Military Engineer Services-MES has published Repair /Replacement Of Dg Set , Amf Panel , Bty Charger With Connected Works At Ota Gaya. Submission Date for this Tender is 29-08-2019. Electrical Panel Tenders in Garrison Engineer Gaya Paharpur Mil Stn Gaya Bihar Bihar. Bidders can get complete Tender details and download the document.
Name of Work: Repair/ maintainance of DG set , AMF panel , Bty Charger with connected works at OTA Gaya | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | M&L comprehensive maint and attending complaint of DG set 200 KVA completed all as specified and directed by E-in-Charge. | 6 | Each Complaint | |
2 | 2 | Ditto all as per item No 1 here in before but 100 KVA capacity | 14 | Each Complaint | |
3 | 3 | Ditto all as per item No 1 here in before but 25/30 KVA capacity. | 4 | Each Complaint | |
4 | 4 | Supply and fixing Engine oil servo type in 20 Ltrs seal pack 20w/40 . Make:-HP/BP/Gulf | 450 | Ltrs | |
5 | 5 | Supply and fixing radiator coolant in 1 Ltrs seal Pack . | 40 | Ltrs | |
6 | 6 | Supply and fixing fuel filter Cartige as per sample of DG set 200 KVA capacity with rubber seal. . | 3 | Each Set | |
7 | 7 | Supply and fixing mobil filter Cartige as per sample of DG set 200 KVA capacity with rubber seal. . | 3 | Each Set | |
8 | 8 | Supply and fixing Air filter Cartige as per sample of DG set 200 KVA capacity with rubber seal. . | 3 | Each Set | |
9 | 9 | Supply and fixing fuel filter Cartige as per sample of DG set 100 KVA capacity with rubber seal. . | 7 | Each Set | |
10 | 10 | Supply and fixing mobil filter Cartige as per sample of DG set 100 KVA capacity with rubber seal. . | 7 | Each Set | |
11 | 11 | Supply and fixing Air filter Cartige as per sample of DG set 100 KVA capacity with rubber seal. . | 7 | Each Set | |
12 | 12 | Supply and fixing fuel filter Cartige as per sample of DG set 25/30 KVA capacity with rubber seal. . | 2 | Each Set | |
13 | 13 | Supply and fixing mobil filter Cartige as per sample of DG set 25/30 KVA capacity with rubber seal. . | 2 | Each Set | |
14 | 14 | Supply and fixing Air filter Cartige as per sample of DG set 25/30 KVA capacity with rubber seal. . | 2 | Each Set | |
15 | 15 | M&L Seilencer assembly complete with mufler of 100 KVA DG set all as directed. | 5 | Each Set | |
16 | 16 | Ditto all as per item No 15 here in before but 200 KVA DG set | 3 | Each Set | |
17 | 17 | M&LReplacement of lead Acid battery of Cap 180 AH , 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 6 | Each | |
18 | 18 | M&LReplacement of lead Acid battery of Cap 150 AH , 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 2 | Each | |
19 | 19 | M&L for repairs of self starter of 200 KVA DG set by repair/replacement of following unserviceable items:-\n (i) Re-winding of self starter armature.\n (ii) Replacement of cumutator and brushes.\n (iii) Replacement of bentex complete all as specified and directed. | 2 | Assesed | |
20 | 20 | M&L for repairs of self starter of 100 KVA DG set by repair/replacement of following unserviceable items:-\n (i) Re-winding of self starter armature.\n (ii) Replacement of cumutator and brushes.\n (iii) Replacement of bentex complete all as specified and directed. | 2 | Each | |
21 | 21 | M&L for repairs of self starter of 25/30 KVA DG set by repair/replacement of following unserviceable items:-\n (i) Re-winding of self starter armature.\n (ii) Replacement of cumutator and brushes.\n (iii) Replacement of bentex complete all as specified and directed.\n | 2 | Each | |
22 | 22 | M&L Replacement of AMF Gen Set controller for 200/100 KVA DG set as per sample complete all as specified and directed. | 5 | Each | |
23 | 23 | M&L Automatic voltage regulator controller 200/100 KVA as per sample. | 5 | Each | |
24 | 24 | M&L for repairs of dynemo cum alternator of 200 KVA DG set by repair/replacement of following unserviceable items complete all as specified and directed:-\n (i) Re-winding of dynemo.\n (ii) Replacement of circuit panel. | 2 | Each | |
25 | 25 | M&L for replacement of lead Acid battery of Cap 100 AH , 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 2 | Each | |
26 | 26 | M&L for replacement of lead Acid battery of Cap 70 AH , 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 4 | Each | |
27 | 27 | M&L for replacement of Battery Charger cap 180 AH ,12 Volt Capacity ,single Phase 240 Volt inc Amp meter , Voltmeter and On Off Switch , Indicator(Red and Green) complete all as specified and directed. | 4 | Each | |
28 | 28 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 800 amps rated aluminium bus bar for neutral complete with the following accessories incl Cable Gland & PCC Foundation and Coping taking down old all as specified and directed (Location -HQ Generator Panel )\nNote-MCCB and onload changeover switch will be measured and paid saparately against respective item of schedule. | 1 | Each job | |
29 | 28.01 | (a) Incoming | |||
30 | 28.02 | (i)ON load Change Over Switches 250 Amp 04 Pole,415V ,Front Operated QTY-01 Nos,Make-HPL /Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
31 | 28.03 | (ii) MCCB 04 Pole 36 kA, 250Amp,415V QTY-01 Nos,Make-HPL / Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
32 | 28.04 | (b) Out goings | |||
33 | 28.05 | (i) MCCB 04 Pole 25 KA,160 Amp AC , 415 volts,QTY-02 Nos,Make-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
34 | 28.06 | (ii) MCCB 04 Pole 25 KA,125 Amp AC , 415 volts,QTY-02 Nos,Make-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
35 | 28.07 | (iii) Aluminium bus bar 3 phase, 4 wire 800 Amp,415 V | |||
36 | 28.08 | (iv) Digital Volt meter 0-500V with slector switch, make-AE/L&T | |||
37 | 28.09 | (v) Digital Amp meter 0-500 amp with CT and selector switch. make-AE/L&T | |||
38 | 28.1 | (vi) Indicating lamp (Blue, Yellow &Red-1 set)LED Type Make-AE/L&T/ Havells | |||
39 | 29 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 800 amps rated aluminium bus bar for neutral complete with the following accessories incl Cable Gland & PCC Foundation and Coping taking down old all as specified and directed (Location -GC MESS)\nNote-MCCB will be measured and paid saparately against respective item of schedule. | 1 | Each | |
40 | 29.01 | (a) Incoming | |||
41 | 29.02 | (i) MCCB 04 Pole 36 kA, 250Amp,415V ,Make-HPL / Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
42 | 29.03 | (b) Out goings | |||
43 | 29.04 | (i) MCCB 04 Pole 25 KA,160 Amp AC , 415 volts,Make-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
44 | 29.05 | (ii) Aluminium bus bar 3 phase, 4 wire 800 Amp,415 V | |||
45 | 29.06 | (iii) Digital Volt meter 0-500V with slector switch, make-AE/L&T | |||
46 | 29.07 | (iv) Digital Amp meter 0-500 amp with CT and selector switch. make-AE/L&T | |||
47 | 29.08 | (v) Indicating lamp (Blue, Yellow &Red-1 set)LED Type Make-AE/L&T/ Havells | |||
48 | 29.09 | (vi) MCCB 04 Pole 25 KA,125 Amp AC , 415 volts,Make-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd /ABB | |||
49 | 30 | S&F MCCB 04 pole, 35 KA 630 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 1 | Each | |
50 | 31 | S&F MCCB 04 pole, 50 KA 400 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 1 | Each | |
51 | 32 | S&F MCCB 04 pole, 36 KA 250 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 2 | Each | |
52 | 33 | S&F MCCB 04 pole, 25 KA 160 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 4 | Each | |
53 | 34 | S&F MCCB 04 pole, 25 KA 125 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 4 | Each | |
54 | 35 | S&F MCCB 04 pole, 25 KA 100 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 1 | Each | |
55 | 36 | S&F On load change over switch 250 Amps, AC 415 volts with enclosures complete all as specified and directed. | 1 | Each | |
56 | 37 | Excavation in trenches not exc 1.5 mtr wide not exc 1.5 depth and getting out in soft/loose soil complete all as specified and directed. | 135 | Cum | |
57 | 38 | Returning, refiling in, incl spreading, watring and well ramming in layers not exc 25 cm in soft/loose soil. | 86 | Cum | |
58 | 39 | Removing surplus soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point. | 49 | Cum | |
59 | 40 | M&L Sand cushioning for underground cable with localy available sand for protection of cable incl spreading and consolidation complete all as specified and directedc. | 41 | Cum | |
60 | 41 | Supply & Lay in trenches dry well burnt locally available sub Class "B" bricks over sand cushioning for protection of cable complete all as specified and directed. | 4 | Per 1000 Nos | |
61 | 42 | Supply&Lay in trenches/laid floor/duct/drawn through conduit XLPE insulated , screened, PVC badded, galvenized steel striped or wire armoured heavy duty electric cabole 1100 V grade with alluminium conductor of cross sectional area of 120 sqmm, 3.5 core complete all as specified and directed. | 100 | RM | |
62 | 43 | All as per item no 42 but of size 95 sqmm, 3.5 core | 100 | RM | |
63 | 44 | All as per item no 42 but of size 50 sqmm, 3.5 core | 100 | RM | |
64 | 45 | All as per item no 42 but of size 35 sqmm, 3.5 core | 100 | RM | |
65 | 46 | All as per item no 42 but of size 25 sqmm, 3.5 core | 150 | RM | |
66 | 47 | M&L Earthing complete with galvenized steel earth plate electrode 600mm x 600mm x 6mm buried diredctly in ground verticaly to a depth not less than 2.25 m below normal ground level (with top edge of earth plate not less than 1.5m below ground level) connected to GI strip 32mm x 6mm main earthing lead by means of galvenized bolts, nuts & washers all as showning in electrical plate no 3 of MES sch part-I (2009) with connected to earth test point & to main switch board etc with and an incl ediquate quantity of charcole dust and common salt around earth plate, PCC 1:3:6 type C1 using 20 mm graded stone agreegate for earth pit with precast RCC (1:2:4) type B1 using 20mm graded stone agreegate 40mm thick cover reinforce with 8mm dia TMT bars 3 nos both way with 20mm dia MS round bar handle, GI light grade watering pipe 20mm dia with funnel and wire mess and 40mm dia GI light grade earth lead protection pipe complete all as specified and directed. | 4 | Each Set |