| 1 | 1 | M & L for Periodical maintenance of solar street lighting system including solar PV module by cleaning of dust, tightening of nut & bolts, applying greasing of battery terminal and supply and fill / topping up of distilled water (minimum of 6 litre) for battery as required complete all as specified and as directed.\nNote :- Maintenance of each solar street light system shall be carried out 4 times in a entire contract peroid and shall be measured as one job. The quoted rate deemed to be include for the above provision. | | 250 | JOB |
|---|
| 2 | 2 | Supply and fix electronic control unit assembly including charge controller and inverter for capacity of 12v/5A dusk to dawn operating condition including taking down unserviceable control unit assembly complete all as specified and as directed. \nMake:- Luminous/SuKam /Bajaj | | 25 | EACH |
|---|
| 3 | 3 | Supply and fix electronic control unit assembly including charge controller and inverter for capacity of 12v/10A dusk to dawn operating condition including taking down unserviceable control unit assembly complete all as specified and as directed. \nMake:- Luminous/SuKam /Bajaj | | 25 | EACH |
|---|
| 4 | 4 | Supply and fix crystalline type solar PV module of capacity 125 Wp comply with IEC 61215 Edition II / BIS 14286 or IEC 61646 and module efficiency not less than 12% including taking down existing unserviceable panel all as specified and as directed.\n | | 12 | EACH |
|---|
| 5 | 5 | Supply and fix light lead acid tubular battery capacity 100Ah, 12V, for solar street light including taking down unserviceable battery complete all as specified and as directed.\nMake:- Exide or equivalent in Amaron/Tata Power | | 12 | EACH |
|---|
| 6 | 6 | Supply and fix MS tubular pole of length 5m and 50mm dia, pre painted with two coats of synthetic enamel paint over a coat of red oxide primer and erected with PCC (1:3:6) type C2 (using 40mm graded stone aggregate) in foundation of size 0.6x0.6x0.9m and providing PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as in coping around pole of size 0.45x0.45x0.45m including necessary formwork and aspplying three coats of white wash on coping surfaces complete all as specified and as directed including taking down existing unserviceable/corroded street light pole. \nNote:- The rate quoted is deemed to be inclusive of Demolition of existing concrete, necessary excavation, PCC foundation, PCC coping with necessary form work and painting. Painting pattern of pole shall be of alternate bands of black and yellow colour for an height of 1m from bottom of pole and aluminium paint for remaining portion | | 8 | JOB |
|---|
| 7 | 7 | Taking down existing unserviceable/corroded battery box and supply and fix new MS battery box of size 60x30x30cm made out of 1.6mm thick mild steel sheet and apply two coats of epoxy paint over a coat of primer both sides for accommodating battery with necessary arrangement and fixing the box on pole complete all as specified and as directed. | | 50 | EACH |
|---|
| 8 | 8 | M & L for Periodical maintenance of solar PV modules (Set of 168 Nos) of solar power Generating plant by checking all circuit boards, connections, alongwith cleaning of dust, tightening of nut & bolts , repairs/renewal of connecting cables including cleaning of surrounding area all as specified and as directed. Note:- Tenderer are advised to visit the site before quoting the rate. Rate quoted is deemed to include for maintenance of PV module from the date of commencement till completion and will be measured as one JOB. If the completion date is extended by the Accepting Officer extra payment is not admissible for the extended period. Maintenance will be done free of cost. | | 1 | JOB |
|---|
| 9 | 9 | S&F PVC insulated, unsheathed bright annealed bare copper conductor industrial cables 6 sqmm 3 core for solar generating plant upto 50 KW all as specified | | 80 | RM |
|---|
| 10 | 10 | M & L for preparation of old painted steel surfaces and painting MS tubular Solar street light pole not more than 5 m long above GL including clamps brackets etc with one coat of synthetic enamel black and yellow colour paint with alternate layer up to 1 m height from bottom of pole and one coat of aluminium paint for the remaining portion including writing pole numbers etc., all as specified and as directed | | 175 | EACH\nJOB |
|---|
| 11 | 11 | M & L for preparation of old surfaces and applying one coat of white wash on PCC copings around poles of size not more than 0.45 X 0.45 X 0.45 m all as specified and as directed.\n | | 158 | EACH |
|---|
| 12 | 12 | M&L for electrical earthing complete with copper plate electrode of size 60cm x 60cm x 3.15mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, connected to copper strip of size 20x3mm as earth lead by means of bolts, nuts and washers of galvanised iron and protected with 40mm dia GI pipe , light grade upto 7.5m all as specified and as shown in MES schedule electrical plate No 3 of SSR Part I, including excavation and earth work in any type of soil, PCC 1:2:4 type B1 in chamber, GI pipe light grade 20mm bore with funnel for watering, CI cover complete including taking down existing unserviceable earthing all as specified and as directed. \n | | 5 | EACH\nSET |
|---|
| 13 | 13 | S & F copper strip of size 20x3mm as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in couduit/pipe or fixed to poles or any other indicated situation complete all as directed. | | 30 | RM |
|---|
| 14 | 14 | S & F rigid non-metallic PVC conduit 32 mm with necessary fittings complete all as specified and as directed.\n | | 20 | RM |
|---|
| 15 | 15 | M&L for cutting existing bituminous road surfaces not more than 150mm thick, removing the debris for laying of pipes/cables and making good with PCC 1:3:6 type C1 (using 20mm graded aggregate) to match with the adjustant surface complete all as specified and as directed. \nNote : Excavation and earth work beyond150mm thick will be measured and paid under relevant items.\n | | 10 | SQM |
|---|
| 16 | 16 | M&L for electrical earthing complete with galvanised steel plate electrode of size 60cm x 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, connected to copper strip of size 25x4mm as earth lead by means of bolts, nuts and washers of galvanised iron and protected with 40mm dia GI pipe , light grade upto 7.5m all as specified and as shown in MES schedule electrical plate No 3 of SSR Part I, including excavation and earth work in any type of soil, PCC 1:2:4 type B1 in chamber, GI pipe light grade 20mm bore with funnel for watering, CI cover complete including taking down existing unserviceable earthing all as specified and as directed. \n | | 8 | EACH\nSET |
|---|
| 17 | 17 | S & F GI strip of size 25x4mm as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in couduit/pipe or fixed to poles or any other indicated situation complete all as directed. | | 45 | RM |
|---|
| 18 | 18 | M&L for electrical earthing complete with galvanised steel plate electrode of size 60cm x 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, connected to galvanised earth lead wire of 4mm dia as earth lead by means of bolts, nuts and washers of galvanised iron and protected with 40mm dia GI pipe , light grade upto 7.5m all as specified and as shown in MES schedule electrical plate No 3 of SSR Part I, including excavation and earth work in any type of soil, PCC 1:2:4 type B1 in chamber, GI pipe light grade 20mm bore with funnel for watering, CI cover complete including taking down existing unserviceable earthing all as specified and as directed. \n | | 6 | EACH\nSET |
|---|
| 19 | 19 | S & F GI wire of 4mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in couduit/pipe or fixed to poles or any other indicated situation complete all as directed. | | 81 | RM |
|---|
| 20 | 20 | Supply and installation of Maintenance free tripod environment friendly earthing system comprising of 17.2 mm dia 3 M long 3 Nos earth electrode of low carbon steel electrode with molecular copper bonded for a thickness of 250 microns and 30 Kgs of cabon based powerset environment friendly backfill compound with bimetallic clamp placed in equalized triangle with 450mm dia clamp and all as specified as per IS-3043 and as directed at site taking down of unserviceable earthing all as specified and as directed incl taking down unserviceable items. Make:- Jef eco/ tercel/ Gravin or equivalent. | | 2 | EACH\nJOB |
|---|
| 21 | 21 | Supply and fix on pole/wall or lay in trenches under road/drain crossings etc for drawing cables GI pipe light grade ISI marked of size 100mm bore dia including necessary pipe fittings, clamps, bolts, nuts etc all as specified and as directed | | 12 | RM |
|---|
| 22 | 22 | Supply and fix on pole/wall or lay in trenches under road/drain crossings etc for drawing cables GI pipe light grade ISI marked of size 80mm bore dia including necessary pipe fittings, clamps, bolts, nuts etc all as specified and as directed | | 20 | RM |
|---|
| 23 | 23 | Supply and fix on pole/wall or lay in trenches under road/drain crossings etc for drawing cables GI pipe light grade ISI marked of size 50mm bore dia including necessary pipe fittings, clamps, bolts, nuts etc all as specified and as directed | | 30 | RM |
|---|
| 24 | 24 | Material and labour providing EARTHPLUS ADVANCED EARTHING COMPOUND 10 KG BAG to chemical earth pits including necessary excavation, removing old compound , retruning filling and testing of earthing values complete all as specified and as directed. Make : Gravin, Tercel | | 15 | EACH\nJOB |
|---|
| 25 | 25 | M & L for providing earthing improving compound like magnesium sulphate, copper sulphate, rock salt etc including digging of holes around earthing pits and filling with the compound/compund solution , retruning filling of sand to improve the earthing values and testing of earthing values complete all as specified and as directed. | | 14 | EACH\nJOB |
|---|
| 26 | 26 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m deep and getting out in soft/loose soil complete all as specified and as directed. | | 194 | CUM |
|---|
| 27 | 27 | Returning filling in including levelling watering and well ramming in layers not exceeding 25cm each layer complete all as specified and as directed. | | 114 | CUM |
|---|
| 28 | 28 | Removing excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.50m above the starting point complete all as specified and as directed. | | 80 | CUM |
|---|
| 29 | 29 | Supply, lay in trenches sub class bricks, old size for cable protection all as specified and directed.\nNote:- Bricks shall be laid in such a way that its length is perpendicular to the length of cable. | | 5800 | EACH |
|---|
| 30 | 30 | Supply lay/spread in trenches, river sand, clean, including spreading, levelling, punning as in cushioning of cables all as specified and as directed. \nNote :- Punned depth will be measured and paid\n | | 65 | CUM |
|---|
| 31 | 31 | Supplying and laying reinforced precast concrete cable cover, class HV, type 1, Flat, size300 mm x 180 mm x 40 mm complete laid in trenches as in cable protection all as specified and as directed | | 95 | EACH |
|---|
| 32 | 32 | M&L for plain cement concrete 1:4:8, type D2 (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and as directed | | 4.5 | CUM |
|---|
| 33 | 33 | M&L for plain cement concrete 1:2:4, type B1 (using 20mm graded stone aggregate) as in coping of pole including necessary form work complete all as specified and as directed | | 0.3 | CUM |
|---|
| 34 | 34 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 3.5 core 120 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed. | | 100 | RM |
|---|
| 35 | 35 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 3.5 core 95 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed. | | 100 | RM |
|---|
| 36 | 36 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 3.5 core 70 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed. | | 100 | RM |
|---|
| 37 | 37 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 3.5 core 50 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed. | | 100 | RM |
|---|
| 38 | 38 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 4 core 25 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed. | | 150 | RM |
|---|
| 39 | 39 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 4 core 16 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed. | | 150 | RM |
|---|
| 40 | 40 | Supply, laying and testing LT UG cable XLPE insulated, sheathed, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with multi stranded aluminium conductor of 2 core 10 Sqmm cross sectional area including taking down existing unserviceable cable complete all as specified and as directed.\nNote for item No 34 to 40:-(i) Lugs and glands are deemed to be included in the rate quoted for laying of cable and to be used properly wherever required while connecting cables to the panel board.(ii) Earth work such as excavation, refilling, etc. shall be measured separately under relevant items. | | 200 | RM |
|---|
| 41 | 41 | S&F HT, 11000 volts grade , DISC type insulator, single disc assembly of size 145 mm height and 255 mm dia, ball and socket type, porcelain, vitreous, white or brown for tension with tensile clamps for conductors including taking down the existing unserviceable insulator complete all as pecified and as directed. | | 10 | EACH |
|---|
| 42 | 42 | Dismantling the existing unserviceable Main switches/ MCCB's etc, and Supply & fix the following items in the existing LT distribution pillar boxes, connecting up with suitable size / capacity alumimum strips / rods / cables and testing including necessary drilling of holes to suit the new items, replacement of bolts, nuts and washers all as specified and as directed. \nNote :- Any modification / addition / Alteration required for fixing the new MCCBs in to the existing panel boards shall be carried out without any extra cost all as specified and directed by Engineer-in-Charge. | | | |
|---|
| 43 | 42.01 | Changeover switch 4 pole, 415 volts, on load type 400 Amps capacity | | 1 | EACH |
|---|
| 44 | 42.02 | Changeover switch 4 pole, 415 volts, on load type 200 Amps capacity | | 2 | EACH |
|---|
| 45 | 42.03 | Changeover switch 4 pole, 415 volts, on load type 100 Amps capacity | | 2 | EACH |
|---|
| 46 | 42.04 | Changeover switch 4 pole, 415 volts, on load type 63 Amps capacity | | 2 | EACH |
|---|
| 47 | 42.05 | MCCB, 4 pole, 415 volts, 50Hz, 36 KA, 400 Amps capacity with adjustable thermal and ajustable magnetic setting. | | 1 | EACH |
|---|
| 48 | 42.06 | MCCB, 4 pole, 415 volts, 50Hz, 36 KA, 250 Amps capacity with adjustable thermal and ajustable magnetic setting. | | 1 | EACH |
|---|
| 49 | 42.07 | MCCB, 4 pole, 415 volts, 50Hz, 36 KA, 200 Amps capacity with adjustable thermal and ajustable magnetic setting. | | 1 | EACH |
|---|
| 50 | 42.08 | MCCB, 4 pole, 415 volts, 50Hz, 36 KA, 160 Amps capacity with adjustable thermal and ajustable magnetic setting. | | 1 | EACH |
|---|
| 51 | 42.09 | MCCB, 3 pole, 415 volts, 50Hz, 16 KA, 100 Amps capacity with adjustable thermal and ajustable magnetic setting. | | 2 | EACH |
|---|
| 52 | 42.1 | MCCB, 3 pole, 415 volts, 50Hz, 16 KA, 63 Amps capacity with adjustable thermal and ajustable magnetic setting. | | 2 | EACH |
|---|
| 53 | 43 | Supply and laying in trenches/poles/wall etc HT UG Cable XLPE insulated screened, PVC bedded, galvanised steel strip, armoured electric power cables (Heavy duty earthed) with aluminium conductor 11000 volts grade conforming to IS specifications of size 120 Sqmm 3 core cable including taking down the existing unserviceable cable all as specified and directed :- Note :- (i) Lugs and glands are deemed to be included in the rate quoted for laying of cable and to be used properly wherever required while connecting cables to the panel board. (ii) Earth work such as excavation, refilling, etc. shall be measured separately under relevant items. | | 120 | RM |
|---|
| 54 | 44 | M&L for painting of MS tubular electric HT/LT /street light pole upto 9.0 mtr long above GL with one coat of synthetic enamel black and yellow colour paint with alternate layer up to 1Mtr height from bottom of pole and remaining portion of the pole with aluminium paint including cross arms, clamps, brackets etc., fixed on the same pole all as specified and as directed brushes etc., including preparation of old painted surfaces and writing pole numbers complete all as specified and as directed. | | 250 | EACH |
|---|
| 55 | 45 | M & L for applying one coat of synthetic enamel grey light colour paint on existing LT panel board including preparation of old surfaces complete all as specified and as directed , | | 15 | EACH |
|---|
| 56 | 46 | M&L for insulation rubber mat 1100 volt grade suitable for LT installation of size 2m x 1m x 10mm thick : Make : Jyoti/Jayshon | | 10 | EACH |
|---|
| 57 | 47 | Supply and fix on pole / wall etc., GI pipe Bracket made up of 25 mm bore dia light grade pipe 1.5 mtr Long, suitably bent to shape and fixed on pole with 2 Nos suitable MS calmp of size 25 X3 mm including bolts, nuts and washers all as specified and as directed complete all as specified and as directed. | | 14 | EACH\nJOB |
|---|
| 58 | 48 | S&F GI bracket made out of GI tube 40mm medium grade, 2.0m in length bend to shape for fixing luminair including MS flat iron 30x6 mm clamp and applying two coats of aluminium paint over one coat of primer including preparation of surfaces complete all as specified and as directed. | | 16 | EACH\nJOB |
|---|
| 59 | 49 | Cutting / clearing and removing the vegetable / bush growth any nature / type around the bottom of the electric poles / stays structures / installations / sub station etc., so as to keep the area clean for easy access to carry out repair / maintenance works on ples etc., including cutting and removing the creepers on poles / stays etc., removing from site and throwing out at a place where directed at distance not exceeding 250mtr away all as specified and as directed.\n | | 395 | SQM |
|---|
| 60 | 50 | M&L for steel tubular swaged pole complete with base plate, final taper plug, bolt, nuts and screws as specified type 410 SP-31 (09 m long) including applying two coats of aluminum paint over a coat of primer and taking down the existing unserviceable pole complete all as specified and as directed. | | 5 | EACH |
|---|
| 61 | 51 | Supply and fix porcelain type fuse cut out,100 Amps, SP, Kit cat type fixed inside SMC box / main switch/ board etc. with suitable screws and connecting and testing including taking down the existing unserviceable fuse complete all as specified and as directed.\nMake Havells Cat No IHKKRN4100 or equivalent in L&T/C&S | | 4 | EACH |
|---|
| 62 | 52 | Supply and fix porcelain type fuse cut out, 63 Amps, SP, Kit cat type fixed inside SMC box / main switch/ board etc. with suitable screws and connecting and testing including taking down the existing unserviceable fuse complete all as specified and as directed.\nMake Havells Cat No IHKKRN4063 or equivalent in L&T/C&S | | 4 | EACH |
|---|
| 63 | 53 | S&F junction box, sheet moulding compound (SMC) type with hinged type door, weather proof, dust and vermin proof, locking arrangement off white colour of size 240x130x110mm (internal) suitable holes drilled and mounted on insulator supports for cables terminals in and out complete junction box fixed on pole/wall/ground etc with suitable size clamps, bolts, nuts all as specified and as directed. | | 15 | EACH |
|---|
| 64 | 54 | S&F junction box, sheet moulding compound (SMC) type with hinged type door, weather proof, dust and vermin proof, locking arrangement off white colour of size 300x200x105mm (internal) suitable holes drilled and mounted on insulator supports for cables terminals in and out complete junction box fixed on pole/wall/ground etc with suitable size clamps, bolts, nuts all as specified and as directed. | | 16 | EACH |
|---|
| 65 | 55 | S & F copper conductor cable of size 4.0 Sqmm drawn through PVC conduit all as specified and directed.\nNote: PVC conduit shall be measured and paid seperately | | 100 | RM |
|---|
| 66 | 56 | S & F rigid non-metallic PVC conduit 20 mm dia with necessary fittings and accessories complete all as specified and as directed.\n | | 80 | RM |
|---|
| 67 | 57 | S & F LED light fitting 60W with electronic driver connecting and testing including taking down the existing unserviceable light fitting complete all as specified and as directed.\nMake : Syska , model No ssk-HB-60W or equivalent in CG/Havells/Philips | | 8 | EACH |
|---|
| 68 | 58 | S & F highbay LED light fitting 120W, connecting and testing including taking down the existing unserviceable light fitting complete all as specified and as directed.\nMake : Syska , model No ssk-HB-120W-IP or equivalent in CG/Havells/Philips | | 4 | EACH |
|---|
| 69 | 59 | Cutting of tree branches of any type / size of trees touching / approaching the electric OH lines / poles structures etc., by climbing on trees, cutting required number of branches of any size / girth protruding towards OH lines so as to keep tree branches clear / off not less than 1.5mtr away from any side of conductors on poles, removing cut branches from site and throwing out at a place where directed but not more than 250mtr away from the site all as specified and as directed. Note :- 1. Suitable ropes shall be used to hold the branches while cutting in progress to prevent branches falling on OH lines and causing damages. 2. In case of any damages to the OH lines / poles or any other structures, the same shall be repaired / rectified / made good by the contractor with out any extra cost. 3. Shut down of electric supply shall be taken before climbing trees. 4. The cut branches shall be removed from site and deposited at a distance not exceeding 200 mtr as directed. 5. Each tree will be measured as one Job irrespective of any number of branches. | | 150 | EACH\nJOB |
|---|
| 70 | 60 | S & F Triple pole, mechanically operated, mounted on insulator and steel frame with operating mechanism worked from ground level switch air break Gang operated for current rating upto 400 amps and 11000 volts complete all as specified. | | 4 | EACH |
|---|