630 | Supply of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document. | 630 | ||
64 | 640 | Point type Infrared detector (28 nos,TLF pump seal (MS+Transmix) - 7 Nos , Ethanol Decanation pumps - 2 Nos,Stripping pumps MS &Ethanol 1 each =2 Nos ,Sludge pump seal-1 No., Pump house drain pit - 1 no.; Vapour recovery system drain pit - 1 no., Ethanol - 3X4 ) | 640 | 54 | EA |
65 | 650 | Open path type Infrared detector (0-90 m) along with alignment telescope, configuration & Testing kit etc (Transmix + Ethanol) | 650 | 6 | EA |
66 | 660 | Range 0-90 m (10nos + 4 PH Manifold ) | 660 | 14 | EA |
67 | 670 | Supply of weather proof and Explosion proof Hooter cum beasons/ flash light along with accessories and structual supports as per specification. ( Near MS tank Dyke- 2 nos + 1 Ethanol Dyke, Pump House (TLF+Decnatation) - 2 no.,Sludge Pump- 1 No. & Vapour recovery system-1no. ) | 670 | 7 | EA |
68 | 680 | Supply of Portable gas detector along with accessories complete as per specification and tender document. | 680 | 1 | EA |
69 | 690 | Miscellaneous | 690 | ||
70 | 700 | Supply of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, other erection material as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated elese where in tender) | 700 | ||
71 | 710 | Fire Engine pump discharge end | 710 | 6 | EA |
72 | 720 | Jockey pum discharge end | 720 | 2 | EA |
73 | 730 | Hydrant Header lines ( Header -2 nos ) | 730 | 2 | EA |
74 | 740 | AFFF LINE (FOAM LINE) | 740 | 1 | EA |
75 | 750 | Supply of Wailing siren 3 KM RANGE with controller as per specification. | 750 | 1 | EA |
76 | 760 | Supply of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, Customer service room, Driver's Rest Room with minimum 30% spare MCT blocks for future cable entry along with frame and mounting accessories complete as per specification and tender document. | 760 | 1 | LS |
77 | 770 | Supply of external surge & Lightening protection devices of suitable connector and type along with accessories complete as per specification and tender document at following places. | 770 | ||
78 | 780 | Type 1+2 SPD - Input power supply of UPS | 780 | 3 | EA |
79 | 790 | SPD (Type 2 / IC category C1,C2,C3,D1) - Serial port of MCS (RJ 45 type) | 790 | 20 | EA |
80 | 800 | Type 1 SPD - Earth pit | 800 | 17 | EA |
81 | 810 | Cabling, JB, Earthing: | 810 | ||
82 | 820 | Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc | 820 | ||
83 | 830 | Supply of FRLS Armoured Copper Power cable as per tender specifications. | 830 | ||
84 | 840 | 3C x 2.5 sqmm | 840 | 240 | RM |
85 | 850 | 4C x 2.5 sqmm | 850 | 100 | RM |
86 | 860 | 8C x 2.5 sqmm | 860 | 100 | RM |
87 | 870 | 10C x 2.5 sqmm | 870 | 100 | RM |
88 | 880 | 12C x 2.5 sqmm | 880 | 2980 | RM |
89 | 890 | 24C x 2.5 sqmm | 890 | 4920 | RM |
90 | 900 | 3C x 4 sqmm | 900 | 100 | RM |
91 | 910 | 4C x 4 sqmm | 910 | 100 | RM |
92 | 920 | 4C x 6 sqmm | 920 | 100 | RM |
93 | 930 | 4C x 10 sqmm | 930 | 100 | RM |
94 | 940 | Supply of FRLS Armoured Aluminium Power cable as per tender specifications. | 940 | ||
95 | 950 | 3.5C x 120 sqmm | 950 | 100 | RM |
96 | 960 | Supply of FRLS Armoured Copper Control cable as per tender specifications. | 960 | ||
97 | 970 | 2C x 1.5 sqmm | 970 | 100 | RM |
98 | 980 | 3C x 1.5 sqmm | 980 | 100 | RM |
99 | 990 | 4C x 1.5 sqmm | 990 | 1260 | RM |
100 | 1000 | 6C x 1.5 sqmm | 1000 | 100 | RM |
101 | 1010 | 8C x 1.5 sqmm | 1010 | 7610 | RM |
102 | 1020 | 10C x 1.5 sqmm | 1020 | 100 | RM |
103 | 1030 | 12C x 1.5 sqmm | 1030 | 9630 | RM |
104 | 1040 | 16C x 1.5 sqmm | 1040 | 100 | RM |
105 | 1050 | 18C x 1.5 sqmm | 1050 | 100 | RM |
106 | 1060 | 20C x 1.5 sqmm | 1060 | 100 | RM |
107 | 1070 | 24C x 1.5 sqmm | 1070 | 12180 | RM |
108 | 1080 | 32C x 1.5 sqmm | 1080 | 100 | RM |
109 | 1090 | 36C x 1.5 sqmm | 1090 | 100 | RM |
110 | 1100 | 48C x 1.5 sqmm | 1100 | 15840 | RM |
111 | 1110 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. | 1110 | ||
112 | 1120 | 1P x 1.5 sqmm | 1120 | 2280 | RM |
113 | 1130 | 2P x 1.5 sqmm | 1130 | 39300 | RM |
114 | 1140 | 3P x 1.5 sqmm | 1140 | 100 | RM |
115 | 1150 | 4P x 1.5 sqmm | 1150 | 6030 | RM |
116 | 1160 | 6P x 1.5 sqmm | 1160 | 100 | RM |
117 | 1170 | 8P x 1.5 sqmm | 1170 | 100 | RM |
118 | 1180 | 10P x 1.5 sqmm | 1180 | 100 | RM |
119 | 1190 | 12P x 1.5 sqmm | 1190 | 1200 | RM |
120 | 1200 | 16P x 1.5 sqmm | 1200 | 100 | RM |
121 | 1210 | 18P x 1.5 sqmm | 1210 | 100 | RM |
122 | 1220 | 1T x 1.5 sqmm | 1220 | 100 | RM |
123 | 1230 | 8T x 1.5 sqmm | 1230 | 2640 | RM |
124 | 1240 | Supply of FS Armoured Copper Power cable as per tender specifications. | 1240 | ||
125 | 1250 | 3C x 2.5 sqmm | 1250 | 8448 | RM |
126 | 1260 | 3C x 4 sqmm | 1260 | 100 | RM |
127 | 1270 | 4C x 2.5 sqmm | 1270 | 100 | RM |
128 | 1280 | 4C x 4 sqmm | 1280 | 100 | RM |
129 | 1290 | Supply of FS Armoured Copper Control cable as per tender specifications. | 1290 | ||
130 | 1300 | 2C x 1.5 sqmm | 1300 | 100 | RM |
131 | 1310 | 3C x 1.5 sqmm | 1310 | 8640 | RM |
132 | 1320 | 4C x 1.5 sqmm | 1320 | 6340 | RM |
133 | 1330 | 6C x 1.5 sqmm | 1330 | 100 | RM |
134 | 1340 | 8C x 1.5 sqmm | 1340 | 100 | RM |
135 | 1350 | 10C x 1.5 sqmm | 1350 | 100 | RM |
136 | 1360 | 12C x 1.5 sqmm | 1360 | 6340 | RM |
137 | 1370 | 18C x 1.5 sqmm | 1370 | 100 | RM |
138 | 1380 | 24C x 1.5 sqmm | 1380 | 100 | RM |
139 | 1390 | 32C x 1.5 sqmm | 1390 | 100 | RM |
140 | 1400 | 36C x 1.5 sqmm | 1400 | 100 | RM |
141 | 1410 | 48C x 1.5 sqmm | 1410 | 100 | RM |
142 | 1420 | Supply of FS Armoured Copper Signal cable as per tender specifications. | 1420 | ||
143 | 1430 | 1P x 1.5 sqmm | 1430 | 25250 | RM |
144 | 1440 | 2P x 1.5 sqmm | 1440 | 2400 | RM |
145 | 1450 | 3P x 1.5 sqmm | 1450 | 100 | RM |
146 | 1460 | 4P x 1.5 sqmm | 1460 | 100 | RM |
147 | 1470 | 1T x 1.5 sqmm | 1470 | 3030 | RM |
148 | 1480 | Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. | 1480 | 100 | RM |
149 | 1490 | Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. | 1490 | 1000 | RM |
150 | 1500 | Supply of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. | 1500 | ||
151 | 1510 | 10 m | 1510 | 50 | EA |
152 | 1520 | 15 m | 1520 | 50 | EA |
153 | 1530 | 20 m | 1530 | 20 | EA |
154 | 1540 | 25 m | 1540 | 25 | EA |
155 | 1550 | 30 m | 1550 | 30 | EA |
156 | 1560 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document | 1560 | 3000 | RM |
157 | 1570 | Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | 1570 | 500 | RM |
158 | 1580 | Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | 1580 | 500 | RM |
159 | 1590 | Supply of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. | 1590 | ||
160 | 1600 | 50 mm | 1600 | 4000 | RM |
161 | 1610 | 100 mm | 1610 | 2500 | RM |
162 | 1620 | 150 mm | 1620 | 2500 | RM |
163 | 1630 | 300 mm | 1630 | 15000 | RM |
164 | 1640 | 600 mm | 1640 | 100 | RM |
165 | 1650 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. | 1650 | ||
166 | 1660 | 24 ways JB | 1660 | 1 | EA |
167 | 1670 | 18 ways JB | 1670 | 23 | EA |
168 | 1680 | 12 ways JB | 1680 | 15 | EA |
169 | 1690 | 8 ways JB | 1690 | 38 | EA |
170 | 1700 | 6 ways JB | 1700 | 18 | EA |
171 | 1710 | 4 ways JB | 1710 | 14 | EA |
172 | 1720 | Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | 1720 | 200 | RM |
173 | 1730 | Earth Pit | 1730 | ||
174 | 1740 | Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) | 1740 | ||
175 | 1750 | Control room | 1750 | 3 | EA |
176 | 1760 | Tank dyke | 1760 | 16 | EA |
177 | 1770 | Pump house ( 2 No. Near Fire Engine P/H) | 1770 | 2 | EA |
178 | 1780 | STRUCTURAL STEEL & CIVIL FOUNDATION | 1780 | ||
179 | 1790 | Supply of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including surface finish, painting, Civil foundations as required , nuts, bolts, washers, cleats, stiffners, gussets, base plate etc | 1790 | 65 | TON |
180 | 1800 | SERVICE COMPONENTS | 1800 | ||
181 | 1810 | Tank Farm Management System | 1810 | ||
182 | 1820 | Installation, integration, testing and commisioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better, in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 1820 | ||
183 | 1830 | For Cone Roof Vertical tanks (Primary and Secondary Radar Gauges - HSD-2x5, FO-2X5, LVFO-2X1, LDO-2X1 ,SKO-2X1, PCK- 2X1, Jet fuel- 2x3, ATF-2X2, LSHFHSD- 2X2) | 1830 | 42 | EA |
184 | 1840 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges : MS-2X2,Transmix-2x2 )) | 1840 | 8 | EA |
185 | 1850 | For External Floating Roof Vertical tanks (Primary and Secondary Radar Gauges - MS-2x3, | 1850 | 6 | EA |
186 | 1860 | For A/G Horizontal tanks (Primary and Secondary Radar Gauges - Ethanol -2X3) | 1860 | 6 | EA |
187 | 1870 | Installation, integration, testing and commisioning of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better, in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 1870 | ||
188 | 1880 | For water tanks : Water-2 Nos.;SLUDGE-1 Nos. | 1880 | 3 | EA |
189 | 1890 | Installation, integration, testing and commisioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. | 1890 | ||
190 | 1900 | With minimum 8 elements temperature sensor (for above ground tanks -MS-5,HSD-5, FO-5, LVFO-1, LDO-1 ,SKO-1, PCK- 1, Jet fuel- 3, ATF-2, LSHFHSD- 2, Transmix-2, Ethanol-3) | 1900 | 31 | EA |
191 | 1910 | Installation, integration, testing and commisioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 1910 | ||
192 | 1920 | ( 3 ELEMENTS for above ground tanks --MS-5,HSD-5, FO-5, LVFO-1, LDO-1 ,SKO-1, PCK- 1, Jet fuel- 3, ATF-2, LSHFHSD- 2, Transmix-2, Ethanol-3) | 1920 | 31 | EA |
193 | 1930 | Installation, integration, testing and commisioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) | 1930 | ||
194 | 1940 | For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) | 1940 | 62 | EA |
195 | 1950 | For water tanks : Water-2 Nos.;SLUDGE-1 Nos. | 1950 | 3 | EA |
196 | 1960 | Installation, integration, testing and commisioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document | 1960 | ||
197 | 1970 | For A/G Vertical Product tanks | 1970 | 31 | EA |
198 | 1980 | Installation, integration, testing and commisioning of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. | 1980 | ||
199 | 1990 | For Primary Radar gauges installed on A/G vertical & horizontal product tanks, water tank & Sludge tank | 1990 | 1 | SET |
200 | 2000 | For Secondary Radar gauges installed on A/G vertical & horizontal product tanks, | 2000 | 1 | SET |
201 | 2010 | Installation, integration, testing and commisioning of 2 Nos. of TFMS Server (Rack type ) along with 1 No. rack mounted colour LED monitor, standard keyboard, mouse, 4 port industrial grade KVM switch, Licensed OS (latest supported by TFMS software), Licenced Antivirus, Licenced latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. (Locations: 2 nos. in Control Room)\n\nNote: Original OEM TFMS software to be loaded in both of TFMS Servers in Control Room. | 2010 | 1 | SET |
202 | 2020 | Installation, integration, testing and commisioning of TFMS Workstation with minimum 27" LED colour monitor, standard keyboard, mouse, KVM Switch, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. (Locations: 1 nos. in Control Room + 1 no. TM's cabin).\nOriginal OEM TFMS client software to be loaded in 2 nos of TFMS work station. | 2020 | ||
203 | 2030 | Rack type at Control Room, form factor - Rack, CPU height - 2U | 2030 | 2 | EA |
204 | 2040 | Tower type at TM Cabin | 2040 | 1 | EA |
205 | 2050 | Push Buttons Outside Dyke Walls | 2050 | ||
206 | 2060 | Installation, integration, testing and commisioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. | 2060 | ||
207 | 2070 | For ROSOVs ( 25 Tank x 3 nos.) | 2070 | 75 | EA |
208 | 2080 | for MOV's (6 tanks x3 nos.) | 2080 | 18 | EA |
209 | 2090 | For tank water draw off MOVs ( 31 Tank x 1 nos.) | 2090 | 31 | EA |
210 | 2100 | ESD PUSH BUTTON STATION | 2100 | ||
211 | 2110 | Installation, integration, testing and commisioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. | 2110 | ||
212 | 2120 | Local ESD Push Button Station ( Each Battery of TLF -2 no., TLF pump house - 1 no., TW Unloading Area -14, TW Unloading Pump House-1) | 2120 | 18 | EA |
213 | 2130 | Plant ESD Push Button Station ( Each battery of TLF - 2 No., Main Entry/Exit of Tank Wagon Unloading Area-2) | 2130 | 4 | EA |
214 | 2140 | Installation, integration, testing and commisioning of Plant ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) | 2140 | 3 | EA |
215 | 2150 | Control Room equipments | 2150 | ||
216 | 2160 | Installation, integration, testing and commisioning of Triple / Quadruple Modular Redundant, SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels with Biometric Fingerprint cum contactless smart card reader and allied acessoriesand limit switches, Marshalling Panels with Biometric Fingerprint cum contactless smart card reader and allied acessoriesand limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI console, wirings, glands, plugs, other modules/ hardwares required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document. Safety PLC shall be designed with consideration of present IO's + future IO's or 2500 nos IO's whichever is minimum. | 2160 | 1 | LS |
217 | 2170 | Supply of redundant System Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 18.5" suitable for 24x7 operation along with High availability redundancy software working on redundant (Primary and Secondary) hot standby mode , keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document.\nOR\nSupply of Dual Mode Redundant Grade with built in redundancy TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 18.5" suitable for 24x7 operation, keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document. \n\nTAS Management Servers (TAS-MS) shall have either of the above mentioned configuration meeting the complete specification and tender requirements. \n\nIn addition, the TAS-MS shall be configured to have Zero Downtime to repair, Full data redundancy shall be provided using proven technology , it shall also provide port level redundancy.The system solution shall be capable of self fault detection and isolation, all necessary hardware/software configuration etc to achieve the same shall be included. | 2170 | 1 | LS |
218 | 2180 | Supply of Complete Sysyem Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for System Management Server, Operator work stations, fire fighting OIC, Engineering Work Stations, work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nThe supplied software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- System Management Server \n -Valve Automation System (ROSOVs, MOVs, DBBV, MCS Interface, SOVs, etc)\n-Tank Farm Management System ( TFMS Server, Primary & Secondary Radar Gauging, AOPS, Level transmitters, Level Switch, Density probes, MSTW, CIU etc)\n-- MCC, Pump, Borewell, DG Sets, Air compressors, VFDs\n- HC Detection System Interface\n- Fire Fighting System,, Fire Engines, DG Set, Jockey pumps,\n- ESD System, Emergency panel, Power ESD, Local ESD, Wailing sirens\n-Pressure Transmitters\n- UPS & Power distribution boards etc\n- Interface with IOCL SAP through firewall\n- Any other Third Party Interface/ devices as per scope of the work order etc. | 2180 | 1 | LS |
219 | 2190 | Installation, integration, testing and commisioning of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader for front & back door seperately with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. | 2190 | ||
220 | 2200 | For mounting of CIU, redundant SYMS / TFMS server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, Ethernet switch, GSM modems, MCBs etc as per specification and tender document. (Location: Control Room Building) | 2200 | 2 | LS |
221 | 2210 | For mounting of ethernet switchs ,LIU & OFC componets along with required accessories like power sockets etc complete as per specification and tender document.\n(Location: Control Room) | 2210 | 1 | LS |
222 | 2220 | For mounting of Rack mounted Master Control Stations (4 sets of redundant MCS) for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. (Location: Control Room Building) | 2220 | 1 | EA |
223 | 2230 | Installation, integration, testing and commisioning of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor, standard keyboard, mouse,KVM Switch, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. CPU shall be kept in Panel room in Rack. | 2230 | ||
224 | 2240 | 27" Rack Mounted type (1 nos. in Control Room, 1 EWS/OIC ) in CR, | 2240 | 2 | EA |
225 | 2250 | Installation, integration, testing and commisioning of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor, standard keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. | 2250 | ||
226 | 2260 | Tower mounted type in TM's Cabin | 2260 | 1 | EA |
227 | 2270 | Installation, integration, testing and commisioning of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) (rack mounted) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. | 2270 | 2 | EA |
228 | 2280 | Installation, integration, testing and commisioning of minimum 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) (rack mounted) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, EWS, OPC Servers, Alarm Display OIC, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. | 2280 | ||
229 | 2290 | 24 ports ( 2 optical & 22 Copper ports) Location: Admin Building | 2290 | 2 | EA |
230 | 2300 | 24 ports ( 2 optical & 22 Copper ports) Location: Control Room | 2300 | 2 | EA |
231 | 2310 | 10 ports ( 2 optical & 8 Copper ports) Location: Plant manager room | 2310 | 2 | EA |
232 | 2320 | Installation, integration, testing and commisioning of Monochrome Laser Printer along with accessories for PLC and TFMS report printing in control room (2 nos.) complete as per specifications and tender document. | 2320 | 2 | EA |
233 | 2330 | Supply of parallel redundant UPS of minimum capacity of 60 KVA or as per load calculation (whichever is higher) for entire TAS equipments and third party devices integrated with TAS and powered through TAS UPS with 30% spare capacity for future load connection. The scope also includes supply of parallel battery bank (2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries etc complete as per specification and tender document. The batteries shall be Sealed Maintenance free type Ni-Cd batteries. | 2330 | 1 | SET |
234 | 2340 | Supply of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader with accessories for powering Safety PLC Panel, SYMS, OIC, EWS, TFMS System, printers, other control room equipments, Tank Farm Instruments, other display boards, ROSOV ESD port and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. | 2340 | 1 | LS |
235 | 2350 | Installation, integration, testing and commisioning of Open desk operator consoles, chairs, printer tables etc complete as per specification and tender document. | 2350 | ||
236 | 2360 | Open desk operator consoles for mounting of 2 nos. of 27" Rack mounted CPU, 2 Nos. of keyboard, 2 Nos. of optical mouse, 2 Nos. of monitor in two tiers etc. ( Each console will consists of nessary electrical wirring, 4 Nos. Sockets, 4 Nos. buttons, MCBs as required, LIght, Louvers & FAN number as required.) as shown in drawing attached in tender.\n(for mounting 1 OIC, 1 EWS, 1 TFMS workstation) | 2360 | 3 | EA |
237 | 2370 | Chairs (Godrej PCH 5002T or equivalent) | 2370 | 4 | EA |
238 | 2380 | Standard Printer Tables of Godrej or equivalent make (1 nos. in control room) | 2380 | 1 | EA |
239 | 2390 | Installation, integration, testing and commisioning of minimum 55" 4K HD LED monitor along 1 Hooter, mounting accessories etc. for alarm display complete as per specifications and tender document | 2390 | 1 | EA |
240 | 2400 | Installation, integration, testing and commisioning of minimum 75" 4K HD LED monitor mounting accessories etc. for TFMS display complete as per specifications and tender document | 2400 | 1 | EA |
241 | 2410 | Hydrocarbon Detection system | 2410 | ||
242 | 2420 | Installation, integration, testing and commisioning of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document. | 2420 | ||
243 | 2430 | Point type Infrared detector (28 nos,TLF pump seal (MS+Transmix) - 7 Nos , Ethanol Decanation pumps - 2 Nos,Stripping pumps MS &Ethanol 1 each =2 Nos ,Sludge pump seal-1 No., Pump house drain pit - 1 no.; Vapour recovery system drain pit - 1 no., Ethanol - 3X4 ) | 2430 | 54 | EA |
244 | 2440 | Open path type Infrared detector (0-90 m) along with alignment telescope, configuration & Testing kit etc (Transmix + Ethanol) | 2440 | 6 | EA |
245 | 2450 | Range 0-90 m (10nos + 4 PH Manifold ) | 2450 | 14 | EA |
246 | 2460 | Installation, integration, testing and commisioning of weather proof and Explosion proof Hooter cum beasons/ flash light along with accessories and structual supports as per specification. ( Near MS tank Dyke- 2 nos + 1 Ethanol Dyke, Pump House (TLF+Decnatation) - 2 no.,Sludge Pump- 1 No. & Vapour recovery system-1no. ) | 2460 | 7 | EA |
247 | 2470 | Conducting fire and hydrocarbon vapour mapping study through reputed agencies having proven track record of conducting similar studies for oil installation across globe,using standard licensed software along with submission of study reports as per specification and tender document. | 2470 | 1 | EA |
248 | 2480 | Miscellaneous | 2480 | ||
249 | 2490 | Installation, integration, testing and commisioning of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, other erection material as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated elese where in tender) | 2490 | ||
250 | 2500 | Fire Engine pump discharge end | 2500 | 6 | EA |
251 | 2510 | Jockey pum discharge end | 2510 | 2 | EA |
252 | 2520 | Hydrant Header lines ( Header -2 nos ) | 2520 | 2 | EA |
253 | 2530 | AFFF LINE (FOAM LINE) | 2530 | 1 | EA |
254 | 2540 | Installation, integration, testing and commisioning of Wailing siren 3 KM RANGE with controller as per specification. | 2540 | 1 | EA |
255 | 2550 | Installation, integration, testing and commisioning of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, Customer service room, Driver's Rest Room with minimum 30% spare MCT blocks for future cable entry along with frame and mounting accessories complete as per specification and tender document. | 2550 | 1 | LS |
256 | 2560 | Installation, integration, testing and commisioning of external surge & Lightening protection devices of suitable connector and type along with accessories complete as per specification and tender document at following places. | 2560 | ||
257 | 2570 | Type 1+2 SPD - Input power supply of UPS | 2570 | 3 | EA |
258 | 2580 | SPD (Type 2 / IC category C1,C2,C3,D1) - Serial port of MCS (RJ 45 type) | 2580 | 20 | EA |
259 | 2590 | Type 1 SPD - Earth pit | 2590 | 17 | EA |
260 | 2600 | Cabling, JB, Earthing: | 2600 | ||
261 | 2610 | Note: Laying,Glanding,ferruling,termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc | 2610 | ||
262 | 2620 | Laying, glanding, ferruling and termination of FRLS Armoured Copper Power cable as per tender specifications. | 2620 | ||
263 | 2630 | 3C x 2.5 sqmm | 2630 | 240 | RM |
264 | 2640 | 4C x 2.5 sqmm | 2640 | 100 | RM |
265 | 2650 | 8C x 2.5 sqmm | 2650 | 100 | RM |
266 | 2660 | 10C x 2.5 sqmm | 2660 | 100 | RM |
267 | 2670 | 12C x 2.5 sqmm | 2670 | 2980 | RM |
268 | 2680 | 24C x 2.5 sqmm | 2680 | 4920 | RM |
269 | 2690 | 3C x 4 sqmm | 2690 | 100 | RM |
270 | 2700 | 4C x 4 sqmm | 2700 | 100 | RM |
271 | 2710 | 4C x 6 sqmm | 2710 | 100 | RM |
272 | 2720 | 4C x 10 sqmm | 2720 | 100 | RM |
273 | 2730 | Laying, glanding, ferruling and termination of FRLS Armoured Aluminium Power cable as per tender specifications. | 2730 | ||
274 | 2740 | 3.5C x 120 sqmm | 2740 | 100 | RM |
275 | 2750 | Laying, glanding, ferruling and termination of FRLS Armoured Copper Control cable as per tender specifications. | 2750 | ||
276 | 2760 | 2C x 1.5 sqmm | 2760 | 100 | RM |
277 | 2770 | 3C x 1.5 sqmm | 2770 | 100 | RM |
278 | 2780 | 4C x 1.5 sqmm | 2780 | 1260 | RM |
279 | 2790 | 6C x 1.5 sqmm | 2790 | 100 | RM |
280 | 2800 | 8C x 1.5 sqmm | 2800 | 7610 | RM |
281 | 2810 | 10C x 1.5 sqmm | 2810 | 100 | RM |
282 | 2820 | 12C x 1.5 sqmm | 2820 | 9630 | RM |
283 | 2830 | 16C x 1.5 sqmm | 2830 | 100 | RM |
284 | 2840 | 18C x 1.5 sqmm | 2840 | 100 | RM |
285 | 2850 | 20C x 1.5 sqmm | 2850 | 100 | RM |
286 | 2860 | 24C x 1.5 sqmm | 2860 | 12180 | RM |
287 | 2870 | 32C x 1.5 sqmm | 2870 | 100 | RM |
288 | 2880 | 36C x 1.5 sqmm | 2880 | 100 | RM |
289 | 2890 | 48C x 1.5 sqmm | 2890 | 15840 | RM |
290 | 2900 | Laying, glanding, ferruling and termination of FRLS Armoured Copper Signal cable as per tender specifications. | 2900 | ||
291 | 2910 | 1P x 1.5 sqmm | 2910 | 2280 | RM |
292 | 2920 | 2P x 1.5 sqmm | 2920 | 39300 | RM |
293 | 2930 | 3P x 1.5 sqmm | 2930 | 100 | RM |
294 | 2940 | 4P x 1.5 sqmm | 2940 | 6030 | RM |
295 | 2950 | 6P x 1.5 sqmm | 2950 | 100 | RM |
296 | 2960 | 8P x 1.5 sqmm | 2960 | 100 | RM |
297 | 2970 | 10P x 1.5 sqmm | 2970 | 100 | RM |
298 | 2980 | 12P x 1.5 sqmm | 2980 | 1200 | RM |
299 | 2990 | 16P x 1.5 sqmm | 2990 | 100 | RM |
300 | 3000 | 18P x 1.5 sqmm | 3000 | 100 | RM |
301 | 3010 | 1T x 1.5 sqmm | 3010 | 100 | RM |
302 | 3020 | 8T x 1.5 sqmm | 3020 | 2640 | RM |
303 | 3030 | Laying, glanding, ferruling and termination of FS Armoured Copper Power cable as per tender specifications. | 3030 | ||
304 | 3040 | 3C x 2.5 sqmm | 3040 | 8448 | RM |
305 | 3050 | 3C x 4 sqmm | 3050 | 100 | RM |
306 | 3060 | 4C x 2.5 sqmm | 3060 | 100 | RM |
307 | 3070 | 4C x 4 sqmm | 3070 | 100 | RM |
308 | 3080 | Laying, glanding, ferruling and termination of FS Armoured Copper Control cable as per tender specifications. | 3080 | ||
309 | 3090 | 2C x 1.5 sqmm | 3090 | 100 | RM |
310 | 3100 | 3C x 1.5 sqmm | 3100 | 8640 | RM |
311 | 3110 | 4C x 1.5 sqmm | 3110 | 6340 | RM |
312 | 3120 | 6C x 1.5 sqmm | 3120 | 100 | RM |
313 | 3130 | 8C x 1.5 sqmm | 3130 | 100 | RM |
314 | 3140 | 10C x 1.5 sqmm | 3140 | 100 | RM |
315 | 3150 | 12C x 1.5 sqmm | 3150 | 6340 | RM |
316 | 3160 | 18C x 1.5 sqmm | 3160 | 100 | RM |
317 | 3170 | 24C x 1.5 sqmm | 3170 | 100 | RM |
318 | 3180 | 32C x 1.5 sqmm | 3180 | 100 | RM |
319 | 3190 | 36C x 1.5 sqmm | 3190 | 100 | RM |
320 | 3200 | 48C x 1.5 sqmm | 3200 | 100 | RM |
321 | 3210 | Laying, glanding, ferruling and termination of FS Armoured Copper Signal cable as per tender specifications. | 3210 | ||
322 | 3220 | 1P x 1.5 sqmm | 3220 | 25250 | RM |
323 | 3230 | 2P x 1.5 sqmm | 3230 | 2400 | RM |
324 | 3240 | 3P x 1.5 sqmm | 3240 | 100 | RM |
325 | 3250 | 4P x 1.5 sqmm | 3250 | 100 | RM |
326 | 3260 | 1T x 1.5 sqmm | 3260 | 3030 | RM |
327 | 3270 | Laying, glanding, ferruling and termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. | 3270 | 100 | RM |
328 | 3280 | Laying, glanding, ferruling and termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. | 3280 | 1000 | RM |
329 | 3290 | Laying, glanding, ferruling and termination of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. | 3290 | ||
330 | 3300 | 10 m | 3300 | 50 | EA |
331 | 3310 | 15 m | 3310 | 50 | EA |
332 | 3320 | 20 m | 3320 | 20 | EA |
333 | 3330 | 25 m | 3330 | 25 | EA |
334 | 3340 | 30 m | 3340 | 30 | EA |
335 | 3350 | Laying, glanding, ferruling and termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document | 3350 | 3000 | RM |
336 | 3360 | Laying, jointing, connection, testing and commissioning of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | 3360 | 500 | RM |
337 | 3370 | Laying, jointing, connection, testing and commissioning of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | 3370 | 500 | RM |
338 | 3380 | Laying, jointing, connection, testing and commissioning of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. | 3380 | ||
339 | 3390 | 50 mm | 3390 | 4000 | RM |
340 | 3400 | 100 mm | 3400 | 2500 | RM |
341 | 3410 | 150 mm | 3410 | 2500 | RM |
342 | 3420 | 300 mm | 3420 | 15000 | RM |
343 | 3430 | 600 mm | 3430 | 100 | RM |
344 | 3440 | Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. | 3440 | ||
345 | 3450 | 24 ways JB | 3450 | 1 | EA |
346 | 3460 | 18 ways JB | 3460 | 23 | EA |
347 | 3470 | 12 ways JB | 3470 | 15 | EA |
348 | 3480 | 8 ways JB | 3480 | 38 | EA |
349 | 3490 | 6 ways JB | 3490 | 18 | EA |
350 | 3500 | 4 ways JB | 3500 | 14 | EA |
351 | 3510 | Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | 3510 | 200 | RM |
352 | 3520 | Earth Pit | 3520 | ||
353 | 3530 | Installation, testing and commisioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) | 3530 | ||
354 | 3540 | Control room | 3540 | 3 | EA |
355 | 3550 | Tank dyke | 3550 | 16 | EA |
356 | 3560 | Pump house ( 2 No. Near Fire Engine P/H) | 3560 | 2 | EA |
357 | 3570 | STRUCTURAL STEEL & CIVIL FOUNDATION | 3570 | ||
358 | 3580 | Design, fabrication, painting & errection of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations s required , nuts, bolts, washers, cleats, stiffners, gussets, base plate etc | 3580 | 75 | TON |
359 | 3590 | SIL VERIFICATION / VALIDATION | 3590 | ||
360 | 3600 | SIL verification from approved third party agencies. (For SIFs as per SIL Assessment study report/detail engg). All required documentation as per specs and other documentation mentioned elsewhere in tender scope has to be submitted. Complete as per specification / tender documents. | 3600 | 1 | LS |
361 | 3610 | Validation of entire Safety System (SIS) for SIFs (for e.g. AOPS -SIF) shall be carried out from approved third party agency prior to trial period. Automation contractor shall bear the responsibility of its co-ordination and logistics. The third party has to submit a detailed report along with certification for SIS which is to be approved by IOCL along with all other required documentation as per specification and tender documents. | 3610 | 1 | LS |
362 | 3620 | Services for Safety Instrumented System testing after installation in presence of safety, operation and engg. Team from user. Demonstration of safety system during pre OISD / OISD & statutory audits & there after periodic testing. Complete as per specifications / tender documents. | 3620 | 1 | EA |
363 | 3630 | OTHER SERVICES | 3630 | ||
364 | 3640 | Providing training to IOCL employee as per schedule/Module for 2 days as per tender document | 3640 | 1 | Module |
365 | 3650 | Submission of detailed system design, Engineering, Documentations etc as per tender document | 3650 | 1 | LS |
366 | 3660 | Submission of Final Detailed system design, Engineering, Documentations, as built drawings etc complete as per tender | 3660 | 1 | LS |
367 | 3670 | Resident Engineer support on quarterly basis in case of shift addition during CAMC period | 3670 | 1 | EA |
368 | 3680 | Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per direction of EIC. | 3680 | ||
369 | 3690 | Product tank addition | 3690 | 1 | per tank |
370 | 3700 | Product code change | 3700 | 1 | per product code |
371 | 3710 | Comphrehensive AMC - PART -III | 3710 | ||
372 | 3720 | Comprehensive Annual Maintenance Contract for a period of Seven years for entire Terminal Automation System after successful completion of SAT as described in Technical Bid. \nCost of all the required spares, hardwares, software modification, tools and tackles, ladders, labours, Preventive & Breakdown maintenance Service, calibration of instruments, proving & stampings of metering equipments, rectification/ replacement of faulty TAS equipment etc required for running and maintenance of the entire Terminal Automation System to the desired performance level throughout the contract period of CAMC is included in the item rates and the same has to be borne by the Vendor. \nThe scope also includes posting of Resident Engineer (s) to take care of running and maintenance of the entire Automation System complete as per the tender document. | 3720 | ||
373 | 3730 | First Year @4% of the basic CAPEX cost | 3730 | 1 | LS |
374 | 3740 | Second Year @4% of the basic CAPEX cost | 3740 | 1 | LS |
375 | 3750 | Third Year @7% of the basic CAPEX cost | 3750 | 1 | LS |
376 | 3760 | Fourth Year @7% of the basic CAPEX cost | 3760 | 1 | LS |
377 | 3770 | Fifth Year @10% of the basic CAPEX cost | 3770 | 1 | LS |
378 | 3780 | Sixth Year @6% of the basic CAPEX cost | 3780 | 1 | LS |
379 | 3790 | Seventh Year @12% of the basic CAPEX cost | 3790 | 1 | LS |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy