| 1 | 1 | Taking out of LT panel/Feeder Pillar box Including all fittings completed from the site completed as per directed by Engr-in-Charge. | BI01010001010000000000000515BI0100001112 | 6 | Each |
|---|
| 2 | 2 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 1200 amps (03 Nos 1200 Amps for Phase and 01 No 600 Amps for neutral) rated aluminium bus bar for neutral complete with Cable Gland and fixing arrangement all as specified and directed. Location : GC power House Transformer 630KVA\nNote : MCCB will be measured and paid separately against respective item of the schedule. | | 2 | Each |
|---|
| 3 | 2.01 | (a) Incoming | | | |
|---|
| 4 | 2.02 | (i) MCCB 04 Pole 50 kA, 800 Amp,415 Volts (Qty 01 No)\n | | | |
|---|
| 5 | 2.03 | (b) Out goings | | | |
|---|
| 6 | 2.04 | (i) MCCB 04 Pole 25 KA, 250 Amp, 415 Volts, (Qty - 06 Nos)\n | | | |
|---|
| 7 | 2.05 | (ii) Aluminium bus bar suitable size 3 phase, 4 wire 1200 Amp,415 V | | | |
|---|
| 8 | 2.06 | (iii) Digital Volt meter 0-500V with slector switch, make-AE/L&T | | | |
|---|
| 9 | 2.07 | (iv) Digital Amp meter 0-1000 amp with CT and selector switch. make-AE/L&T | | | |
|---|
| 10 | 2.08 | (v) Indicating lamp (Blue, Yellow &Red-1 set)LED Type make-AE/L&T/ Havells | | | |
|---|
| 11 | 3 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Indoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 2.00 mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 1200 amps (03 Nos 1200 Amps for Phase and 01 No 600 Amps for neutral) rated aluminium bus bar for neutral complete with Cable Gland and fixing arrangement all as specified and directed. \nLocation -CSD canteen Transformer 630 KVA\nNote : MCCB will be measured and paid separately against respective item of the schedule. | | 2 | Each |
|---|
| 12 | 3.01 | (a) Incoming | | | |
|---|
| 13 | 3.02 | (i) MCCB 04 Pole 50 kA, 800 Amp,415 Volts (Qty 01 No)\n | | | |
|---|
| 14 | 3.03 | (b) Out goings | | | |
|---|
| 15 | 3.04 | (i) MCCB 04 Pole 36 KA, 630 Amp, 415 Volts, (Qty - 01 No)\n | | | |
|---|
| 16 | 3.05 | (ii) MCCB 04 Pole 36 KA, 400 Amp, 415 Volts, (Qty - 01 No)\n | | | |
|---|
| 17 | 3.06 | (iii) MCCB 04 Pole 25 KA, 200 Amp, 415 Volts, (Qty - 02 Nos)\n | | | |
|---|
| 18 | 3.07 | (iv) Aluminium bus bar suitable size 3 phase, 4 wire 1200 Amp,415 V | | | |
|---|
| 19 | 3.08 | (v) Digital Volt meter 0-500V with slector switch, make-AE/L&T | | | |
|---|
| 20 | 3.09 | (vi) Digital Amp meter 0-500 amp with CT and selector switch. make-AE/L&T | | | |
|---|
| 21 | 3.1 | (vii) Indicating lamp (Blue, Yellow &Red-1 set)LED Type make-AE/L&T/ Havells | | | |
|---|
| 22 | 3.11 | (viii) Indicating lamp (Blue, Yellow &Red-1 set)LED Type make-AE/L&T/ Havells | | | |
|---|
| 23 | 4 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mm x 4mm angle iron frame and 3 .15 mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 1200 amps (03 Nos 1200 Amps for Phase and 01 No 600 Amps for neutral) rated aluminium bus bar for neutral complete with Cable Gland and fixing arrangement all as specified and directed. (Location -Rajvardan Stadium)\nNote : MCCB will be measured and paid separately against respective item of the schedule. | | 1 | Each |
|---|
| 24 | 4.01 | (a) Incoming | | | |
|---|
| 25 | 4.02 | (i) MCCB 04 Pole 50 kA, 400 Amp,415 Volts (Qty 01 No)\n | | | |
|---|
| 26 | 4.03 | (b) Out goings | | | |
|---|
| 27 | 4.04 | (i) MCCB 04 Pole 25 KA, 200 Amp, 415 Volts, (Qty - 03 Nos)\n | | | |
|---|
| 28 | 4.05 | (ii) MCCB 04 Pole 25 KA, 160 Amp, 415 Volts, (Qty - 01 No)\n | | | |
|---|
| 29 | 4.06 | (iii) Aluminium bus bar suitable size 3 phase, 4 wire 1200 Amp,415 V | | | |
|---|
| 30 | 4.07 | (iv) Digital Volt meter 0-500V with slector switch, make-AE/L&T | | | |
|---|
| 31 | 4.08 | (v) Digital Amp meter 0-500 amp with CT and selector switch. make-AE/L&T | | | |
|---|
| 32 | 4.09 | (vi) Indicating lamp (Blue, Yellow &Red-1 set)LED Type make-AE/L&T/ Havells | | | |
|---|
| 33 | 5 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mm x 4mm angle iron frame and 3 .15 mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 1200 amps (03 Nos 1200 Amps for Phase and 01 No 600 Amps for neutral) rated aluminium bus bar for neutral complete with Cable Gland and fixing arrangement all as specified and directed. (Location -RMA Qtr & Demo Area)\nNote : MCCB will be measured and paid separately against respective item of the schedule. | | 1 | Each |
|---|
| 34 | 5.01 | (a) Incoming | | | |
|---|
| 35 | 5.02 | (i) MCCB 04 Pole 50 kA, 400 Amp,415 Volts (Qty 01 No)\n | | | |
|---|
| 36 | 5.03 | (b) Out goings | | | |
|---|
| 37 | 5.04 | (i) MCCB 04 Pole 36 KA, 315 Amp, 415 Volts, (Qty - 01 No)\n | | | |
|---|
| 38 | 5.05 | (ii) MCCB 04 Pole 36 KA, 250 Amp, 415 Volts, (Qty - 02 Nos)\n | | | |
|---|
| 39 | 5.06 | (iii) MCCB 04 Pole 36 KA, 200 Amp, 415 Volts, (Qty - 01 Nos)\n | | | |
|---|
| 40 | 5.07 | (iv) Aluminium bus bar suitable size 3 phase, 4 wire 1200 Amp,415 V | | | |
|---|
| 41 | 5.08 | (v) Digital Volt meter 0-500V with slector switch, make-AE/L&T | | | |
|---|
| 42 | 5.09 | (vi) Digital Amp meter 0-500 amp with CT and selector switch. make-AE/L&T | | | |
|---|
| 43 | 5.1 | (vii) Indicating lamp (Blue, Yellow &Red-1 set)LED Type make-AE/L&T/ Havells | | | |
|---|
| 44 | 6 | supply ,installation,commisioning and testing LT Feeder piller box outdoor type double door and single shutter from open including locking arrangement system made out of MS sheet of 3.00 mm CRCA sheet 0.6x0.6x0.3 Mtr and double door,canopy dust proof,bottom cable entry plate and gland for cable size 95/70/50/35/25/16/10 Sqmm 3.5 core suitable MS angle iron 40x40x5 mm with alluminium busbar rating capacity 500 Amps (03 Nos 500 Amps for phase & 01 No 250 Amps for neutral) system mounted on hygroscopic insulators bus bar connected with MCCB 04 Pole 25 KA 250 Amps,415 volt(as incomer) including fixing arrangement complete all as specified and directed. | | 1 | Each |
|---|
| 45 | 7 | Supply & fixing of MCCB 04 Pole 50 KA 800 Amps, AC 415 Volts \"C Frame adjustable thermal & adjustable Magnetic setting (Ics = 50% of Icu) complete all as specified and directed \nMake : Havells Cat Part No IHLCHF0800 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Incommer) | | 4 | Each |
|---|
| 46 | 8 | Supply & fixing of MCCB 04 Pole 50 KA 400 Amps, AC 415 Volts \"C Frame adjustable thermal & adjustable Magnetic setting (Ics = 50% of Icu) complete all as specified and directed \nMake :Havells Cat Part No IHLCHF0400 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Incommer) | | 2 | Each |
|---|
| 47 | 9 | Supply & fixing of MCCB 04 Pole 35 KA 630 Amps, AC 415 Volts \"C Frame adjustable thermal & adjustable Magnetic setting (Ics = 75% of Icu) complete all as specified and directed \nMake :Havells Cat Part No IHLCHF0630 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Outgoing) | | 2 | Each |
|---|
| 48 | 10 | Supply & fixing of MCCB 04 Pole 35 KA 400 Amps, AC 415 Volts \"C Frame adjustable thermal & adjustable Magnetic setting (Ics = 75% of Icu) complete all as specified and directed \nMake Havells Cat Part No IHLCHF0400 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Outgoing) | | 2 | Each |
|---|
| 49 | 11 | Supply & fixing of MCCB 04 Pole 35 KA 315 Amps, AC 415 Volts \"C Frame adjustable thermal & adjustable Magnetic setting (Ics = 75% of Icu) complete all as specified and directed \nMake Havells Cat Part No IHLCHF0315 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Outgoing) | | 1 | Each |
|---|
| 50 | 12 | Supply & fixing of MCCB 04 Pole 25 KA 250 Amps, AC 415 Volts \"a Frame adjustable thermal & adjustable Magnetic setting (Ics = 75% of Icu) complete all as specified and directed \nMake Havells Cat Part No IHLANDCF0250 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Outgoing) | | 14 | Each |
|---|
| 51 | 13 | Supply & fixing of MCCB 04 Pole 25 KA 200 Amps, AC 415 Volts \"a Frame adjustable thermal & adjustable Magnetic setting (Ics = 75% of Icu) complete all as specified and directed \nMake Havells Cat Part No IHLANDCF0200 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Outgoing) | | 8 | Each |
|---|
| 52 | 14 | Supply & fixing of MCCB 04 Pole 25 KA 160 Amps, AC 415 Volts \"a Frame adjustable thermal & adjustable Magnetic setting (Ics = 75% of Icu) complete all as specified and directed \nMake Havells Cat Part No IHLANDCF0160 and HPL/L&T Lexic/Legrand/C&S Electric Ltd /ABB/equivalent specification of made.\n(As Outgoing) | | 1 | Each |
|---|
| 53 | 15 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm X 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt around earth plate, PCC 1:3:6 type C-1 using 20mm graded stone aggregate for earth pit with pre cast RCC (1:2:4) type B-1 using 20mm graded stone aggregate 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed. | | 14 | Each Set |
|---|
| 54 | 16 | Supply and laying in trenches/laid in floor/duct/drawn through conduit XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100 Volts grade with aluminum conductor of cross sectional area 120 Sqmm, 3.5 Core complete all as specified and directed | | 75 | RM |
|---|
| 55 | 17 | All as per Item No 16 but of size 95 Sqmm, 3.5 Core | | 90 | RM |
|---|
| 56 | 18 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m deep and getting out in soft/loose soil complete all as specified and directed | | 15 | Cum |
|---|
| 57 | 19 | Returning, filling in, incfluding spreading, watering and well ramming in layers not exc 25 cm in soft/loose soil | | 9 | Cum |
|---|
| 58 | 20 | Removing suplus soil to a distance not exc 50m and depositing where directed at a level not exc 1.5 m above the starting point | | 6 | Cum |
|---|
| 59 | 21 | Material and labour for sand cushioning for under ground cable with locally available sand for protection of cable including spreading and consolidations complete all as specified and directed | | 4.5 | Cum |
|---|
| 60 | 22 | Supply and laying in trenches dry well burnt locally available sub Class \"B\" bricks over sand cushioning for pretection of cable complete all as specified and directed | | 0.45 | Per 1000 Nos |
|---|
| 61 | 23 | Supply & fixing in replacement of light grade, 50 mm dia GI tubing with all fittings fixed on walls/ poles/ in trenches as in earth lead protection pipe all as specified & directed . | | 20 | RM |
|---|
| 62 | 24 | Material and Labour Boring under road/foot path for inserting of 80 mm dia/50mm dia GI tubing for drawing UG cable with proper finishing complete all as specified and directed | | 20 | RM |
|---|