Rajasthan State Road Development And Construction Corporation Limited has published Electrification Work Including Transformer And Sub Station Work Of Boys And Girls Hostel At Govind Guru Tribal University , Banswara . . Submission Date for this Tender is 23-08-2019. Electrification Work Tenders in Govind Guru Tribal University, Banswara. Rajasthan. Bidders can get complete Tender details and download the document.
Name of Work : -Electrification Work including Transformer and sub Station work of Boys and Girls Hostel at Govind Guru Tribal University, Banswara. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1.01 | (Part 'A' Electrification work Boy's and Girl's hostel) | 0.0001 | P.Cum | |
2 | 1.02 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles, Hot Dipped Galvanized Modular Box of 20 SWG with earth terminal, 6 A Modular switch,Modular plate with grid plate, screws, making connections, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
3 | 1.03 | Short point (up to 3 mtr.) | 600 | P. point | |
4 | 1.04 | Medium point (up to 6 mtr.) | 800 | P. point | |
5 | 1.05 | Long point (up to 10 mtr..) | 390 | P. point | |
6 | 1.06 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles, Hot Dipped Galvanized Modular Box of 20 SWG with earth terminal 6 A two way Modular switch, Modular plate with grid plate, screws, making connections, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
7 | 1.07 | Long point (up to 10 mtr..) | 12 | P. point | |
8 | 1.08 | Wiring of 3 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles, Hot Dipped Galvanized Modular Box of 20 SWG with earth terminal 6 A modular switch, 6 A modular socket, Modular plate with grid plate, screws, making connections, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
9 | 1.09 | On board | 320 | P. point | |
10 | 1.1 | Short point (up to 3 mtr.) | 390 | P. point | |
11 | 1.11 | Medium point (up to 6 mtr.) | 200 | P. point | |
12 | 1.12 | Long point (up to 10 mtr..) | 130 | P. point | |
13 | 1.13 | S&F following sizes (dia.) of ISI marked medium duty PVC conduit along with accessories in surface / recessed using saddles, clamps, fastener as required. Group-1 including cutting the wall, covering conduit and making good the same as required. Group-1. | 0.0001 | P.Cum | |
14 | 1.14 | 20 mm | 3200 | Mtr. | |
15 | 1.15 | 25 mm | 4400 | Mtr. | |
16 | 1.16 | 32 mm | 800 | Mtr. | |
17 | 1.17 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required. Group-1. | 0.0001 | P.Cum | |
18 | 1.18 | 2 x 1.5 sq.mm | 3000 | Mtr. | |
19 | 1.19 | 2 x 2.5 sq. mm. + 1x1.5sqmm | 6000 | Mtr. | |
20 | 1.2 | 1 x 4.0 sq.mm | 800 | Mtr. | |
21 | 1.21 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. | 4000 | Mtr. | |
22 | 1.22 | 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. | 560 | Mtr. | |
23 | 1.23 | 1 x 16.0 sq.mm | 800 | Mtr. | |
24 | 1.24 | 2 x 10.0 sq.mm | 600 | Mtr. | |
25 | 1.25 | Supplying and drawing PVC jacketed with annealed bare copper inner conductor & tinned copper conductor shielding foam PE dielectric coaxial cable of approved make in existing surface or recessed conduit/casing capping including making connections as required. Group-1. | 0.0001 | P.Cum | |
26 | 1.26 | RG - 6 | 100 | Mtr. | |
27 | 1.27 | Supplying and fixing of power plug point Modular accessories on hot dipped galvanized modular on surface or in recessed with suitable size of grid plate with cover plate including cost of modular 16 amp. Switch and socket outlet , making connection , testing , etc. as required. Group-1. | 40 | Each | |
28 | 1.28 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required. Group-2. | 0.0001 | P.Cum | |
29 | 1.29 | 2.5 Sq.mm 3 core flat / Round | 450 | Mtr. | |
30 | 1.3 | 6.0 Sq.mm 3 core flat / Round | 300 | Mtr. | |
31 | 1.31 | P & F 18 SWG Sheet steel boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) on surface or in recessed as required. Group-1. | 0.0001 | P.Cum | |
32 | 1.32 | 175mm x 100mm x 60mm | 30 | Each | |
33 | 1.33 | 200mm x 150mm x 60mm | 20 | Each | |
34 | 1.34 | 200mm x 250mm x 75mm | 20 | Each | |
35 | 1.35 | P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and enamel paint including cutting, welding, holes etc.of following sizes as required. Group-1. | 0.0001 | P.Cum | |
36 | 1.36 | 35mm x 35mm x 5mm | 6 | Mtr. | |
37 | 1.37 | P & Fixing M.S. sheet on existing angle iron frame by means of nuts and bolts and making required no. of holes for fixing accessories including two coat of red oxide paint and two coats of enamel paint etc. as required. Group-1. | 0.0001 | P.Cum | |
38 | 1.38 | 1.6 mm thick | 3 | Sqm. | |
39 | 1.39 | P & Fixing M.S. flat on existing angle iron frame and making required no. of holes for fixing accessories including one coat of red oxide paint and two coats of enamel paint etc. as required. Group-1. | 0.0001 | P.Cum | |
40 | 1.4 | 38 mm x 5 mm | 12 | Mtr. | |
41 | 1.41 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. Group-2. | 0.0001 | P.Cum | |
42 | 1.42 | 3.0 mm thick | 2 | Sqm. | |
43 | 1.43 | 6.4 mm thick | 12 | Sqm. | |
44 | 1.44 | P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
45 | 1.45 | Single pole MCB 6 A to 32 A rating | 288 | Each | |
46 | 1.46 | Four pole MCB 40 A 63 A rating | 24 | Each | |
47 | 1.47 | P&F Recessed/ Surface mounting heavy duty horizontal type sheet steel Distribution board phophatised/ powder painted complete with suitable rating insulated copper bus bar, shorting link , neutral link, earth link and din bar,masking sheet, conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required. Group-1. | 0.0001 | P.Cum | |
48 | 1.48 | 8 Way Double door (Three phase) | 14 | Each | |
49 | 1.49 | P&F 240/415 V Residual current circuit breaker conforming to IS:12640:1988/ IEC 61008 on existing board/sheet including making connections, testing etc. as required (ii) 40Amps. DP | 12 | Each | |
50 | 1.5 | P & F ISI marked 6 amp bakelite batten/angle holder including making connection testing etc. as required. Group-1. | 120 | Each | |
51 | 1.51 | P & F ISI marked single tone electronic call bell including making connection testing etc. as required. Group-1. | 2 | Each | |
52 | 1.52 | P & F following modular accessories made out of unbreakable and fire retardant poly carbonate with silver contacts including making connections testing etc. as required. Group-1 | 0.0001 | P.Cum | |
53 | 1.53 | RJ-11 telephone jack double two line | 8 | Each | |
54 | 1.54 | T.V. coaxial socket | 4 | Each | |
55 | 1.55 | 5 step fan regulator 2 Module | 280 | Each | |
56 | 1.56 | Blanking plate | 100 | Each | |
57 | 1.57 | RJ-45 computer jack with shutter | 6 | Each | |
58 | 1.58 | Supply , Drawing and Testing of 4 pair, 24 AWG UTP Cat 6 Cable as per latest ammendments of TIA /EIA 568 B.2-1 Specifications in existing MS/PVC Conduits including making connections to Information outlets and Patch Panels with ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing required | 1200 | mtr | |
59 | 1.59 | SITC of wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors with / without detachable extension type structure. (only outer area on all sides shall be measured & panel to be fabricated from CPRI approved fabricator). Interconnection between bus bar and switchgears / cable shall be rigidly supported and made out by flexible copper wires (up to 125 amp ) and by solid bus bar (>125 amp ). All joints / interconnections of copper bus bar shall be dully tinned. Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves. Earth and Neutral bus bar shall be half of the size of phase bus bar. | 35 | Sqm. | |
60 | 1.6 | Supplying and fixing of Aluminium / Copper bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. | 0.0001 | P.Cum | |
61 | 1.61 | Electrolytic grade Aluminium bus bar | 20 | Kg. | |
62 | 1.62 | SF of (0-500) V range Volt meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Group-1. | 0.0001 | P.Cum | |
63 | 1.63 | Digital type | 3 | Each | |
64 | 1.64 | SF of CT operated direct reading type Ampere meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Group-1. | 0.0001 | P.Cum | |
65 | 1.65 | Digital type | 0.0001 | P.Cum | |
66 | 1.66 | Below 500 A | 3 | Each | |
67 | 1.67 | SF of Current Transformer , with all necessary support in existing panel including connection etc. as required. Group-1 . | 0.0001 | P.Cum | |
68 | 1.68 | from 200 / 5 to 400/5 Ratio , 10 VA , class 1 accuracy | 9 | Each | |
69 | 1.69 | SF of selector switch of 10 A for voltmeter (4 position ) including making connection etc. as required. Group-1 . | 3 | Each | |
70 | 1.7 | SF of CT linked selector switch of 10 A for Ampere meter (4 position ) including making connection etc. as required. Group-1 . | 3 | Each | |
71 | 1.71 | SF of 110/220 V, LED (22.5 mm dia ) Indicating lamp with integral circuit, terminal block, including connection etc. as required. Group-1. | 0.0001 | P.Cum | |
72 | 1.72 | Red/yellow/Green colour | 9 | Each | |
73 | 1.73 | SITC of quick make and quick break 4 POLE current limiting MCCB having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with front face and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip ,earth fault trip, push ( test ) to trip , including making connections with lugs & spreaders, etc. as required. Group-1. | 0.0001 | P.Cum | |
74 | 1.74 | With Thermal Magnetic release | 0.0001 | P.Cum | |
75 | 1.75 | up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 18 | Each | |
76 | 1.76 | 400 Amp ,35 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu | 2 | Each | |
77 | 1.77 | 250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 8 | Each | |
78 | 1.78 | P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required. | 0.0001 | P.Cum | |
79 | 1.79 | 40 A 63 A rating | 12 | Each | |
80 | 1.8 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required. Group-1 of size. | 0.0001 | P.Cum | |
81 | 1.81 | 240.0 Sq.mm | 0.0001 | P.Cum | |
82 | 1.82 | 3.5 core | 350 | Mtr. | |
83 | 1.83 | 10.0 Sq.mm | 0.0001 | P.Cum | |
84 | 1.84 | 4 core | 390 | Mtr. | |
85 | 1.85 | 150.0 Sq.mm | 0.0001 | P.Cum | |
86 | 1.86 | 3.5 core | 580 | Mtr. | |
87 | 1.87 | Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty aluminium lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. Group-1 of size. | 0.0001 | P.Cum | |
88 | 1.88 | 3.5 x 240.0 sq.mm | 12 | Set | |
89 | 1.89 | 4 x 10.0 sq.mm | 12 | Set | |
90 | 1.9 | 3.5 x 150.0 sq.mm | 16 | Set | |
91 | 1.91 | Maintenance free Gel Earthing with Pipe in pipe / Pipe in strip technology filled with anti corrosive conductive compound ( CPRI Tested ) below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineral filling compound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone ) and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. of following sizes. | 0.0001 | P.Cum | |
92 | 1.92 | With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating | 0.0001 | P.Cum | |
93 | 1.93 | GI pipe 2000 mm long, 50 / 25mm, Terminal 12 mm GI Strip | 12 | Set | |
94 | 1.94 | S & Laying following size earth wire / strip in horizontal or vertical run in ground / surface / recess including riveting, soldering, saddles, making connection etc. as required. Group-1. | 0.0001 | P.Cum | |
95 | 1.95 | 25mm x 3mm G.I. ( Hot Dipped ) Strip | 250 | Mtr. | |
96 | 1.96 | S & Laying following size' B ' class G.I. Pipe confirming to IS : 1239 P - 1 ( 1990 ) with accessories for laying earth conductor/strip / cable in ground/surface/recess as required. Group-1 | 0.0001 | P.Cum | |
97 | 1.97 | 50 mm dia. | 20 | Mtr. | |
98 | 1.98 | 100 mm dia. | 20 | Mtr. | |
99 | 1.99 | Making of hole in wall of required size for housing exhaust fan and making good the same, with cement plaster as required. Group-1 of following size: | 0.0001 | P.Cum | |
100 | 2 | Up to 457 mm size | 4 | Each | |
101 | 2.01 | P & F 1200 mm sweep BEE 5 star rated double ball bearing capacitor start , aluminium body & blade ceiling fan complying to IS 374:1979, 1/p 50 watt at max speed & 230 volt , air delivery >210 CMM, speed >330 RPM with down rod upto 30 cm with 3 x 1.5 sqmm pvc insulated flexible copper conductor making connection testing etc as required. | 280 | Each | |
102 | 2.02 | P & F 18 SWG M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . | 280 | Each | |
103 | 2.03 | P&F of Double ball bearing, capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible copper conductor ,making connections, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
104 | 2.04 | 300 mm sweep | 18 | Each | |
105 | 2.05 | P & F of Gravity Louver shutter of superior quality made out of PVC including cost of nuts, bolts, etc as reqd. | 0.0001 | P.Cum | |
106 | 2.06 | Up to 380 mm size | 18 | Each | |
107 | 2.07 | P & F of IP20 surface / recess mounted LED Downlight made of pressure diecast aluminum housing ,with heat sink and good quality reflector , high efficiency external driver , power consumption 14/15 watt system lumen efficacy > 80 lumen / watt . CCT 6000°K(minimum) K , CRI > 80, PF > 0.9, life time 50000 burning hours. Group-1. | 180 | Each | |
108 | 2.08 | P & F of IP20 LED tube light 20 watt with external batten made from CRCA sheet steel suitabe to replace T-8/T-12 tube light, integral driver, 2000 lumen +5 % tolerance system lumen efficiency of 100 Lm / watt minimum expected life time of 25000 burning hours, CCT 5700K, ANSI , CRI 80, driver efficiency >85%, life expectancy of driver min 30000 hours, PF 0.95 at full load / 230 V AC. Group-1. | 450 | Each | |
109 | 2.09 | P&F of IP65 protected LED Street Light fixture 70-75 watt ( with surge protection device 10 KA ) applicable for area lighting with extruded pressure diecast aluminium housing system lumen efficiency of 100 lm / watt minimum, toughened glass with diffuser, suitable lenses on LED, 240 volt, 50 Hz of high power LED lampssupplied with pre-wired cable of 1 mtr. Integrated driver shall be of high efficiency > 85% and in compliance to IEC standards system life of 50,000 burning hours, CRI>80, PF>0.9 at full load, CCT 5700-6500 K (as per directions of Engineer Incharge ). Fixtures shall be of CE compliance. Group-1. | 30 | Each | |
110 | 2.1 | S & F of Street light bracket made out from following size of ' B ' class GI pipe with heavy duty pole clamp, Saddles suitable fastners etc. as required. | 0.0001 | P.Cum | |
111 | 2.11 | 32 mm Dia. | 30 | Mtr. | |
112 | 2.12 | S & F of FR PVC insulated & sheathed 3 core flexible copper conductor ISI marked (IS:694) of 1.1 kV grade of following rating: | 0.0001 | P.Cum | |
113 | 2.13 | 4.0 Sq.mm | 650 | Mtr. | |
114 | 2.14 | SITC of ISI mark( IS:8472) self priming monoblock pump set of approved make, TEFC, permanent split capacitor type (PSC), fitted with thermal overload protection, mechanical seal, 1440/1500 RPM, single phase(180 to 240 V). Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively.Note- All the pumps star rated as per notification of (BEE) ministry of Power, Government of India | 0.0001 | P.Cum | |
115 | 2.15 | 0.5 HP, 1-Ø, (6-28)Mtr, (52-12)LPM | 2 | Each | |
116 | 2.16 | Supply & fixing of GI pipes with flanges duly screwed & welded including rubber washer, nuts & bolts of 8mm dia complete in all respect ISI make. | 0.0001 | P.Cum | |
117 | 2.17 | B class 32mm dia | 64 | mtr | |
118 | 2.18 | Supply and erection of GI Octagonal / Conical pole of following length and dimension as per table E-10 with base plate on the cement concrete foundation of M-20 grade (1:1.5:3) with the help of anchor bolts of grade 6.8 (IS: 1367 P III ). The pole shall have a weatherproof flush door and locking arrangements. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning. | 0.0001 | P.Cum | |
119 | 2.19 | Octagonal MS Poles made of S-355JO grade steel sheet , folded lengthwise to obtained Octagonal shape, having single longitudinal seam weld and hot dipped galvanised internally & externally in accordance with IS 2629. (See Table E - 10 for specs.) | 0.0001 | P.Cum | |
120 | 2.2 | 7 Mtr. | 20 | Each | |
121 | 2.21 | Supply, Erection and Fixing of hot dipped galvanised Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles | 0.0001 | P.Cum | |
122 | 2.22 | Single arm overhang | 20 | Each | |
123 | 2.23 | P / L of Double wall corrugated HDPE pipe confirming to IS : 14930 P - 1 & 2 with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required of Gemini or IS:14930 marked make. Outer Dia. / Inner dia. | 0.0001 | P.Cum | |
124 | 2.24 | 120 / 103.5 mm | 900 | Mtr. | |
125 | 2.25 | 50 / 55 mm | 750 | Mtr. | |
126 | 2.26 | Supply and Installation of Information outlets made of high impact plastic body ABS FR Grade with spring loaded collapsible shutters in jack Recess, suitable for Cat 6 application complying to latest ammendments EIA/ TIA 568 B.2-1 Specifications in existing modular /MS Boxes along with necessory connections as requiredGrpI | 12 | Each | |
127 | 2.27 | Supply & fixing of Faceplate for Flush / Surface Mount Information Outlets Single Aperture with screw hole covers & Icon Tree Size 86mmX86mm | 0.0001 | P.Cum | |
128 | 2.28 | Single Aperture | 12 | Each | |
129 | 2.29 | Supply , Installation and Testing of 4 pair , 100 Ohm, 24 AWG , Cat 6 UTP, flexible , Double ended Patch Cords along with 2 No of RJ 45 connectors with strain relief transparent boots as per TIA /EIA 568 B.2-1 Specifications.GrpI | 0.0001 | P.Cum | |
130 | 2.3 | 2 Mtr / 7 ft | 10 | Each | |
131 | 2.31 | 1 Mtr/3 ft | 10 | Each | |
132 | 2.32 | Supply , Installation, Testing and Comissioning of Wall mounted Communication rack with glass doors, handles ,lock , Top and Bottom Cable entries, Supports for mounting rack on wall , Cable managers, one Fan, Equipment mounting hardware, power supply box for supplying power to switches, fans etc along with earth continuity kit, Mcb, indicator, moulded power supply cable | 0.0001 | P.Cum | |
133 | 2.33 | 6 U(44 mm ) wall mounted | 4 | Each | |
134 | 2.34 | Supply , Installation, Testing and Comissioning of Rack mounted 19", Cat 6 UTP,1.5-1.6 MM CRS chasis , powder coated Modular Patch Panels with collapsible shutters on jacks to support latest ammendments of TIA / EIA Cat 6 Specifications in Existing Communication Rack along with necessary connections of Cat 6 UTP Cables, With Rear Cable management trays and clamps. | 0.0001 | P.Cum | |
135 | 2.35 | 12 Ports | 4 | Each | |
136 | 2.36 | SITC of Managed Layer-2 Intelligent Ethernet Switch providing 24 x 10/100 Fast Ethernet ports and with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software | 4 | Each | |
137 | 2.37 | Supplying and drawing PVC/ Polythene insulated and PVC sheathed unarmoured/ armoured telephone cable with 0.5 mm dia. Tinned / annealed copper conductor taped &confirming to ITD specification S/WS -113C of approved make in existing surface or recessed conduit/casing capping.Grp I | 0.0001 | P.Cum | |
138 | 2.38 | Unarmoured Telephone cable in existing surface or recessed conduit/casing capping. | 0.0001 | P.Cum | |
139 | 2.39 | 2 pair | 1200 | mtr | |
140 | 2.4 | 10 pair | 800 | mtr | |
141 | 2.41 | P&F recessed/ surface mounting heavy duty Vertical type 16 SWG sheet steel Distribution board with provision of incomer suitable for MCCB and SP / TP MCB as outgoing , phophatised ,powder painted complete with insulated suitable rating copper bus bar , neutral link, earth link and din bar, masking sheet & conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required. | 0.0001 | P.Cum | |
142 | 2.42 | Double door with Provision of Incomer MCCB 100 / 125 A Rating | 0.0001 | P.Cum | |
143 | 2.43 | 6 Way | 8 | each | |
144 | 2.44 | SITC of Fixed / Draw out type 3 pole Air Circuit Breaker conforming to IS 60947 P - 2 in existing LT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, earth fault and microprocessor based release with separate LED indication for each type of fault ,LCD display , Thermal memory at least 4NO & 4NC auxiliary contacts safety shutter and fault position acknowledgement mechanism . type ACB shall have separate indication for service, test, isolation, maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , Uimp - 12 KV, including making connections etc. as required. | 0.0001 | P.Cum | |
145 | 2.45 | Draw out type (Manual spring charged) | 0.0001 | P.Cum | |
146 | 2.46 | 630 A Rating , 50kA | 1 | Each | |
147 | 2.47 | 800 A Rating , 50kA | 1 | Each | |
148 | 2.48 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/joint kit of Group1 and approved make suitable for XLPE insulated 11 KV / 33 KV cable, with required components, prepration of cable ends,testing etc. as required of following sizes . | 0.0001 | P.Cum | |
149 | 2.49 | 11 KV End Termination Kit Indoor type | 0.0001 | P.Cum | |
150 | 2.5 | 3 core 70/95 Sq.mm | 8 | Each | |
151 | 2.51 | 11 KV End Termination Kit Outdoor type | 0.0001 | P.Cum | |
152 | 2.52 | 3 core 120/150/185/225 Sq.mm | 8 | Each | |
153 | 2.53 | Part 'B' Sub station Work | 0.0001 | P.Cum | |
154 | 2.54 | BSR Items Based on Electric BSR 2013 | 0.0001 | P.Cum | |
155 | 2.55 | Supply, Fabricating & installing following sizes of powder coated perforated M.S. cable trays including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders, fastners, supports etc. as required. | 0.0001 | P.Cum | |
156 | 2.56 | 100mm x 50mm x 1.6mm | 60 | Each | |
157 | 2.57 | 300mm x 62.5mm x 2.0mm | 60 | Each | |
158 | 2.58 | P & F of ventilating fans, Capacitor start, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
159 | 2.59 | 150 mm sweep | 4 | Each | |
160 | 2.6 | SITC of self healing MPP/MP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.5 Watt per KVAR . including making connections with suitable capacity conductors/cables testing etc. as required. Group-1. | 0.0001 | P.Cum | |
161 | 2.61 | Heavy duty Three phase 440 V , 50 Hz capacitor (Bank) | 120 | kVAR | |
162 | 2.62 | SITC of microprocessor based three phase sensing power factor correction relay having following sensing capacity secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, metering facility as required. Group-1. | 0.0001 | P.Cum | |
163 | 2.63 | 12 to 14 stage | 0.0001 | P.Cum | |
164 | 2.64 | sensitivity up to 50 milli Amp | 2 | Each | |
165 | 2.65 | P & F Cam operated rotary switches on existing panel with 2 way and off position Group-1. | 0.0001 | P.Cum | |
166 | 2.66 | one pole | 0.0001 | P.Cum | |
167 | 2.67 | 16 A | 24 | Each | |
168 | 2.68 | P & F of ac operated heavy duty 230 /440 Volt power contactor conforming to IS:13947-4-1/IEC:947-4-1 having provision of mechanical interlocking, auuxilary contacts, Din rail mounting type including making connections, testing etc. as required. Group-1. | 0.0001 | P.Cum | |
169 | 2.69 | 4 pole Power contactors with following AC 1 Rating | 0.0001 | P.Cum | |
170 | 2.7 | Up to 32 Amp | 4 | Each | |
171 | 2.71 | P & F of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current , conforming to IS:13947-4-1/IEC:947-4-1, Din rail mounting type including making connections, testing etc. as required. Group-1. suitable for following capacity capacitor bank. | 0.0001 | P.Cum | |
172 | 2.72 | up to 6 KVAR | 20 | Each | |
173 | 2.73 | 7 to 10 KVAR | 4 | Each | |
174 | 2.74 | P&F of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming etc. as required. Group-1 | 0.0001 | P.Cum | |
175 | 2.75 | One day reserve (mechanical type ) | 4 | Each | |
176 | 2.76 | P & Laying XLPE insulated IS:7098/II/85 of Group1 and approved make H.T.cable for working voltage 11 K.V. Earthed direct in ground including excavation of 30cmx100cm size trench, 25cm layer of river sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection testing etc.as required. Group-1 of size. | 0.0001 | P.Cum | |
177 | 2.77 | 3 core 95.0 Sq.mm | 180 | Mtr. | |
178 | 2.78 | 3 core 150.0 Sq.mm | 160 | Mtr. | |
179 | 2.79 | Providing & making heat shrinkable type indoor / outdoor/ straight through terminations / joint kit of Group1 and approved make suitable for XLPE insulated 11 KV / 33 KV cable, with required components, prepration of cable ends,testing etc. as required. Group-1 of following sizes . | 0.0001 | P.Cum | |
180 | 2.8 | 11 KV End Termination Kit Indoor type | 0.0001 | P.Cum | |
181 | 2.81 | 3 core 70/95 Sq.mm | 12 | Set | |
182 | 2.82 | 11 KV End Termination Kit Outdoor type | 0.0001 | P.Cum | |
183 | 2.83 | 3 core 70/95 Sq.mm | 6 | Set | |
184 | 2.84 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required. Group-1 of size. Armoured | 0.0001 | P.Cum | |
185 | 2.85 | 1.5 Sq.mm | 0.0001 | P.Cum | |
186 | 2.86 | 12 core | 80 | Mtr. | |
187 | 2.87 | 2.5 Sq.mm | 0.0001 | P.Cum | |
188 | 2.88 | 12 core | 100 | Mtr. | |
189 | 2.89 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required. Group-1 complete in all respect of rating: | 0.0001 | P.Cum | |
190 | 2.9 | 24 V DC | 2 | Each | |
191 | 2.91 | SITC of FCBC ( Float cum boost charger)suitable for 415V +/-10%, 50 Hz , 1-? / 3 -? Input & 24/ 48 /110 V DC OutputNatural Cooled, free standing in Sheet Steel enclosure,SCR controlled , regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,Built in DC Distribution Board (6 No MCB), indication , control as required. Group-1 of following rating: | 0.0001 | P.Cum | |
192 | 2.92 | 15A + 15A | 2 | Each | |
193 | 2.93 | SITC of 11 KV, 400/630 A, 20kA / 3 sec, Out door Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, ring core protection & metering CT, Auxiliary relay for WTI, OTI ,Bucholz alarm & trip along with annuciator panel, master trip relay, mechanical ON / OFF / Earth indication, Voltage presence indicator, Shunt trip coil, 24 V DC power pack, Digital multi function meter, with Bus PT panel with 3 Nos single phase voltage transformers of the ratio 11kV/v3 / 110 V/v3, 25 VA, Class 1.0 with HT fuses in the primary and MCB on the secondary side, Voltmeter with selector switch, R Y B phase indication. etc. as required. Group-1, Anti reflex operating handle, right angle boots etc. as required. Group-1. | 3 | Set | |
194 | 2.94 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , Painting etc. as required. Group-1. | 500 | Kg. | |
195 | 2.95 | Supplying and fixing of chain link fencing with angle iron posts 50x50x6mm placed at every 3 Mtr. apart 30cm in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner and every tenth post to be strutted with (50 x 50 x 6cm) angle iron provided and fixed and fitted with posts including earth work in excavation etc. complete with chain link size. | 0.0001 | P.Cum | |
196 | 2.96 | 50mm x 50mm x 3.15mm | 200 | Sqm. | |
197 | 2.97 | Supply & Fixing ISI marked ( IS : 15683 ) Poratable Fire Exitnguisher,Trolley mounted Mech. Foam type capacity 09 ltrs with gun-metal cap and nozzle and complete respects in all respects including initial fill and wall suspension. | 10 | Each | |
198 | 2.98 | Supply & Fixing ISI marked ( IS : 15683 ) Portable fire Extinguisher, Carbon-dioxide type flat base including valve, discharge hose of not less than 10 mm dia. min. 600 mm long & complete in all respects including initial fill with C02 gas confirming to IS:307-1966 filled to a filling ratio of not more than 0.667and wall suspension bracket. Capacity 4.5 Kg. | 10 | Each | |
199 | 2.99 | Supply & Fixing ISI marked ( IS : 15683 ) Portable Fire Exitnguisher, ABC type, finished externally with red enamel paint, complete in all respects including initial fill and wall suspension of following capacity. | 0.0001 | P.Cum | |
200 | 3 | 6 kg | 16 | Each | |
201 | 3.01 | Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following specifications: | 0.0001 | P.Cum | |
202 | 3.02 | DP :double pole structure on 2 no ISMB 125 x 70 mm, 10 mtr high using 7 no MS channel each of size 100 mm x 50 mm x 2500 mm complete in all respect with nuts, springs washers, clamps as required. Group-1. | 0.0001 | P.Cum | |
203 | 3.03 | GO:Off load type gang operated 3-pole vertical flute type switch suitable for 11KV ; 400A ,3-ø, central post rotating double break isolator complete with MS hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator ,GI pipe of suitable length for operation. | 0.0001 | P.Cum | |
204 | 3.04 | DO: 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators | 0.0001 | P.Cum | |
205 | 3.05 | LA: 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv Overhead line with rated voltage of 9kv rms & nominal discharge current rating of 5 ka & complete with galvanized clamping arrangement GI bolts, nuts, washer etc as required. Group-1. | 0.0001 | P.Cum | |
206 | 3.06 | JUMPERS: 3 no 11kv acsr conductors mounted on pin type insularors as required. Group-1. 6.GENERAL:The go shall be operated by hand operated liver properly earthed with provision for locking mounted at 3’ | 2 | Each | |
207 | 3.07 | Supply and erection of GI stay set as per Discom specification complete with long stay rod with anchor plate including stay clamps turn buckle and G.I stay wire tightened through strain insulator, in cement concrete 1:3:6 including excavation of pit-re-filling etc as reqd. | 0.0001 | P.Cum | |
208 | 3.08 | Stay set of dia 16mm,1.8m long stay rod and anchor plate 300x300x6.4mm | 4 | Each | |
209 | 3.09 | Earth work in excavation/ by mechanical means (Hydraulic Excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed:\n | 4 | Cum. | |
210 | 3.1 | Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: | 0.0001 | P.Cum | |
211 | 3.11 | Cement Mortar 1:6 ( 1-Cement : 6-Sand). | 16 | Cum. | |
212 | 3.12 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. | 0.0001 | P.Cum | |
213 | 3.13 | M10 grade Nominal Mix \n1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). | 2 | Cum. | |
214 | 3.14 | Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : | 0.0001 | P.Cum | |
215 | 3.15 | 25 mm thick | 40 | Sqm. | |
216 | 3.16 | Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding: | 0.0001 | P.Cum | |
217 | 3.17 | New work (Two or more coats applied @ 3.84 kg/10 sqm). | 40 | Sqm. | |
218 | 3.18 | Supply, Installation, Testing & Commissioning of HT metering cubical panel as approved By DISCOMs fabricated out of 14 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX6mm having provision for Following: (i)Provision for fixing Trivector Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set (To be supplied by DISCOMs), (iii)TT Block, (iv) 6mm Bakelite sheet on all sides, (V) 3/6 core copper cable for interconnections etc. as required. Group-1. | 2 | Each | |
219 | 3.19 | NON BSR Items Based on Market Rates | 0.0001 | P.Cum | |
220 | 3.2 | S I T C of Copper wound Transformer LEVEL 1 conforming to IS: 2026 & Losses as per Discom's CTL ( CTL Test certificate to be attached ) of rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, standard accessories like conservator, silica gel breather, radiator, fins, HT bushing & LT cableboxes, Off -LTC (+/- 5% in steps of 2.5%) winding temperature rise of 50/55 C, ISI marked drain valve, Dial type Temperature gauge, first fill of oil, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer. ( See table - 08 for CTL Losses ) Note:- All the Distribution Transformers must be star rated as per notification of (BEE) ministry of Power, Government of India | 0.0001 | P.Cum | |
221 | 3.21 | 250KVA | 1 | Each | |
222 | 3.22 | 500KVA | 1 | Each | |
223 | 3.23 | Add extra for difference of Level 1 to Level 2 transformer @10% extra | 0.0001 | P.Cum | |
224 | 3.24 | 250KVA | 1 | Each | |
225 | 3.25 | 500KVA | 1 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy