| 1 | 1 | S&F stay assembly with diameter of stay rod 20mm complete with accessories all as shown in electrical plate No 1 including taking down existing unserviceable stay assembly complete all as specified and as directed.\nNote : Loop type insulator, stay clamps, excavation and concrete will be measured separately.\n | | 3 | EACH SET |
|---|
| 2 | 2 | S&F loop type insulator large size, vitreous porcelain white or brown with overall dimensions 90X140mm, clearance of hole 25.5mm including taking down existing unserviceable insulator complete all as specified and as directed. | | 4 | EACH |
|---|
| 3 | 3 | S&F lightning arrester, expulsion type complete with all fitting transmission class, discharge capacity 65 Kilo Amps suitable for 11000 Volts rating, ISI marked including taking down existing unserviceable lightning arrester complete all as specified and as directed. | | 2 | EACH SET |
|---|
| 4 | 4 | S&F Steel tubular swaged poles compete with cast iron base plate, finial taper plug, bolts, nuts and screws of following size types including applying two coats of aluminium paint over a coat of red oxide primer including taking down existing unserviceable pole complete all as specified and as directed. Note: Earth work excavation and Civil work for mounting of pole shall be measured and paid seperately under relevant item. Mounting of pole shall be dine all as directed by the Engineer-in-charge. | | | |
|---|
| 5 | 4.01 | 11mtr long, type 410 SP-55 | | 1 | EACH |
|---|
| 6 | 4.02 | 9 mtr long, type 410 SP-31 | | 2 | EACH |
|---|
| 7 | 5 | S&F cable jointing kit for 11 KV (earthed) grade cable straight through heat shirnkable type joint complete with jointing material and accessories suitable for HT UG XLPE cable armoured heavy duty cables with aluminium conductor of size 120 Sqmm 3 core connecting up and testing including taking down unserviceable joint complete all as specified and as directed. | | 7 | EACH |
|---|
| 8 | 6 | Supply and install switch Air Break gang operated triple pole, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level complete, rating upto 200 Amps 11 KV including taking down existing unserviceable switch complete all as specified and as directed. | | 9 | EACH |
|---|
| 9 | 7 | S&F cable end termination jointing, heat shrinkable type, indoor type complete with all accessories and insulating compound etc., as per manufacturers instructions suitable for HT 11000 volts, XLPE UG cables of size 3 core 120 to 185 sqmm connection up and testing including taking down existing unserviceable termination joint complete all as specified and as directed. | | 6 | EACH |
|---|
| 10 | 8 | S&F cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of applying two coats of aluminium paint over a coat of primer including taking down existing corroded steel sections complete all as specified and as directed. | | 0.8 | QTL |
|---|
| 11 | 9 | S&F insulator HT 11000 volts grade, PIN type of size 150mm height and 150mm dia, porcelain, vitreous, white or brown including galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut including taking down existing unserviceable insulator complete all as specified and as directed. | | 6 | EACH |
|---|
| 12 | 10 | Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5 mtr in depth and getting out in soft/loose soil complete all as specified and as directed. | | 265 | CUM |
|---|
| 13 | 11 | Returning, filling in trenches, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer in soft/loose soil all as specified and as directed. | | 106 | CUM |
|---|
| 14 | 12 | Removing excavated material/surplus soil and depositing where directed at a distance not exceeding 50mtr and depositing at a level not exceeding 1.5 mtr from starting point all as specified and as directed. | | 156 | CUM |
|---|
| 15 | 13 | Supply lay/spread in trenches, river sand, clean, including spreading, levelling, punning as in cushioning of cables all as specified and as directed.\nNote :- Punned depth will be measured and paid.\n | | 130 | CUM |
|---|
| 16 | 14 | Supply, lay in trenches fly ash bricks, old size for cable protection all as specified and directed. \nNote:- Bricks shall be laid in such a way that its length is perpendicular to the length of cable.\n | | 11000 | EACH |
|---|
| 17 | 15 | Supply, laying, connecting and testing LT UG cable FRLS XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade sheathed, multi stranded of following cross sectional area including taking down of unserviceable cables complete all as specified and as directed :- Note :-(i) Lugs and glands are deemed to be included in the rate quoted for laying of cable and to be used properly wherever required while connecting cables to the panel board. (ii) Earth work such as excavation, refilling, etc. shall be measured separately under relevant items. | | | |
|---|
| 18 | 15.01 | 3.5 core 150 Sqmm | | 200 | RM |
|---|
| 19 | 15.02 | 3.5 core 120 Sqmm | | 460 | RM |
|---|
| 20 | 15.03 | 3.5 core 95 Sqmm | | 180 | RM |
|---|
| 21 | 15.04 | 3.5 core 70 Sqmm | | 250 | RM |
|---|
| 22 | 15.05 | 3.5 core 50 Sqmm | | 250 | RM |
|---|
| 23 | 15.06 | 3.5/4 core 25 Sqmm | | 190 | RM |
|---|
| 24 | 15.07 | 4.0 core 16 Sqmm | | 97 | RM |
|---|
| 25 | 16 | S&F HT 11000 volts grade, DISC type insulator single disc assembly of size 145mm height and 255mm dia ball and socket type, porcelain, vitreous, white or brown for tension with tensile clamps for conductors including taking down existing unserviceable insulators complete all as specified and as directed. | | 6 | EACH |
|---|
| 26 | 17 | Cutting/clearing and removing the vegetable/bush growth any nature/type around the electric poles/stays structures/installations / substation., so as to keep clean the area for easy access to carry out repair/maintenance works on poles etc., including cutting and removing the creepers on poles/stays etc., removing from site and throwing out at a place where directed at distance not exceeding 250mtr away complete all as specified and as directed. | | 450 | SQM |
|---|
| 27 | 18 | Removing existing blue metal/hard core from substation yards cleaning the surface/area below the hard core, relaying/spreading removed blue metal/hard core including levelling of surfaces complete all as specified and as directed. | | 25 | SQM |
|---|
| 28 | 19 | S&F horn Gap type fuse unit 11000 volts grade mounted on insulators and steel frame single pole fixed on DP structures including taking down existing unserviceable fuse unit complete all as specified and as directed. | | 6 | EACH |
|---|
| 29 | 20 | Dismantling of existing OH lines ACSR conductors of any size / type from poles/ structures, restringing/refixing the same dismantled ACSR conductors on poles/insulators with necessary aluminium binding wires for reducing sag on conductors etc., complete all as specified and as directed. | | 1000 | RM |
|---|
| 30 | 21 | S&F galvanised steel wire 4mm dia for earth continuity conductor stringed/fixed including necessary clamps, screws fixed on cross arms/insulator bolts etc., including taking down existing unserviceable GI wire complete all as specified and as directed. | | 110 | RM |
|---|
| 31 | 22 | S&F junction box sheet moulding compound (SMC) type with hinged type door, locking arrangement half white colour of size 300x200x105mm (internal) fixed on pole/wall etc with suitable size clamps bolts nuts including taking down existing unserviceable box complete all as specified and as directed. | | 20 | EACH |
|---|
| 32 | 23 | S&F junction box sheet moulding compound (SMC) type with hinged type door, locking arrangement half white colour of size 240x130x110mm (internal) fixed on pole/wall etc with suitable size clamps bolts nuts including taking down existing unserviceable box complete all as specified and as directed. | | 20 | EACH |
|---|
| 33 | 24 | Cutting of tree branches of any type/size of trees, touching/approaching the electric OH lines/Poles structures etc., by climbing on trees, cutting required number of branches of any size/girth protruding towards OH lines so as to keep tree branches clear/off not less than 1.5mtr away from any side of conductors on poles, removing cut branches from site and throwing out at a place where directed not more than 250mtr away from site complete all as specified and as directed.\nNote :-1. Suitable ropes shall be used to hold the branches while cutting in progress to prevent branches falling on OH lines and causing damages. 2. In case of any damages to the OH lines / poles or any other structures, the same shall be repaired / rectified / made good by the contractor with out any extra cost. 3. Shut down of electric supply shall be taken before climbing trees. 4. The cut branches shall be removed from site and deposited at a distance not exceeding 200 mtr as directed. 5. Each tree will be measured as one Job irrespective of any number of branches. | | 160 | EACH\nJOB |
|---|
| 34 | 25 | M&L for hard core of gauge not exceeding 63mm, deposited, spread and levelled in layers not exceeding 15cm thick watered and rammed to a true surfaces using broken stones etc complete all as specified and as directed. | | 5 | CUM |
|---|
| 35 | 26 | Laying only bricks in trenches burnt bricks old size, sub class ‘B’ for cable protection complete all as specified and as directed.\nNote: The serviceable bricks obtained from item No 15 shall be reused. | | 2260 | EACH |
|---|
| 36 | 27 | M&L for PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in foundations filling and mass concrete complete all as specified and directed. | | 4 | CUM |
|---|
| 37 | 28 | M&L for PCC 1:3:6, type C1 (using 20mm graded stone aggregate) as in plinth protection, platforms, pole coping etc., complete all as specified and directed. | | 4 | CUM |
|---|
| 38 | 29 | Dismantling the existing following unserviceable main switches/MCCB’s etc and S&F new items in the existing LT distribution pillar boxes and connecting up with suitable size/capacity aluminium strips/rods/cables and testing including necessary drilling of holes to suit the new items renewal of bolts, nuts and washers all as specified and as directed. Note :- Any modification/addition/alteration required for fixing the new MCCB in to the existing panel boards shall be carried out without any extra cost \nMake : Havells/Standard/L&T\n | | | |
|---|
| 39 | 29.01 | Change over switch 4 pole 415 volts on load type having capacity 100 Amps complete all as specified and as directed. | | 4 | EACH |
|---|
| 40 | 29.02 | Change over switch 4 pole 415 volts on load type having capacity 63 Amps complete all as specified and as directed. | | 4 | EACH |
|---|
| 41 | 29.03 | MCCB 4 pole, 415 volts, 50 Hz, 35 KA, 400 Amps adjustable thermal and adjustable magnetic setting complete all as specified and as directed. | | 5 | EACH |
|---|
| 42 | 29.04 | MCCB 4 pole, 415 volts, 50 Hz, 35 KA, 250 Amps adjustable thermal and adjustable magnetic setting complete all as specified and as directed. | | 5 | EACH |
|---|
| 43 | 29.05 | MCCB 4 pole, 415 volts, 50 Hz, 25 KA, 200 Amps adjustable thermal and adjustable magnetic setting complete all as specified and as directed. | | 4 | EACH |
|---|
| 44 | 29.06 | MCCB 4 pole, 415 volts, 50 Hz, 25 KA, 160 Amps adjustable thermal and adjustable magnetic setting complete all as specified and as directed. | | 7 | EACH |
|---|
| 45 | 29.07 | MCCB 3 pole, 415 volts, 50 Hz, 25 KA, 100 Amps adjustable thermal and adjustable magnetic setting complete all as specified and as directed. | | 7 | EACH |
|---|
| 46 | 30 | Supply and fix on pole/wall or lay in trenches under road/drain crossings etc for drawing cables GI pipe light grade ISI marked of following size including taking down existing unserviceable bracket complete all as specified and as directed :- | | | |
|---|
| 47 | 30.01 | 40mm bore dia | | 48 | RM |
|---|
| 48 | 30.02 | 50mm bore dia | | 48 | RM |
|---|
| 49 | 30.03 | 80mm bore dia | | 36 | RM |
|---|
| 50 | 30.04 | 100mm bore dia | | 24 | RM |
|---|
| 51 | 31 | M&L electrical earthing complete with GI plate electrode of size 60cm x 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, connected to galvanised earth lead wire 4mm dia by means of bolts, nuts and washers of galvanised iron, earth lead wire protected by means of 15mm bore light grade GI pipe upto switch board / panel board, all as specified and as shown in MES schedule electrical plate No 3 of SSR Part I, including excavation and earth work in any type of soil, PCC 1:2:4 type C1 in chamber, RCC 1:2:4 type C1, 40mm thick cover slab with 6mm dia MS bars at 100mm centre both ways, with 6mm dia MS hook, charcoal dust, salt, funnel for watering complete all as specified and as directed. | | 14 | EACH SET |
|---|
| 52 | 32 | Supply, fabricate, install, test and commissioning of LT panel board indoor type (CPRI Approved manufacturer), AC, 3 Phase, 4 wire, 415/500v, 50 Hz floor mounted powder coated with FRP insulator fixed on angle iron frame, fabricated with 2mm thick mild steel and suitable size pressed steel frame work, factory made, bottom with detachable plates, front and rear with hinged type door and locking arrangement chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 3 Nos, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strips/road insulated complete including painting of panel boards with two coats synthetic enamel paint over one coat of red oxide primer including dismantling old unserviceable panel board complete all as specified and comprising of the following:-\nIncoming :-\n(a) MCCB 400 Amps, 4 Pole, 35 KA with adjustable thermal and adjustable magnetic setting-01 No.\n\n\n | | 1 | EACH |
|---|
| 53 | 32.01 | Outgoing :-\n(a) MCCB 250 Amps 4 Pole, 35 KA with adjustable thermal and fixed magnetic setting-02 Nos.\n(b) MCCB 200 Amps 4 Pole, 25 KA with adjustable thermal and fixed magnetic setting-02 Nos.\n(c) MCCB 100 Amps 4 Pole, 25 KA with adjustable thermal and fixed magnetic setting-02 Nos.\n(d) Digital volt meter 0-500 volts with selector switch-01 Nos, Make : AE/Havells/Autonix/HPL\n(e) Digital Amp meter 0-200 Amps with selector switch and CT-01 No, Make : AE/Havells/Autonix/HPL\n(f) LED indicator RYB-03 No, Make : AE/Havells/Autonix/HPL. | | | |
|---|
| 54 | 33 | Supply and laying in trenches/poles/wall etc HT UG Cable FRLS XLPE insulated screened, PVC bedded, galvanised steel strip, multi stranded, armoured electric power cables (Heavy duty earthed) with aluminium conductor 11000 volts grade conforming to IS specifications of size 120 Sqmm 3 core cable including taking down the existing unserviceable cable complete all as specified and directed :- Note :- (i) Lugs and glands are deemed to be included in the rate quoted for laying of cable and to be used properly wherever required while connecting cables to the panel board. (ii) Earth work such as excavation, refilling, etc. shall be measured separately under relevant items. | | 100 | RM |
|---|
| 55 | 34 | M&L for cutting existing bituminous road surfaces not more than 150mm thick, removing the debris for laying of pipes/cables and making good with PCC 1:3:6 type C1 (using 20mm graded aggregate) to match with the adjacent surface complete all as specified and as directed. \nNote : Excavation and work beyond150mm thick will be measured and paid under relevant items.\n | | 35 | SQM |
|---|
| 56 | 35 | Supply, fix, connect and test, on pole/pillar/wall etc. LED street light luminare, outdoor type 48 Watts with replaceable drivers suitable for operation on AC, single phase, 100-265 Volts, 50 Hz supply including provision of two single core 2.5 Sqmm aluminium conductor PVC insulated, 1100 Volts grade cables not more than 8 mtr long and connecting up OH line / SMC box conductors and fittings and testing, including taking down old fittings all as specified and as directed. Make : Havells Cat No : ENDURAPEARLNEOSL40WLED757PASYTOPC (Model No ENDURA PEARL NEO) or equivalent of make CG/PHILIPS | | 65 | EACH |
|---|
| 57 | 36 | M&L for preparation of old painted surfaces, removing dust and other deposited materials by scraping from HT/LT tubular pole 8mtr to 9mtr long, painting of pole with one coat of black paint upto 1 Mtr from bottom and painting the rest of the pole including cross arms cable protection pipe clamps, street light bracket with one coat of aluminium paint including writing 50mm size figures/letters over black back ground for making pole Nos substation Nos with white synthetic enamel paint complete all as specified and as directed. | | 270 | EACH |
|---|
| 58 | 37 | M&L for preparation of old painted surfaces, removing dust and other deposited materials by scraping from LT panel board and applying two coats syenthetic enamel paint light grey shade complete all as specified and as directed. | | 83 | EACH |
|---|
| 59 | 38 | M&L for rubber mat 1100 volts grade suitable for LT installation of size 2mtr x 1mtr x 10mm thick complete all as specified and as directed.\nMake : Jyoti/Denson or equivalent.\n | | 6 | EACH |
|---|
| 60 | 39 | Dismantling of following unserviceable parts/items/accessories form street light control boxes and S & F with new items including checking of internal wirings, renewal of unserviceable wires, connecting up and testing complete all as specified and as directed. | | | |
|---|
| 61 | 39.01 | Timer switch, analog type for automatic street light ON/OFF control Make : SEIMENS/L&T/GEC | | 5 | EACH |
|---|
| 62 | 39.02 | Electrical contactor 63 Amps, 3 phase, 415 volts with relay, 3 pole Make : L&T model ML 6/SEIMENS/BCH | | 5 | EACH |
|---|
| 63 | 40 | S&F on pole/wall etc GI pipe bracket made up with 25mm bore light grade pipe 2 mtr long suitably bent to shape and fixed on pole with 2 Nos MS clamp of size 25x3mm size including bolts, nuts and washers for fixing of street light fittings on poles/building etc complete all as specified and as directed | | 33 | EACH\nJOB |
|---|
| 64 | 41 | S & F building security LED light fitting 20W complete with all accessories including providing suitable twin core flexible copper wire including taking down the existing unserviceable light fitting complete all as specified and as directed.\nMake : Havells, cat part No : ENDURAPEARLSL20WLED757SASYTOPC or equivalent in CG/Philips\n | | 49 | EACH |
|---|