Supply, Installation, Testing And Commissioning Of Electromechanical Equipment And Other Allied Works At Delhi Jal Board Office Building Andrews Ganj., EXECUTIVE ENGINEER (EM) WS SOUTH-I-Delhi

Delhi Jal Board-DJB has published Supply, Installation, Testing And Commissioning Of Electromechanical Equipment And Other Allied Works At Delhi Jal Board Office Building Andrews Ganj.. Submission Date for this Tender is 22-08-2019. Electromechanical Machinery Tenders in EXECUTIVE ENGINEER (EM) WS SOUTH-I Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

21413482
Supply, Installation, Testing And Commissioning Of Electromechanical Equipment And Other Allied Works At Delhi Jal Board Office Building Andrews Ganj.
Open Tender
Indian
Delhi
EXECUTIVE ENGINEER (EM) WS SOUTH-I
22-08-2019

Tender Details

Supply, Installation, Testing And Commissioning Of Electromechanical Equipment And Other Allied Works At Delhi Jal Board Office Building Andrews Ganj.

Key Value

Document Fees
INR 500 /-
EMD
INR 18700.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: S/I/T/C of E/M equipment and other allied works at Delhi Jal Board Office Building Andrews Ganj.
Sl. No. Item Description Item Code / Make Quantity Units
1 1.01 Supply of 5HP (3.7KW) 3000 RPM Mono block Pump set with CI impeller, C 40 Shaft, Gland Packing sealing, CI casing having following duty point: Head 15-30 Mtr, Discharge: 825-250 LPS, Suitable size for 65 X 50 mm for operation on 3 phase 415V, 50Hz AC supply. \nMake:- M&P/KIRLOSKAR/Any DJB Approved Make\n item1 3 Nos.
2 2 Supply of MS Base Frame required for mono block pump set. item2 3 Nos.
3 2.99 Supply of M.S pipe of size 65 mm dia heavy duty as per IS: 1239. Make – Jindal/Tata item3 24 Mtr.
4 3.98 Supply of M.S pipe of size 40 mm dia heavy duties as per IS: 1239. Make – Jindal/Tata item4 10 Mtr.
5 4.97 Supply of M.S Reducer of size 50 X 40 mm dia item5 3 Nos.
6 5.96 Supply of M.S bend of size 40mm item6 3 Nos.
7 6.95 Supply of M.S Gap Piece of size 65 mm item7 3 Nos.
8 7.94 Supply of M.S Reducer of size 65MM item8 3 Nos.
9 8.93 Supply of M.S Flange of size 65 mm x12mm thickness. item9 12 Nos.
10 9.92 Supply of M.S Flange of size 50 mm x12mm thickness. item10 6 Nos.
11 10.91 Supply of M.S Flange of size 40 mm x12mm thickness. item11 12 Nos.
12 11.9 Supply of Pressure Gauge of rating 0-60 PSI with complete fittings item12 3 Nos.
13 12.89 Supply of flanged type non-rising sluice valve of size 65 mm with design std. IS 14846 PN 1.0 having CI body, dome, wedge confirming to IS:210 Gr. FG 260 & bronze wedge rings, SS spindle, gland packing, greasy jute, packing fasteners and natural rubber gasket .Make- Kirloskar/IVC item13 3 Nos.
14 13.88 Supply of flanged type non-rising sluice valve of size 50mm with design std. IS 14846 PN 1.0 having CI body, dome, wedge confirming to IS:210 Gr. FG 260 & bronze wedge rings, SS spindle, gland packing, greasy jute, packing fasteners and natural rubber gasket. Make- Kirloskar/IVC item14 3 Nos.
15 14.87 Supply of flanged type swing check non-return valve of size 50 mm with design std. IS 5312 part I PN 1.0 having CI body, cover, door, confirming to IS:210 Gr. FG 260 & bronze body ring, natural rubber door face, SS hinge pin, fasteners and natural rubber gasket. Make- Kirloskar/IVC item15 3 Nos.
16 15.86 Supply of synthetic rubber sheet 50% synthetic item16 20 Kg.
17 16.85 Making of RCC foundation of size 1.5 mtr X1mtr X0.9m by 1:2:4 concrete including providing fixing of 3 nos. foundation bolt of size 20mm X600mm item17 3 Jobs.
18 17.84 Installation and commissioning the pump set as per original position with proper alignment and also making of all electrical connections, fitting all valves, bends etc. Fixing of65 mm and 40mm dia M.S. Pipe having, along with Non Return Valves, Sluice Valves ,Pipes and Flange welding, with the help of all labour like Fitter, Welder Cutter ,Helper ,Beldar ,Electrician, and Supervisor etc. and material like Welding machine ,Cutter Set ,Oxygen Cylinder, Nut Bolt ,Pecking Sheet ,welding rods and T&P etc.. item18 3 Jobs.
19 18.83 Providing and fixing of 4.5 Kg. Carbon-dioxide fire extinguishers complete with delivery hose horn, squeeze grip release valve, locking arrangement, operation manual and bracket as per IS 15683 ISI marked duly filled with initial gas charging complete with suitable wall mounted brackets etc. as required fixing on existing wall with grouting of fasner etc. Make- Life Guard/Cease fire/Any DJB Approved Make item19 12 Nos.
20 19.82 Providing and fixing of 9 Kg. ABC Store pressure type Fire Extinguisher squeeze grip release valve discharge pipe locking arrangement pressure gauge, operation manual and bracket conforming to IS: 15683:2006 duly charged with ISI Marked Mono ABC powder complete in all respect etc. as required. existing wall with grouting of fasner etc. Make- Life Guard/Cease fire/Any DJB Approved Make item20 12 Nos.
21 20.81 Providing and Fixing Fire Bucket Stand suitable for 4 buckets. Branded for good quality. item21 6 Nos.
22 21.8 Providing and Fixing of water cooler 80 Ltr storage capacities double taps stainless steel body, stainless steel tank. Make- Blue Star/ Voltas/ Any DJB Approved Make item22 4 Nos.
23 22.79 LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1600MM x1800x375MM. Having following components of approved make. item23 1 Nos.
24 23.78 MCCB 415V, TP 3phase 50Hz,100Amp with handle & Spreader - Make L&T/siemens item24 1 Nos.
25 24.77 MCCB 415V, TP 3phase 50Hz,25-32Amp - Make L&T item25 4 Nos.
26 25.76 MCB Single pole 6Amp. Make L&T/Havells item26 12 Nos.
27 26.75 MCB Triple pole 32Amp. Make L&T/Havells item27 4 Nos.
28 27.74 Power capacitors 415V unit of 5Kvar Make: Epcos item28 3 Nos.
29 28.73 Power capacitors 415V unit of 3Kvar Make: Epcos item29 3 Nos.
30 29.72 Over load relay 6-10Make: L&T/siemens item30 3 Nos.
31 30.71 Over load relay 9Amp. -15Amp Make: L&T/siemens item31 3 Nos.
32 31.7 Digital Amp. Meter Make AE/L&T item32 4 Nos.
33 32.69 Digital Volt Meter0-500V -Make AE/L&T item33 1 Nos.
34 33.68 Motor protection Relay Make: L&T/Siemens item34 3 Nos.
35 34.67 Power contactor 220V 3phase32Amp. Make L&T/siemens item35 6 Nos.
36 35.66 Power contactor 220V 3phase25Amp. Make L&T/siemens item36 3 Nos.
37 36.65 Star delta timer on delay make: L&T/Siemens item37 3 Nos.
38 37.64 Indicating lights LED type RYB & On/OFF Make : L&T /Havells item38 15 Nos.
39 38.63 Current Transformer200/5,30/5Make AE /Saviour item39 12 Nos.
40 39.62 Fitting of the above components in panel enclosure S. No: 24 to 39 with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard wares complete in all respect. Loading ,unloading by crane or heavy labor and cartage up to site Dismantling of old panel structure including removing of cable etc. from site ,cleaning & dressing the surface for Installation of the panel at site on base frame ,laying of cable ,termination of cable both incoming & out going side item40 1 Jobs.
41 40.61 Installation of the panel at site, matching of bus bars ,links, bends, re-dressing of existing cable at site ,termination of cable both incoming & out going side through cable gland & thimble item41 1 Jobs.
42 41.6 PVC insulated copper flexible cable single core 16 sq.mm. Make: Havells/Finolex/ any DJB Approved make. item42 200 Mtr.
43 42.59 Internal wiring with copper wire as per CPWD specification for light power & plug points in recess/surface/main distribution board for pump house having 4 nos light points. Fans point and 2 nos. power points-2 nos. for shifting old exiting lighting feature from Andrews ganj building item43 1 Jobs.
44 43.58 loading, unloading by crane & heavy labour & cartage up to site item44 1 Jobs.
45 44.57 Testing & commissioning of pump set , panel and allied accessories as per required parameters with relevant IS .testing of the panel prior to switching on as follow \nA) Continuity and earth testing \nB) Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. \nC) checking for all tightness of nut and bolts \nD) Alignments of doors etc. \nE) Interlocking tests. \nF) All function tests\nG) Testing on load with engineer in charge\n item45 1 Jobs.