| 1 | 1 | Taking down carefully copper/aluminum point wiring light/fan/sockets out let/power point complete (fittings such as switches, sockets, ceiling rose, pendent holders, light fittings etc. are to be measured separately) and/or drawing out from existing conduit/batten and making good disturbed surface of walls/floors/ceiling, complete all as specified and as directed. | | 3415 | Point |
| 2 | 2 | Material and labour for concealed point wiring using approved colour coding as per IS, with multi stranded copper conductor 1.5 sqmm (Nominal area), single core, FRLS (FIRE Retardent Low Smoke), PVC insulated and unsheathed stranded cable drawn through and including non metallic, heavy duty PVC concealed conduit not less than 20mm dia and its fittings including all tees, bell mouth pieces and fixing accessories such as couplers, saddlers, pipe hooks etc, PVC junction boxes ISI marked with GI sunken boxes made out of 1.2mm thick of any module from 2 to 18 module confirming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly coated with two coats of anti corrosive paint over a coat of red oxide primer internally and externally including modular cover plates with frame i.e. inner and outer plate extended upto 25 mm over sunken box for housing the modular switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light/fan point contorlled by one switch ncluding 1.5 sqmm single core PVC insulated and unsheathed FRLS copper cable, 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor upto common earth and connecting to common earth dolly with suitable size of lugs for one light point/ fan point controlled by one switch complete all as specified and as directed. \nNotes :- Switch, socket and fan regulators to be measured and paid for separately. PVC Conduit confirming to IS 9537 part I & III. \nNote (All chases will be cut by chase cutter only) | | 1580 | Point |
| 3 | 3 | Description all as per Srl item No.02 here in before but for socket outlet point 5 Amp on Independent board. | | 290 | Point |
| 4 | 4 | Description all as per Srl item No.02 here in before but for socket outlet point 5 Amp on same board. | | 185 | Point |
| 5 | 5 | Description all as per Srl item No.02 here in before but one bell point controlled by one bell push. | | 30 | Point |
| 6 | 6 | Description all as per serial item No.02 above but with 2.5 sqmm cable for 3 pin 15 Amps switch socket outlet (Power point) complete all as specified and as directed. | | 260 | Point |
| 7 | 7 | Material and labour for concealed point wiring using approved colour coding as per IS, with multi stranded copper conductor 1.5 sqmm (Nominal area), single core, FRLS (Fire Retardant Low Smoke), PVC insulated and unsheathed stranded cable drawn through existing concealed conduit including 3mm thick decorative laminated sheet top cover 3mm thick Hylam including 1.5 sqmm single core PVC insulated and unsheathed FRLS cable, 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor upto common earth and connecting to common earth dolly with suitable size of lugs for one light point/ fan point controlled by one switch complete all as specified and as directed. Note :- Switch, socket, ceiling rose, lamp holder, fan regulators etc. to be measured and paid for separately) . | | 710 | Point |
| 8 | 8 | Description all as per Srl item No.07 here in before but for socket outlet point 5 Amp on Independent board. | | 135 | Point |
| 9 | 9 | Description all as per Srl item No.07 here in before but for socket outlet point 5 Amp on same board. | | 85 | Point |
| 10 | 10 | Description all as per serial item No.07 above but with 2.5 sqmm cable for 3 pin 15 Amps switch socket outlet (Power point) complete all as specified and as directed. | | 140 | Point |
| 11 | 11 | Supply and fixing switch piano 5 Amps, flush type, single pole, one way, 230 volt , AC supply, ISI Marked, complete all as specified and directed. | | 220 | Each |
| 12 | 12 | Supply and fixing switch piano, bell push, 6 Amps , flush type, 230V, 50 Hz supply, complete all as specified and as directed. | | 30 | Each |
| 13 | 13 | Supply and fixing switch piano 15 Amps, flush type, single pole, one way, 230 volt , AC supply, ISI Marked, complete all as specified and directed. | | 60 | Each |
| 14 | 14 | Supply and fixing socket outlet 3 pin 6 Amps, 230 volt. flush type complete all as specified and directed. | | 70 | Each |
| 15 | 15 | Supply and fixing socket outlet 2 in 1, 6 pin 5 /16 Amp and multi pin flush type, complete all as specified and directed. | | 60 | Each |
| 16 | 16 | Supply and fixing modular switches, one way, 6 amps one module, 230V, 50 Hz supply, complete all as specified and as directed. | | 2760 | Each |
| 17 | 17 | Supply and fixing modular switches, one way, 20 Amps, one module, 230 volt , AC supply, complete all as specified and directed. | | 340 | Each |
| 18 | 18 | Supply and fixing modular socket outlet 6 amps, 2/3 pin combined 2 module, 230 volt,complete all as specified and directed. | | 625 | Each |
| 19 | 19 | Supply and fixing modular socket outlet 16 amps,2/3 pin , combined 2 module, complete all as specified and as directed. | | 340 | Each |
| 20 | 20 | Supply and fixing fan regulator step type 2 module, complete all as specified and as directed. | | 165 | Each |
| 21 | 21 | Supply and fixing ceiling rose surface bakelite 65x50mm, 3 terminal complete all as specified and as directed. | | 1610 | Each |
| 22 | 22 | Supply and fixing lamp holder/angle holder , PVC/polycarbonate type with back plate suitable for batten fittings,complete all as specified and as directed. | | 680 | Each |
| 23 | 23 | Supply and fixing Bell electric , SP, ding dong type, 240V, ISI Marked complete all as specified. | | 30 | Each |
| 24 | 24 | Supply and fixing fan regulator/ Dimmer electronic step type , 120 watt ,2 module, 230 Volts, AC supply, suitable for ceiling fan any type/make/sweep complete all as specified and as directed. | | 20 | Each |
| 25 | 25 | Supply and fixing channel for fixing of LED tube rod, aluminium housing body in CRCA body suitable for 18/20 watt LED tube, high efficient, AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light including disconnecting and taking down existing light fitting and removal complete all as specified and directed. ( Tube rod shall be measured and paid for separately ). Make Havells Cat Part No LUMILINEPLUSBS18WLED865SPCSS/Wipro Cat Part No LL20-221-XXX65NE3/Philips Cat Part No TMC501 P 2XT-LED 22WP 3242 or equivalent make as specified in appendix 'B' in tender documents. | | 640 | Each |
| 26 | 26 | Supply and fixing 18 W LED tube rod, environment friendly, high efficient, T8 with aluminium extrusion heat sink for potimum performance with high luminous efficiency and easy and taking down existing tube and removal complete all as specified and directed. Make Havells Cat Part No CRYSTAL1213T8DSTL18WLED8655GLASS/Wipro Cat Part No LL13-181-650/Philips Cat Part No 18W865 T 81 or equivalent make as specified in appendix 'B' in tender documents. . | | 640 | Each |
| 27 | 27 | Supply and fixing decorative surface mounted LED tube light fitting with high efficient diffuser mirror light, aluminium housing in CRCA body suitable and including 10 watt LED tube high efficient, AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light including disconnecting and taking down existing light fitting and removal complete all as specified and directed.Make Havells Cat Part No LUMILINEPLUSBS10WLED865SPCSS/Wipro Cat Part No LW07-141-XXX-57-XX/Philips Cat Part No WT 202W LED65 CW PSU S2 or equivalent make as specified in appendix 'B' in tender documents. | | 30 | Each |
| 28 | 28 | Supply and fixing post top lantern LED 35W , cast aluminium spigot, with high effieient LED light, with poly carbonate diffuser, complete with high efficient LED lamp 30 W and accessories internally pre wired and including connecting up with three core 1.5 sqmm flexible copper conductor cable including disconnecting and taking down existing light fitting and removal complete all as specified and directed. Make Havells Cat Part No RUBYPT35LED757PSYMTOPO/Wipro Cat Part No LP02-501-XXX-57-XX/Philips Cat Part No BGP400 LED35L CW MR FG SI or equivalent make as specified in appendix 'B' in tender documents. | | 8 | Each |
| 29 | 29 | Supply and fixing bulk head light fitting, 10 watt, energy efficient with lamp 10 watt with provision of 2/3 core PVC copper conductor cable 0.5 Sqmm size from ceiling rose to light fitting complete including disconnecting and taking down existing light fitting and removal complete all as specified and directed. Make Havells Cat Part No HEXAFT10WLED857SSYMBO/Wipro Cat Part No LW07-141-XXX-57-XX/Philips Cat Part No WT 202W LED65 CW PSU S2 PC or equivalent make as specified in appendix 'B' in tender documents. | | 60 | Each |
| 30 | 30 | Supply and fixing LED security light luminaire 35 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP65 protection, better optics for uniform distribtion with multiplte LEDs not less than 2 W eachand having optical grade polycarbonate lens with all accessories internally pre wired and including connecting up with three core 1.5 sqmm flexible copper conductor cable from ceiling rose to connector of light including disconnecting and taking down existing light fitting and removal complete all as specified and directed.Make Havells Cat Part No ENDURACITYLINERLATPLUSSL35LED757SASYBOPC/Wipro Cat Part No LR13-501-XXX-57-XX/Philips Cat Part No BRPO 52 LED 036 CW HP SLA FG SIPSU GR or equivalent make as specified in appendix 'B' in tender documents. | | 110 | Each |
| 31 | 31 | Supply and fixing bracket for security light made up of 25 mm dia GI pipe 'Light' grade bent to required length, over all length0.90 mtr fixed to wall with two clamps made of 20 x 3 mm MS flat , 4 nos of bolts with nuts including taking down existing unserviceable bracket and removal complete all as specified and directed. | | 75 | Each |
| 32 | 32 | Supply and fixing MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, 'B' curve 6 to 32 Amps, ISI marked complete all as specified and directed. | | 244 | Each |
| 33 | 33 | Supply and fixing MCB double pole and neutral 240 volts, 16 to 32 Amps,10KA, 50 Hz, 'B' Series complete all as specified and as directed. | | 36 | Each |
| 34 | 34 | Supply and fixing MCB single pole and neutral 240 volts, 40 to 63 Amps,10KA, 50 Hz, 'B' Series complete all as specified and as directed. | | 10 | Each |
| 35 | 35 | Supply and fixing RCBO for earth leakage (IP-20) protection and overcurrent and short citcuit protection , ISI marked, 240 volts, 40 Amps, 300 ma sensitivity, DP complete all as specified and as directed. | | 20 | Each |
| 36 | 36 | Supply and fixing sheet metal enclosures for distribution board for MCB's Load line TPN, 4 ways,double door, 415 volts, with and including 200 Amps rated bus bar, vertical type IP 43, with MCCB as incomer and MCB's as out going , one MCCB 125 Amps, TPN, 25 KA microprocessor based as incommer and making all type of connections with suitable size of gland for incomer LT cable complete , concealed on the wall surface, making good the disturbed portion with adjoining surfaces to match with existing finish and taking down the existing DB's any type complete all as specified and as directed. | | 6 | Each |
| 37 | 37 | Supply , insatallation, testing of SPN distibution board 8 way,double door , IP 43 , as per IS 8623 including 200 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles all as specified and directed. | | 28 | Each |
| 38 | 38 | Supply , insatallation, testing of SPN distibution board 12 way,double door , IP 43 , as per IS 8623 including 100 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles all as specified and directed. | | 8 | Each |
| 39 | 39 | Material and labour for sheet metal enclosure SPN with two pin and earth plug and socket with one single pole MCB 32 Amps, complete all as specified and as directed. | | 20 | Each |
| 40 | 40 | Material and labour (in repair) for earthing complete with galvanised earth plate electrode 600mm x 600mmx 6mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 4mm dia galvanised Iron steel wire by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel covered with GI pipe 40 mm dia bore and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work, charcoal & salt in alternate layers, 20mm dia GI pipe (light grade) for watering, funnel, wire mesh, cast iron cover and frame, PCC type C-1 earth pit, etc., including testing on completion complete all as specified and directed. | | 18 | Each |
| 41 | 41 | Material and labour for sub main wiring with two single core FRLS (Fire Retardant Low Smoke), PVC insulated unsheathed copper conductor cable 6 sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLS of 6 sqmm,green colour for earth continuity conductor including including taking down old unserviceable sub main wiring and making good the disturbed surface complete, all as specified and directed.\nNOTE : - Three run of 6.0 sqmm cable with concealed conduct shall be measured as 1 unit.\n | | 760 | RM |
| 42 | 42 | Material and labour for sub main wiring with two single core FRLS (Fire Retardant Low Smoke), PVC insulated unsheathed copper conductor cable 4 sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLS of 4 sqmm,green colour for earth continuity conductor including including taking down old unserviceable sub main wiring and making good the disturbed surface complete, all as specified and directed.\nNOTE : - Three run of 4.0 sqmm cable with concealed conduct shall be measured as 1 unit.\n | | 450 | RM |
| 43 | 43 | Material and labour for sub main wiring with two single core FRLS (Fire Retardant Low Smoke), PVC insulated unsheathed copper conductor cable 2.5 sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLS of 2.5 sqmm,green colour for earth continuity conductor including including taking down old unserviceable sub main wiring and making good the disturbed surface complete, all as specified and directed.\nNOTE- Three run of 2.5 Sqmm cable with concealed conduct shall be measured as 1 unit.\n | | 410 | RM |