Military Engineer Services-MES has published Tender For Repair Maintenance Of Pump Sets Ats Apfc Panels Mccbs Pipe Lines And Other Connected Items For Water Supply Installation At Mil Stn Dagshai Under Ge Kasauli. Submission Date for this Tender is 19-08-2019. Power Factor Panel Tenders in DAGSHAI Himachal Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
---|---|---|---|---|---|
1 | 0.01 | Schedule 'A' Section - I | |||
2 | 1 | Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth and getting out in hard / dense soil complete all as specified and as directed. | 44 | Cum | |
3 | 2 | Removing surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed. | 0.5 | Cum | |
4 | 3 | Returning filling in trenches including spreading, leveling, watering and well ramming in layers n . Exc 25 cm complete all as specified. | 43.5 | Cum | |
5 | 4 | S & F GI tubing medium grade, ISI Marked conforming to IS 1239 Part-I 2004, 15mm bore with and including all fittings such as bends, elbows, tees, short length, socket, union, check nuts, nipples etc. fixed and laid in trenches/floor/under culvert/road crossing etc, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and as directed. \nMake: Jindal Pipes / Tata / BST /Prakash Tubes / OSWAL (Note: Exacavation and earhwork shall be measured and paid for separately.) | 48 | RM | |
6 | 5 | All as per Srl item No. 04.00 above but of size 20mm bore. | 48 | RM | |
7 | 6 | All as per Srl item No. 04.00 above but of size 25mm bore. | 48 | RM | |
8 | 7 | All as per item Srl No. 04.00 above but of size 40mm bore. | 42 | RM | |
9 | 8 | All as per Srl item No. 04.00 above but of size 50mm bore. | 30 | RM | |
10 | 9 | All as per Srl item No. 04.00 above but of size 80mm bore. | 30 | RM | |
11 | 10 | All as per Srl item No. 04.00 above but of size 100mm bore incl suitable size MS flanges for pipe line, Joints and jointing materials shall be included under this item as per site requirement. | 30 | RM | |
12 | 11 | All as per item serial No. 04.00 above but of size 150mm bore incl suitable size MS flanges for pipe line, Joints and jointing materials shall be included under this item as per site requirement. | 30 | RM | |
13 | 12 | S&F Bronze gate valve for 15mm bore pipe, with iron wheel head, screwed both ends for iron pipe and fixed, ISI marked conforming to IS 778 : 1984, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and as directed. Make : Kirloskar / Leader / Zoloto / L&T (Audco) / NVR | 15 | Each | |
14 | 13 | All as per Srl item No. 12.00 above but of size 20mm bore. | 12 | Each | |
15 | 14 | All as per Srl item No. 12.00 above but of size 25mm bore. | 10 | Each | |
16 | 15 | All as per Srl item No. 12.00 above but of size 40mm bore. | 8 | Each | |
17 | 16 | All as per Srl item No. 12.00 here-in-before but of size 50mm bore. | 4 | Each | |
18 | 17 | S & F 1000 litres capacity rotational moulded polyethylene water storage tanks (Cylindrical vertical with closed top) double layered (ISI Marked) conforming to IS 12701: 1996 hoisted and fixed in position, including ball brass valve 20mm bore, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and as directed. Make : Diplast Plastic Ltd / Sintex Industries / Aqua Polymers Pvt Ltd. | 1 | Each | |
19 | 18 | Supply and fixing cast iron Sluice valve PN 1:6 as per IS-14846, body, dome, wedge-CI IS:210, rings bronze IS:318, Spindle-SS IS-6603, Gland Packing gresy jute packing, fasteners-CS, Gasket-Natural rubber, Nominal size DN-150mm, both ends flanged in existing line, after removal of old unserviceable sluice valve without damaging to existing pipe line, after removal of old unserviceable sluice valve without damaging to existing pipe line, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and as directed by Engineer-in-charge. Note :- Suitable size flanges for existing pipe line, joints and jointing material shall be included under this item. \nMake : Kirloskar / Leader / Zoloto / L&T (Audco) | 2 | Each | |
20 | 19 | All as per Srl item No. 18.00 above but nominal size DN-100mm bore. | 2 | Each | |
21 | 20 | All as per Srl item No. 18.00 above but nominal size DN-80mm bore. | 1 | Each | |
22 | 21 | S&F Water meter 150 mm nominal bore conforming to IS:2373-1981 having CI casing bronze body and SS/Alloy/Bronze gear having dial duly marked with litres or kilolitres in boldface, thread/flanged end type with provision of strainer out side the meter, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and as directed . Make - Kranti/Deshmesh/L&T | 1 | Each | |
23 | 22 | All as per item serial No. 21.00 above but of size 100mm bore. | 1 | Each | |
24 | 23 | All as per item serial No. 21.00 above but of size 80mm bore. | 1 | Each | |
25 | 24 | Construction of brick masonary pit of size 120 x 120 x 120cm internal size with MS sheet 3mm thick and angle iron frame of size 40x40x6mm duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer including locking arrangement, lifting handle and including excavation / earth work, PCC in foundation, brick work, plaster including demolition of existing pit complete all as specified and shown in drawing No. STD- 1258, sheet 1/1. (original date - 30.11.93 and revised date - 15.09.2000) \nNote : Drawing mentioned above has not been enclosed herewith, however the same can be seen in the office of GE Kasauli. | 1 | Each Job | |
26 | 25 | Construction of brick masonary pit of size 90 x 90 x 90cm internal size with MS sheet 3mm thick and angle iron frame of size 40x40x6mm duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer including locking arrangement, lifting handle and including excavation / earth work, PCC in foundation, brick work, plaster including demolition of existing pit complete all as specified and shown in drawing No. STD- 1258, sheet 1/1. (original date - 30.11.93 and revised date - 15.09.2000) Note : Drawing mentioned above has not been enclosed herewith, however the same can be seen in the office of GE Kasauli. | 1 | Each Job | |
27 | 26 | Supplying, fixing and testing of high pressure, heavy duty cast steel gate valve, nominal size DN-150 mm, conforming to API 600, Class 600, suitable to hydrostatic test pressure for body 156 kg/sq cm & for seat 115 kg/sq cm, both ends flanged in existing line, after removal of old unserviceable gate valve without damaging to existing pipe line, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and directed by Engr-in-charge. Note : Suitable size MS flanges for existing pipe line, Joints and jointing materials shall be included under this item. Make : Kirloskar / L&T (Audco)/ Leader / Zoloto. | 1 | Each | |
28 | 27 | Supplying, fixing and testing of high pressure, heavy duty cast steel non return valve/ check valve, nominal size DN-150 mm, conforming to BS 1868, Class 600, suitable to hydrostatic test pressure for body 156 kg/sq cm & for seat 115 kg/sq cm, both ends flanged in existing line, after removal of old unserviceable non return valve without damaging to existing pipe line, fixed as in repair including dismentling taking down old unserviceable one complete all as specified and directed by Engr-in-charge. Note : Suitable size MS flanges for existing pipe line, Joints and jointing materials shall be included under this item. Make : Kirloskar / L&T (Audco)/ Leader / Zoloto. | 1 | Each | |
29 | 28 | Supply of calcium type chloride, 65%-70% chlorine content, high strength granular disinfectant for treatment of dirinking water complete all as specified and qty as per requirement and as directed by Engineer-in-charge. Make : Puri chlor brand of M/s Sree Rayalaseema Hi-strength Hypo Ltd / Aquafit or approved by E-in-C's Branch. | 180 | Kgs | |
30 | 29 | Disconnecting /unscrewing coupling for 125 HP pump set and seperating pump and motor, disconnecting all water connections from pump including suction and discharge pipe line and taking out the pump from base frame, transporting to workshop to carry out the necessary repairs and took back after repairs , installing on existing location, making all the connections carefully, commissioning and testing at site to the entire satisfaction of the Engr-in-Charge. Note: All the Spares/ parts/ job repairs required to be replaced shall be measured and paid seperately as under :- | 1 | Each Job | |
31 | 29.01 | Coupling Set suitable for 125 HP Pumpping set. | 1 | Set | |
32 | 29.02 | Replacement of Gland Sleeve. | 2 | Each | |
33 | 29.03 | Counter Plate stainless steel. | 1 | Each | |
34 | 29.04 | Diffuser Packing. | 12 | Each | |
35 | 29.05 | Impeller brazing machining and reboring. | 6 | Each | |
36 | 29.06 | New Key way of impeller disc. | 6 | Each | |
37 | 29.07 | Diffuser outer dia brazing and machining. | 6 | Each | |
38 | 29.08 | Impellers outer dia brazing and machining. | 6 | Each | |
39 | 30 | Taking out old unserviceable with replacement of pressure gaue upto 100 Kg/sqcm, complete all as speciified and as directed by Engineer-in-charge. | 2 | Each | |
40 | 31 | Taking out old unserviceable with replacement of ball bearing 6314, complete all as speciified and as directed. Make: SKF/ NBC | 2 | Each | |
41 | 32 | All as per Srl item No 31.00 above but bearing 6315. | 2 | Each | |
42 | 33 | All as per Srl item No 31.00 above but bearing NU 315. | 2 | Each | |
43 | 34 | All as per Srl item No 31.00 above but bearing NU 308. | 2 | Each | |
44 | 35 | All as per Srl item No 31.00 above but bearing NU 307. | 2 | Each | |
45 | 36 | Disconnecting /unscrewing Auto Transformer Starter Panel of capacity 125 /150/ 250 HP, disconnecting all electric connections and carrying out necessary repair at site with replacement of parts as under complete all as specified including testing at site to the entire satisfaction of the Engr-in-Charge. Note: All the Spares/ parts/ job repairs required to be replaced shall be measured and paid as under : | 5 | Each Job | |
46 | 37 | Electronic over current relay cap 0.5 – 60A 220V AC complete with arrangement for over current, phase reversal, under current and phase imbalance protection suitable for 250 HP ATS Panel complete all as speciified and as directed by Engineer-in-charge. Make: BCH Model : BOCR FDE K12334032 or equivalent in L&T/Schneider | 1 | Each | |
47 | 38 | Electronic over current relay cap 0.5 – 60A 220V AC complete with arrangement for over current, phase reversal, under current and phase imbalance protection suitable for 150 HP ATS Panel complete all as speciified and as directed by Engineer-in-charge. Make: BCH Model : BOCR FDE S611090 or equivalent in L&T/Schneider | 1 | Each | |
48 | 39 | Electronic over current relay cap 0.5 – 60A 220V AC complete with arrangement for over current, phase reversal, under current and phase imbalance protection suitable for 125 HP ATS Panel complete all as speciified and as directed by Engineer-in-charge. Make: BCH Model : BOCR FDE VJ16064003 or equivalent in L&T/Schneider | 1 | Each | |
49 | 40 | Three pole power contactor, AC Control, AC3 Rating 95A/ 47 KW, 415V complete with auxillary contact heavy duty suitable for pumping set opeartion including taking out existing unserviceable power contactor and removal from site complete all as speciified and as directed by Engineer-in-charge. Make : BCH Electric/C&S Electric/Standard/ Indoasian/Havells/HPL | 1 | Each | |
50 | 41 | All as per Srl item No 40.00 above but rating cap 140A/75 KW, 415V. | 1 | Each | |
51 | 42 | All as per Srl item No 40.00 above but rating cap 200A/110 KW, 415V. | 1 | Each | |
52 | 43 | All as per Srl item No 40.00 here in before but rating cap 265A/140 KW, 415V. | 1 | Each | |
53 | 44 | All as per Srl item No 40.00 here in before but rating cap 300A/160 KW, 415V. | 1 | Each | |
54 | 45 | Dismantling and supply, install , connect, test and commssion , 3 phase, heavy duty, explosion proof, self healing capacitor cylinerical type confirming to IS 13340 of following ratings. Make : EPCOS/CG/DUCATI/UNIVERSAL (UNISTAR)/C&S Electric/ Havells/BCH/GE | |||
55 | 45.01 | 5 KVAr heavy duty. | 2 | Each | |
56 | 45.02 | 10 KVAr heavy duty. | 2 | Each | |
57 | 45.03 | 15 KVAr heavy duty. | 2 | Each | |
58 | 46 | M & L for repairing/ servicing of APFC panel board of cap 175 KVAR by replacing the all defective components with new components, re wiring, cleaning, testing, reconnecting, re- installing and commissioning the APFC panel board complete all as directed by Engineer-In-charge. Note:- (i) Supply of cables, wires & other minor spare parts etc. will deemed to be included in the quoted rate. | 1 | Job | |
59 | 47 | Supply and fix the following switch gear/components in various APFC Panels installed at sub station/pump houses :- \nMake - C&S Electric/BCH/Indoasian/Havells/Crompton/Anchor/ GE Power/HPL/Standard Electricals | |||
60 | 47.01 | MCCB, 16A TP, 25 KA. | 2 | Nos | |
61 | 47.02 | MCCB, 25A TP, 25 KA. | 2 | Nos | |
62 | 47.03 | LED type Red/Yellow/Blue Indicating Lamps. | 2 | Nos | |
63 | 48 | S & F MCCB 630 Amps 4 Pole, 36 KA, 415 V, 50 Hz with thermal setting between 70% to 100% adjustable type and connecting up in the existing panel location including taking out existing unserviceable MCCB complete all as specified and as directed by Engineer-in-Charge. Make- ABB/Siemens/L&T/Schneider/Legrand/Merlin Gerin/Hager | 1 | Each | |
64 | 49 | All as per Srl item No 48.00 above but MCCB 400 Amps 4 Pole, 36 KA, 415 V, 50 Hz. | 1 | Each | |
65 | 50 | All as per Srl item No 48.00 above but MCCB 250 Amps 4 Pole, 36 KA, 415 V, 50 Hz. | 1 | Each | |
66 | 51 | All as per Srl item No 48.00 above but MCCB 200 Amps 4 Pole, 36 KA, 415 V, 50 Hz. | 1 | Each | |
67 | 52 | All as per Srl item No 48.00 above but MCCB 100 Amps 4 Pole, 36 KA, 415 V, 50 Hz. | 1 | Each | |
68 | 53 | S & F on load change over switch, four pole with advance neutral 400 Amps, 415 V, 50 Hz conforming to IS : 13947 Part-3 connecting up in the existing panel location including taking out existing unserviceable change over switch complete all as specified and as directed by Engineer-in-charge. Make : L&T / ABB / Schneider/Siemens | 1 | Each | |
69 | 54 | Supply, laying, jointing and testing replacement PVC insulated cable 1100 volt grade with multi stranded, single core copper 150 Sqmm, Grade As Per IS 7098 (Part 1) 1988 including making electrical connection for main panel, to starter and starter to motor in pieces of suitable length as per site requirement duly fixed with suitable size of coper lugs/thimbles complete all as specified and as directed by Engr-in-charge. Make : L&T/Finolex/RPG/RR Kabel/Grandley | 50 | RM | |
70 | 55 | All as per Srl item No 54.00 above but single core copper cable 120 Sqmm. | 40 | RM | |
71 | 56 | M & L for taking out old unserviceable with supply, laying, fixing Double walled corrugated HDPE duct pipe of 50mm outer dia confirming to IS-14930 (Part-II) of approved colout with fittings for cable protection complete all as directed. Make - Dutron/Finolex/Tirupati/SFMC/Jain pipe/Swastik / Telerex / Reliance (RPPPL) | 30 | RM | |
72 | 57 | Dismetling and taking down old/unsv ACSR conductor any size complete all as specified and as directed. | 2 | Qtl | |
73 | 58 | S & F ACSR conductor incl jointing with existing conductor and straining on LT pole and proper fastening to pin/shackle insulators with aluminium binding wires and required jumpering connection complete all as specified. Note :- Size of aluminium conductor as per site requirement will be directed by Engineer-in-Charge. Make : Jaipuria / Diomond / Bharat Conductors | 2 | Qtl | |
74 | 59 | M & L for restraining of overhead ACSR conductor of any size of 5 conductor on pole after disconnecting all jumpering connection & binding of insulators and redoing all jumpering connection and insulator binding with aluminium conductor providing required T&P complete all as specified. | 850 | RM | |
75 | 60 | M & L for restraining of ACSR conductor of any size of 2 conductor on pole after disconnecting all jumpering connection & binding of insulators and redoing all jumpering connection and insulator binding with aluminium conductor providing required T&P all as specified. | 500 | RM | |
76 | 61 | S & F 1100 volts grade heavy duty flat twin core cable PVC insulated with stranded aluminium conductor of size 10 sqmm and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension GI wire from OH conductor to building incl dismentling taking down unserviceable one complete all as specified and as directed. Make : Havells/Polycab/HPL/Grandley/ Gloster/Kalinga/Plaza | 400 | RM | |
77 | 62 | S & F 1100 volts grade heavy duty flat twin core cable PVC insulated with stranded aluminium conductor of size 6 sqmm and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension GI wire from OH conductor to building incl dismentling taking down unserviceable one complete all as specified and as directed. Make : Havells/Polycab/HPL/Grandley/ Gloster/Kalinga/Plaza | 350 | RM | |
78 | 63 | M & L for painting of steel tubular pole with one coat of alumium paint incl cross arm, bracings, supports, nuts, bolts, of LT OH line from above copping to top of pole and marking with alternate white and black paint strip 30 cm wide (5 Nos) with synthetic enamelled paint including marking of Pole Number with letter like " MES LT No " complete all as specified and as directed. | 100 | Each | |
79 | 64 | M & L for trimming of branches of trees touching LT electric over head line and making clear about 3 mtr in radius by climbing up tree or by providing ladder, at a height 7 mtr and above and carrying and depositing where directed not exceeding 50 mtr complete all as specified. | 20 | Per 100 Mtr | |
80 | 65 | Dismentling taking down unserviceable flood/stree/gate light fitting any type any make any capacity from Pole/Building for replacement complete all as specified and as directed. | 15 | Each | |
81 | 66 | S & F LED Street light fitting 72 Watt new generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP66 road luminaire with high power LEDs as light source and electronic driver complete all as specified. Make - Crompton cat part No LSTP-72-CDL or eqivalent in Philips / Bajaj / Osram / Polycab | 5 | Each | |
82 | 67 | S & F LED Street light fitting 90 Watt new generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP66 road luminaire with high power LEDs as light source and electronic drivercomplete all as specified. Make - Crompton cat part No LSTN-90-CDL-A or eqivalent in Philips / Bajaj / Osram /Polycab | 8 | Each | |
83 | 68 | S & F Post top energy saving, environmental friendly, aesthetically designed with indirect symmetrical light distributio, die-cast aluminium IP-65 luminaire with high power COB LED as light source of capacity 40 Watt, 6500K complete all as specified and as directed by Engr-in-charge. Make - Crompton cat part No LPTO-40-CDL or eqivalent in Philips / Bajaj / Osram /Polycab | 2 | Each | |
84 | 69 | Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground (earth pit nbot less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below notmal ground level, connected to galvanised iron earth strip 32x6mm upto test point with suitable GI nuts/bolts and brazed properly up to main board including earth pit in cement concrete 1:2:4 type B-1, precast RCC cover in 1:2:4 reinforced with expanded metal, with suitable handle, excavation and earth work in any type of soil and including medium grade GI watering pipe 25mm bore with funnel wire mesh and medium grade GI wire protection pipe 50mm bore up to main board completew as shown in electrical plate No 3 of MES schedule Part-I 2009, connected to earthing testing point including taking out existing unsv earthing complete ass as specified and testing on completion complete all as specified and as directed by Engineer-in-charge. Note - The units rate including the cost of excavation & earth work in any type of soil, charcoal & salt in alternate layers, 25mm GI pipe (light grade) for watering 50mm GI protection pipe (light grade) funnel wire mesh PCC chamber in PCC 1:3:6 type C-1 cast iron frame and 40mm thick RCC cover for pit etc & no extra payment will be made. | 10 | Each Set | |
85 | 70 | Taking down old unservisable and S &F for battary 12 V 180 Ah maintenance free. Make : Exide /TATA/Amron \nExide Modal No. FXPO-XP1800/Tata Green Modal No. 182H52 CV 180AH/Amaron Modal No. HC180D04R | 4 | Each | |
86 | 71 | S & F Galvanised iron strips 32x6 mm burried in an underground/fixing along pole/wall etc including with insulators, screw, saddle etc required as per site requirement incl dismentling and taking down unsv one complete all as specified and as directed. | 50 | RM | |
87 | 72 | Amount of credit of Rs. 30407.00 for retrived old material as mentioned in Schedule 'A' section-II of tender document in pdf form, will be deducted offline while acceptence of tender. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy