Construction Of Modern Factory Cum Lab For Homco At Valiyakalavoor , Alappuzha-Electrical Works As Per Cgmp Norms
Tender Value
4.20 Crore
Estimated cost
Bid Submission
14 Aug 2019
0 days left
EMD
1 Lakhs
Bank guarantee accepted
Document Fee
8400
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
HOMCO, Valiya Kalavoor, Alappuzha, Kerala → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Construction Of Modern Factory Cum Lab For Homco At Valiyakalavoor , Alappuzha-Electrical Works As Per Cgmp Norms
BOQ
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
|---|---|---|---|---|---|
| 1 | 1 | APPENDIX A EB RECEIVING, METERING & CONSUMER RECEIVING | |||
| 2 | 1.01 | EB RECEIVING :- RING MAIN UNIT:-Supply, Installation, testing and commissiong of 1 No. 11KV, 630A, Motor Operator, Compact outdoor type extensible RING MAIN UNIT with vacuum circuit breaker and CTC(E) as per the Electrical Inspectrate/KSEB Technical specifications and standards both side extensible non drawout type gas insulated RMU. The RMU consists of 3 Nos of 630A, 25KA Air Braker/Load breaker/Isolator with suitably inter locked earth switch. The rate is inculssive of all taxes and duties and transportation insurance, lift lead and position and supervision charges, testing charges. The associated civil works for positioning the RMU with suitable RCC foundation etc complete as referred. | item1 | 1 | Set |
| 3 | 1.02 | EB METERING :- Supply, installation & testing commissioning of Outdoor type 11KV HT meter panel HT CT & PT, TTB, Wiring etc. complete in all respects (11KV HT Electronic Trivector Meter Will be Supplied by Local Electricity Board) | item2 | 1 | Set |
| 4 | 1.03 | Consumer Receiving - 11KV VCB :- Supply, Unloading, shifting, Installation, Testing and Commissioning of Outdoor Type, 11KV HT PANEL , Indoor/Outdoor Type suitable for 11KV, 630A, 350 mva, 3PHASE, 50 Hz, consisting of single 11KV Vaccum Circuit Breakers & Panel Boards made of sheet steel clad dust & vermin proof , free floor standing incluiding existinng base channels etc., with all accessories like power pack/battery charger as required for satisfactory operation in compliance with the statutory Electrical authorities and RRL Technical specifications. | item3 | 1 | Set |
| 5 | 1.04 | Package SUBSTATION 11KV/ 1250 kVA DRY Type/INDOOR Type :- Supply, Unloading, shifting, Installation, Testing and Commissioning of 11KV PACKAGE SUBSTATION Indoor / Outdoor Type suitable for 11KV, 630A, 350 mva, 3PHASE, 50 Hz, consisting of single 11KV Vaccum Circuit Breakers, 1250 kVA Transformer & Panel Boards made of sheet steel clad dust & vermin proof , free floor standing incluiding existinng base channels etc., with all accessories like power pack/battery charger as required for satisfactory operation in compliance with the statutory Electrical authorities & Specfications (Note: Contractor should quote along with Foundation works)\n | item4 | 1 | Set |
| 6 | 2 | H.T. CABLE:- Supply and Laying of HT-XLPE insulated FR PVC outer sheathed, inner extruded PVC SHEATH, 3CORE, ARMOURED, stranded ALUMINIUM conductor cables of cables per IS. The cable shall either be 'laid 'in trench 1.1 M wide 0.75m deep / RCC 'Hume pipe of size 250mm / ready-made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tags shall be of aluminium engraved sheets (2mm)tied at regular intervals of not less than 10mtrs. | |||
| 7 | 2.01 | 3C X 300 Sq. mm 11KV Earthed XLPE Aluminium Armoured cable. :- Supplying, termination, testing and commissioning of following indoor/outdoor type cable end termination suitable for 11 KV (E) aluminum conductor XLPE cable with heat shrinkable jointing kit, cable lugs etc. complete as required. | item5 | 350 | Mtr |
| 8 | 2.02 | 3C x 300 sq.mm. XLPE insulated Al. Ar. Cable (Outdoor Type) | item6 | 1 | Nos |
| 9 | 2.03 | 3C x 300 sq.mm. XLPE insulated Al. Ar. Cable (Indoor Type) | item7 | 3 | Nos |
| 10 | 2.04 | Preparation of TRENCH for cable laying in 1.0m deep x 500mm wide; with 100mm sand cushioning above and below the cable: 450L X 175W X 35Hmm RCC tiles inclusive of excavation work. | item8 | 200 | Mtr |
| 11 | 3 | RESIN CAST BUSDUCT :- Supplying, Installing, Suspension Testing & Commissioning of 2500A, Indoor, Sandwich type Aluminium bus duct for use on 3 Phase, 4 Wire, 415 Volts, 50Hz AC supply with metal clad enclosures made of 2 mm thick steel sheet duly powder coated in convinent section complete with 4 Nos. Aluminium bus bars, necessary joints, elbow joints and, expansion joints, fire barriers at regular interval of 3 Meter, Continuous earthing with two nos. Copper strip of suitable size (one on each side) as required. Between Package Substation to Main LT Panel. Sandwich type Aluminium Busduct between (IP 65 ) | |||
| 12 | 3.01 | Straight Length | item9 | 10 | Mtr |
| 13 | 3.02 | Vertical Bends | item10 | 2 | Nos |
| 14 | 3.03 | Horozontal Bends. | item11 | 2 | Nos |
| 15 | 3.04 | Flange End. | item12 | 2 | Nos |
| 16 | 3.05 | Adopter Boxes. | item13 | 2 | Nos |
| 17 | 3.06 | Copper Flexible. | item14 | 5 | Mtr |
| 18 | 3.07 | Suitable size flexible braided copper | item15 | 2 | Mtr |
| 19 | 4 | DIESEL GENERATOR SET:- Supply, Installation, testing and commissioning of following capacity of three phase D.G. Set with standard specification and Acoustic Enclosure on the foundation provided near the Substation. (Civil works for the foundation will be done by the Owner). Engine: - 6 cylinder, In-line, 4 stroke, radiator cooled engine,?? Full Authority Electronic Engine ? Well designed air handling system with — Dry type, Replaceable paper element air cleaner with restriction indicator — Air to air aftercooling — Optimised turbocharger for increased altitude capabilities ? Best in class fuel economy with — Modular Commom Rail (MCRS) fuel system with A1 class electronic governing — Dual fuel filter system: Pre filter including water separator and Water In Fuel (WIF) sensor and main filter ?? Standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature ?? Venturi combo spin on lube oil filter ?? Plate type lube oil cooler ?? First fill of lube oil and coolant ?? Electrical starter motor with soft start engagement feature ?? Battery charging alternator 2 x 12 V DC atteries. Alternator:-?Brushless Type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-1 ?? 3 Phase reconnectable winding with 12 terminals brought out for connection ?? Better motor starting capability ?? Best in class efficiency Compact design with sealed bearings for longer life and lesser maintenance Impregnation on all wound components for better mechanical strength . Control Panel : - Engine monitoring and annunciation Panel | |||
| 20 | 4.01 | 500 kVA | item16 | 1 | Nos |
| 21 | 4.02 | 750 kVA | item17 | 1 | Nos |
| 22 | 5 | Exhaust Piping | |||
| 23 | 5.01 | Supply & installation of 10\" Class B Pipe including flanges, nuts bolts & Gaskets after silencer. | item18 | 15 | Mtr |
| 24 | 5.02 | Supply & installation of 8\" Class B Pipe including flanges, nuts bolts & Gaskets after silencer. | item19 | 15 | Mtr |
| 25 | 5.03 | Supply & installation of 50 mm thk. Insulation with rockwool density-64 kg/m3 and 24 guage aluminium cladding for above exhaust pipe | item20 | 30 | Mtr |
| 26 | 5.04 | Structural Steel support to support the exhaust pipes upto about 15 mtrs stack height with necessary steel. The final resposibility of the stability of the structure shall remain with the vendor.\nThe DG stack is proposed to be self standing chimney. The necessary steel structure to support the chimney including frame is included in the scope of works. Vendor to submit the drawing showing the arrangement for support of structure.\n(The approximate height of the stack is 15 Mts) | item21 | 2500 | Kg |
| 27 | 6 | MAIN LT PANEL & SUB PANELS :-Fabrication, conveyance, supply, installation, testing and commissioning of self-supported, free standing powder coated cubicle type, 415V, 36 kA Switch Board of CRCA No.14/16 gauge sheet steel construction with cable entry facility at top/bottom. Cable alley, switchgear compartment, meter chamber, bus bar chamber etc. shall be fully segregated & compartmentalized. Shrouding of live parts shall be with 3 mm FRP and two fastener screws and chamber partition at dropper connections with 3 mm FRP. Control wiring shall be with 2.5 sq. mm copper cable of 1100 volt grade for CT leads and 1.5 sq. mm for voltage leads with 2A SP MCB. All meters, connectors, lamps etc. shall have safe finger proof terminals. Doors shall be provided with 4 sq. mm flexible copper and socketed earth leads of green/green and yellow stripped PVC insulation. All copper joints shall be tinned. Knock- outs of proper diameter shall be provided on glanding plates. Ring type CTs shall be rigidly fixed to the cable chamber walls so that socketed cable cores can be easily taken through the CTs. The height of the operating handle of any switch gear shall not be more than 1.8 metres or less than 0.6 metres from bottom level of the switch board. All MCCB's are rotary operated handle with spreader terminals. Painting : Powder coated after seven tank metal treatment. Colour - Admiralty Grey as per I.S.S (RAL 7032). Enclosure : Degree of Protection - IP 54 or above. Doors / Cover : Doors with concealed hinges & bolted cover for bus chamber.Labelling : All incomers and outgoings shall be labelled. PVC identification ferrule numbers shall be used for all internal wiring. The panel manufactrere shoud have CPRI and ISO certification. MAIN LT PANEL:- | |||
| 28 | 6.01 | CRCA Sheet 2mm thickness | item22 | 780 | Sqft |
| 29 | 6.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item23 | 63850 | Cu.Cm |
| 30 | 6.03 | KSEB Incomer : 2000A, 50kA, 4P, EDO Microproceesor based ACB with all protections restricted Earth fault relay, under and over voltage protection relays. | item24 | 1 | Nos |
| 31 | 6.04 | Earth Fault Relay with control accessories | item25 | 1 | Nos |
| 32 | 6.05 | REF Relay with suitable ID/Class resin cast CT | item26 | 1 | Nos |
| 33 | 6.06 | Multi Function Meter with RS 485 port | item27 | 1 | Nos |
| 34 | 6.07 | Ammeter with suitable ID/Class resin cast CT | item28 | 1 | Set |
| 35 | 6.08 | RYB Indication with control MCBs | item29 | 1 | Set |
| 36 | 6.09 | DG1 Incomer : 1250A, 50kA, 4P, EDO Microproceesor based ACB | item30 | 1 | Nos |
| 37 | 6.1 | Control Relays and metering equipments for GCP as per standard | item31 | 1 | Set |
| 38 | 6.11 | Multi Function Meter with RS 485 port | item32 | 1 | Set |
| 39 | 6.12 | suitable ID/Class resin cast CT | item33 | 1 | Set |
| 40 | 6.13 | DG2 Incomer : 800A, 50kA, 4P, EDO Microproceesor based ACB | item34 | 1 | Nos |
| 41 | 6.14 | Control Relays and metering equipments for GCP as per standard | item35 | 1 | Set |
| 42 | 6.15 | Multi Function Meter with RS 485 port | item36 | 1 | Set |
| 43 | 6.16 | suitable ID/Class resin cast CT | item37 | 1 | Set |
| 44 | 6.17 | Bus Coupler : 2000A, 50kA, 4P, EDO Thermal magnetic rels ACB | item38 | 1 | Nos |
| 45 | 6.18 | PLC based AMF with load sharing System | item39 | 1 | Set |
| 46 | 6.19 | Outgoings : 1000A, 4P, 50kA ACB Thermal rels | item40 | 2 | Nos |
| 47 | 6.2 | 630A, 4P, 50kA MCCB Thermal rels | item41 | 1 | Nos |
| 48 | 6.21 | 400A, 4P, 50kA MCCB Thermal rels | item42 | 5 | Nos |
| 49 | 6.22 | 2000/5A, CL:1, 10/15VA, resin cast CT (APFC) | item43 | 1 | Nos |
| 50 | 6.23 | Earth Bus : 32 X 6 mm Copper | item44 | 6 | Mtr |
| 51 | 6.24 | 25 X 6 mm Copper | item45 | 3 | Mtr |
| 52 | 6.25 | 25 X 3 mm Copper | item46 | 3 | Mtr |
| 53 | 6.26 | 100 X 50MM C Channel MS | item47 | 15 | Mtr |
| 54 | 6.27 | Surge Protection Device:- The panel include pluggable type surge arrestor including additional DIN rail bar Class B+C / Class 1 + 2 as per IEC 61643 (IP 20) with potential free contact, thermal disconnector and provission for inbuilt common remote indication for defective arrestor to connect between lin and neutral and 1No. arrestor spark gap type to connect between neutral and earth of following ratng including base element and pluggable arrestors. Terminal voltage 230V, 50Hz, Type single MOV with builtin thermal fuse and cooling Gel (L - N) and spark gas encapsilated or non exhausting ( N - E). Lightning impulze current 37.5kA. (Make OBO Betterman or Mitsubishi) The Surge Protection Device should be installed in ROHS complied, distribution box, 5 division units, emty dimensions 190 x 150 x 125mm. | item48 | 3 | Nos |
| 55 | 7 | HVAC PANEL | |||
| 56 | 7.01 | CRCA Sheet 2 mm thickness | item49 | 200 | Sqft |
| 57 | 7.02 | CRCA Sheet 1.6 mm thickness | item50 | 95 | Sqft |
| 58 | 7.03 | Heat Shrinkable Sleeved Aluminium Bus bar | item51 | 33370 | Cu.Cm |
| 59 | 7.04 | Incomer : 1000A, 4P, 50kA ACB Thermal rels | item52 | 1 | Nos |
| 60 | 7.05 | Multi Function Meter with suitable rating resin cast CT | item53 | 1 | Set |
| 61 | 7.06 | RYB Indication with control MCBs | item54 | 1 | Set |
| 62 | 7.07 | Outgoings : 400A, TP, 35kA MCCB Thermal rels | item55 | 3 | Nos |
| 63 | 7.08 | 250A, TP, 35kA MCCB Thermal rels | item56 | 3 | Nos |
| 64 | 7.09 | 200A, TP, 35kA MCCB Thermal rels | item57 | 2 | Nos |
| 65 | 7.1 | 160A, TP, 35kA MCCB Thermal rels | item58 | 2 | Nos |
| 66 | 7.11 | 75 X 40MM C Channel MS | item59 | 8 | Mtr |
| 67 | 7.12 | Earth Bus : 25 X 6 mm Copper | item60 | 2 | Mtr |
| 68 | 7.13 | 25 X 3 mm Copper | item61 | 4 | Mtr |
| 69 | 8 | POWER SWITCH BOARD - ( PSB ) | |||
| 70 | 8.01 | CRCA Sheet 1.6mm thickness | item62 | 115 | Sqft |
| 71 | 8.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item63 | 9615 | Cu.Cm |
| 72 | 8.03 | Incomer : 1000A, 4P, MCCB without release | item64 | 1 | Nos |
| 73 | 8.04 | Multi Function Meter with suitable rating resin cast CT | item65 | 1 | Set |
| 74 | 8.05 | RYB Indication with control MCBs | item66 | 1 | Set |
| 75 | 8.06 | Outgoings : 400A, 4P, 35kA MCCB Thermal rels | item67 | 1 | Nos |
| 76 | 8.07 | 300A, TP, 35kA MCCB Thermal rels | item68 | 1 | Nos |
| 77 | 8.08 | 200A, TP, 35kA MCCB Thermal rels | item69 | 5 | Nos |
| 78 | 8.09 | 100A, TP, 35kA MCCB Thermal rels | item70 | 1 | Nos |
| 79 | 8.1 | 75 X 40MM C Channel MS | item71 | 8 | Mtr |
| 80 | 8.11 | Earth Bus : 25 X 3 mm Copper | item72 | 5 | Mtr |
| 81 | 9 | AHU MAIN PANEL | |||
| 82 | 9.01 | CRCA Sheet 1.6mm thickness | item73 | 120 | Sqft |
| 83 | 9.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item74 | 5850 | Cu.Cm |
| 84 | 9.03 | Incomer : 400A, TPN, MCCB without release | item75 | 1 | Nos |
| 85 | 9.04 | Multi Function Meter with suitable rating resin cast CT | item76 | 1 | Set |
| 86 | 9.05 | RYB Indication with control MCBs | item77 | 1 | Set |
| 87 | 9.06 | Outgoings : 200A, TP, MCCB Thermal rels | item78 | 6 | Nos |
| 88 | 9.07 | 75 X 40MM C Channel MS | item79 | 7 | Mtr |
| 89 | 9.08 | Earth Bus : 25 X 3 mm Copper | item80 | 3 | Mtr |
| 90 | 10 | UTILITY PANEL | |||
| 91 | 10.01 | CRCA Sheet 1.6mm thickness | item81 | 120 | Sqft |
| 92 | 10.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item82 | 5700 | Cu.Cm |
| 93 | 10.03 | Incomer : 400A, TPN, MCCB without release | item83 | 1 | Nos |
| 94 | 10.04 | Multi Function Meter with suitable rating resin cast CT | item84 | 1 | Set |
| 95 | 10.05 | RYB Indication with control MCBs | item85 | 1 | Set |
| 96 | 10.06 | Outgoings : 200A, TP, MCCB Thermal rels | item86 | 1 | Nos |
| 97 | 10.07 | 100A, TP, MCCB Thermal rels | item87 | 2 | Nos |
| 98 | 10.08 | 63A, TP, MCCB Thermal rels | item88 | 5 | Nos |
| 99 | 10.09 | 200A, TPN, MCCB without release | item89 | 4 | Nos |
| 100 | 10.1 | 75 X 40MM C Channel MS | item90 | 8 | Mtr |
| 101 | 10.11 | Earth Bus : 25 X 3 mm Copper | item91 | 7 | Mtr |
| 102 | 11 | PUMP PANEL | |||
| 103 | 11.01 | CRCA Sheet 1.6mm thickness | item92 | 70 | Sqft |
| 104 | 11.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item93 | 1570 | Cu.Cm |
| 105 | 11.03 | Incomer : 160A, TPN, MCCB without release | item94 | 1 | Nos |
| 106 | 11.04 | RYB Indication with control MCBs | item95 | 1 | Set |
| 107 | 11.05 | Outgoings : 63A, TP, MCCB Thermal rels | item96 | 7 | Nos |
| 108 | 11.06 | 25A, TP MCCB Thermal rels | item97 | 1 | Nos |
| 109 | 11.07 | 75 X 40MM C Channel MS | item98 | 6 | Mtr |
| 110 | 11.08 | Earth Bus : 25 X 3 mm Copper | item99 | 4 | Mtr |
| 111 | 12 | AHU PANEL 1-3 | |||
| 112 | 12.01 | CRCA Sheet 1.6mm thickness | item100 | 500 | Sqft |
| 113 | 12.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item101 | 10860 | Cu.Cm |
| 114 | 12.03 | Incomer : 200A, TPN, Isolator | item102 | 4 | Nos |
| 115 | 12.04 | RYB Indication with control MCBs | item103 | 4 | Set |
| 116 | 12.05 | Outgoings : 100A, TPN, MCCB Thermal rels | item104 | 8 | Nos |
| 117 | 12.06 | 32A, TPN MCCB Thermal rels | item105 | 1 | Nos |
| 118 | 12.07 | 63A, TPN MCCB Thermal rels | item106 | 2 | Nos |
| 119 | 12.08 | 75 X 40MM C Channel MS | item107 | 17 | Mtr |
| 120 | 12.09 | Earth Bus : 25 X 3 mm Copper | item108 | 20 | Mtr |
| 121 | 13 | COMPRESSOR PANEL | |||
| 122 | 13.01 | CRCA Sheet 1.6mm thickness | item109 | 70 | Sqft |
| 123 | 13.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item110 | 1800 | Cu.Cm |
| 124 | 13.03 | Incomer : 200A, TPN, MCCB without release | item111 | 1 | Nos |
| 125 | 13.04 | RYB Indication with control MCBs | item112 | 1 | Set |
| 126 | 13.05 | Outgoings : 125A, TPN, MCCB Thermal rels with 40kW Star Delta Starter with remote PB | item113 | 1 | Set |
| 127 | 13.06 | 100A, TPN, MCCB Thermal rels with 20kW Star Delta Starter with remote PB | item114 | 1 | Set |
| 128 | 13.07 | 63A, TPN MCCB Thermal rels with provision for fixing Star Delta Starter | item115 | 2 | Set |
| 129 | 13.08 | 75 X 40MM C Channel MS | item116 | 5 | Mtr |
| 130 | 13.09 | Earth Bus : 25 X 3 mm Copper | item117 | 3 | Mtr |
| 131 | 14 | APFC PANEL - 300kVAr | |||
| 132 | 14.01 | CRCA Sheet 1.6mm thickness | item118 | 215 | Sqft |
| 133 | 14.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item119 | 3430 | Cu.Cm |
| 134 | 14.03 | Incomer : 630A, TPN, MCCB without release | item120 | 1 | Nos |
| 135 | 14.04 | Multi Function Meter with suitable rating resin cast CT | item121 | 1 | Set |
| 136 | 14.05 | RYB Indication with control MCBs | item122 | 1 | Set |
| 137 | 14.06 | Inteligent Power Factor correction Relay 12 STAGE | item123 | 1 | Nos |
| 138 | 14.07 | Outgoings : 125A, TP, MCCB Thermal rels | item124 | 2 | Nos |
| 139 | 14.08 | 63A, TP, MCCB Thermal rels | item125 | 7 | Nos |
| 140 | 14.09 | 32A, TP, MCCB Thermal rels | item126 | 3 | Nos |
| 141 | 14.1 | Capacitor duty contactor suitable for 50kVAr Heavy duty gas filled Capacitor. | item127 | 2 | Nos |
| 142 | 14.11 | Capacitor duty contactor suitable for 25kVAr Heavy duty gas filled Capacitor. | item128 | 4 | Nos |
| 143 | 14.12 | Capacitor duty contactor suitable for 20kVAr Heavy duty gas filled Capacitor. | item129 | 3 | Nos |
| 144 | 14.13 | Capacitor duty contactor suitable for 15kVAr Heavy duty gas filled Capacitor. | item130 | 2 | Nos |
| 145 | 14.14 | Capacitor duty contactor suitable for 10kVAr Heavy duty gas filled Capacitor. | item131 | 1 | Nos |
| 146 | 14.15 | 50kVAr Heavy duty gas filled Capacitor and 7% series copper type reactor | item132 | 2 | Set |
| 147 | 14.16 | 25kVAr Heavy duty gas filled Capacitor and 7% series copper type reactor | item133 | 4 | Set |
| 148 | 14.17 | 20kVAr Heavy duty gas filled Capacitor and 7% series copper type reactor | item134 | 3 | Set |
| 149 | 14.18 | 15kVAr Heavy duty gas filled Capacitor and 7% series copper type reactor | item135 | 2 | Set |
| 150 | 14.19 | 10kVAr Heavy duty gas filled Capacitor and 7% series copper type reactor | item136 | 1 | Set |
| 151 | 14.2 | 75 X 40MM C Channel MS | item137 | 9 | Mtr |
| 152 | 14.21 | Earth Bus : 25 X 6 mm Copper | item138 | 8 | Mtr |
| 153 | 15 | LIGHT SWITCH BOARD | |||
| 154 | 15.01 | CRCA Sheet 1.6mm thickness | item139 | 125 | Sqft |
| 155 | 15.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item140 | 3240 | Cu.Cm |
| 156 | 15.03 | Incomer : 200A, TPN, MCCB without release | item141 | 1 | Nos |
| 157 | 15.04 | VAF Meter with suitable rating resin cast CT | item142 | 1 | Set |
| 158 | 15.05 | RYB Indication with control MCBs | item143 | 1 | Set |
| 159 | 15.06 | Outgoings : 32A, TP MCCB Thermal rels | item144 | 12 | Nos |
| 160 | 15.07 | 75 X 40MM C Channel MS | item145 | 7 | Mtr |
| 161 | 15.08 | Earth Bus : 25 X 3 mm Copper | item146 | 5 | Mtr |
| 162 | 16 | SUB SWITCH BOARD - 1 ( SSB1 ) | |||
| 163 | 16.01 | CRCA Sheet 1.6mm thickness | item147 | 170 | Sqft |
| 164 | 16.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item148 | 4900 | Cu.Cm |
| 165 | 16.03 | Incomer : 200A, TPN, Switch Disconnector | item149 | 1 | Nos |
| 166 | 16.04 | VAF Meter with suitable rating resin cast CT | item150 | 2 | Set |
| 167 | 16.05 | RYB Indication with control MCBs | item151 | 2 | Set |
| 168 | 16.06 | Outgoings : 100A, TP MCCB Thermal rels | item152 | 1 | Nos |
| 169 | 16.07 | 75A, TP MCCB Thermal rels | item153 | 1 | Nos |
| 170 | 16.08 | 63A, TP MCCB Thermal rels | item154 | 3 | Nos |
| 171 | 16.09 | 25A, TP MCCB Thermal rels | item155 | 1 | Nos |
| 172 | 16.1 | 75 X 40MM C Channel MS | item156 | 12 | Mtr |
| 173 | 16.11 | Earth Bus : 25 X 3 mm Copper | item157 | 7 | Mtr |
| 174 | 17 | SUB SWITCH BOARD - 2 ( SSB2 ) | |||
| 175 | 17.01 | CRCA Sheet 1.6mm thickness | item158 | 125 | Sqft |
| 176 | 17.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item159 | 3950 | Cu.Cm |
| 177 | 17.03 | Incomer : 300A, TPN, Switch Disconnector | item160 | 1 | Nos |
| 178 | 17.04 | VAF Meter with suitable rating resin cast CT | item161 | 1 | Set |
| 179 | 17.05 | RYB Indication with control MCBs | item162 | 1 | Set |
| 180 | 17.06 | Outgoings : 100A, TP MCCB Thermal rels | item163 | 1 | Nos |
| 181 | 17.07 | 63A, TP MCCB Thermal rels | item164 | 5 | Nos |
| 182 | 17.08 | 32A, TP MCCB Thermal rels | item165 | 2 | Nos |
| 183 | 17.09 | 75 X 40MM C Channel MS | item166 | 7 | Mtr |
| 184 | 17.1 | Earth Bus : 25 X 3 mm Copper | item167 | 7 | Mtr |
| 185 | 18 | SUB SWITCH BOARD - 3 ( SSB3 ) | |||
| 186 | 18.01 | CRCA Sheet 1.6mm thickness | item168 | 125 | Sqft |
| 187 | 18.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item169 | 3950 | Cu.Cm |
| 188 | 18.03 | Incomer : 400A, TPN, Switch Disconnector | item170 | 1 | Nos |
| 189 | 18.04 | VAF Meter with suitable rating resin cast CT | item171 | 1 | Set |
| 190 | 18.05 | RYB Indication with control MCBs | item172 | 1 | Set |
| 191 | 18.06 | Outgoings : 160A, TP MCCB Thermal rels | item173 | 1 | Nos |
| 192 | 18.07 | 100A, TP MCCB Thermal rels | item174 | 1 | Nos |
| 193 | 18.08 | 63A, TP MCCB Thermal rels | item175 | 5 | Nos |
| 194 | 18.09 | 32A, TP MCCB Thermal rels | item176 | 3 | Nos |
| 195 | 18.1 | 75 X 40MM C Channel MS | item177 | 7 | Mtr |
| 196 | 18.11 | Earth Bus : 25 X 3 mm Copper | item178 | 7 | Mtr |
| 197 | 19 | LIFT PANEL 1,2 & 3 | |||
| 198 | 19.01 | CRCA Sheet 1.6mm thickness | item179 | 45 | Sqft |
| 199 | 19.02 | Heat Shrinkable Sleeved Aluminium Bus bar | item180 | 1000 | Cu.Cm |
| 200 | 19.03 | Incomer : 100A 4P MCB | item181 | 1 | Nos |
| 201 | 19.04 | Outgoings : 32A, 4P 300mA ELCB | item182 | 8 | Nos |
| 202 | 19.05 | 25A, 2P 30mA ELMCB | item183 | 3 | Nos |
| 203 | 19.06 | 6A, SP MCB | item184 | 4 | Nos |
| 204 | 19.07 | Earth Bus : 25 X 3 mm Copper | item185 | 2 | Mtr |
| 205 | 20 | SS ENCLOSURES | |||
| 206 | 20.01 | 63A Isolator with SS Enclosure | item186 | 5 | Nos |
| 207 | 20.02 | 100A Isolator with SS Enclosure | item187 | 5 | Nos |
| 208 | 20.03 | 125A Isolator with SS Enclosure | item188 | 2 | Nos |
| 209 | 21 | MCB DISTRIBUTION BOARDS:- SITC of following distribution boards. :- MCCB/MCB distribution boards shall be totally enclosed with double door,vertical,surface/recessed mounting type, shall be hinged type with push in type spring/magnetic lock, inner door shall be fixed up with screws with cutouts for MCB operation,copper busbar of at least 1.5 times the rating of incomer MCB/MCCB. The DB shall be completely wired up, up to incoming and outgoing terminals by PVC insulated flexible copper wire of adequate rating. All ELCB installed in LDB & PDB shall be rated for 30mA & 100mA leakage current respectively . All MCB in pwer DB shall be suitable for motive power (curve C ). | |||
| 210 | 21.01 | 16 WAY TPN MCCB VDB. | item189 | 8 | Nos |
| 211 | 21.02 | 14 WAY TPN MCCB VDB. | item190 | 2 | Nos |
| 212 | 21.03 | 12 WAY TPN MCCB VDB. | item191 | 2 | Nos |
| 213 | 21.04 | 8 WAY TPN MCCB VDB. | item192 | 4 | Nos |
| 214 | 21.05 | 6 WAY TPN MCCB VDB. | item193 | 1 | Nos |
| 215 | 21.06 | 12 WAY TPN VDB. | item194 | 2 | Nos |
| 216 | 21.07 | 6 WAY TPN VDB. | item195 | 2 | Nos |
| 217 | 21.08 | 4 WAY TPN VDB. | item196 | 1 | Nos |
| 218 | 21.09 | 12 WAY SPN DB. | item197 | 3 | Nos |
| 219 | 21.1 | 8 WAY TPN DB. | item198 | 10 | Nos |
| 220 | 21.11 | 4 WAY TPN DB. | item199 | 4 | Nos |
| 221 | 21.12 | 100A, 4P MCCB Thermal rels | item200 | 2 | Nos |
| 222 | 21.13 | 80A, 4P MCCB Thermal rels | item201 | 1 | Nos |
| 223 | 21.14 | 63A, 4P MCCB Thermal rels | item202 | 6 | Nos |
| 224 | 21.15 | 40A, 4P MCCB Thermal rels | item203 | 1 | Nos |
| 225 | 21.16 | 32A, 4P MCCB Thermal rels | item204 | 2 | Nos |
| 226 | 21.17 | 63A, 4P MCB | item205 | 1 | Nos |
| 227 | 21.18 | 40A, 4P MCB | item206 | 1 | Nos |
| 228 | 21.19 | 32A, 4P MCB | item207 | 14 | Nos |
| 229 | 21.2 | 63A, TP MCB | item208 | 1 | Nos |
| 230 | 21.21 | 50A, TP MCB | item209 | 1 | Nos |
| 231 | 21.22 | 40A, TP MCB | item210 | 1 | Nos |
| 232 | 21.23 | 6/10/16/20A,25A /32A, TP MCB | item211 | 52 | Nos |
| 233 | 21.24 | 20A, DP MCB | item212 | 2 | Nos |
| 234 | 21.25 | 6/32A SP MCBS | item213 | 350 | Nos |
| 235 | 21.26 | 40A, 4P, 30mA ELCB | item214 | 4 | Nos |
| 236 | 21.27 | 32A, 4P, 30mA ELCB | item215 | 6 | Nos |
| 237 | 21.28 | 63A, 4P, 100mA ELCB | item216 | 2 | Nos |
| 238 | 21.29 | 40A, 4P, 100mA ELCB | item217 | 2 | Nos |
| 239 | 22 | SITC STREET LIGHTING DB(IP-65):- DB Should have a provision for incoming cable of size 4CX16 Sq.mm XLPE AL. cable & 8 runs of 4CX4Sq.mm outgoing cables from Bottom & having 24 Hour Digital Timer unit with Auto/Manual Control. The cost for this item shall also include the Metalic/PCC pedestal, RCC foundation below ground and all other mounting/fixing accessories complete as required. | |||
| 240 | 22.01 | 65W -Street Light with pole and all accessories like contractor , MCB , timer etc. | item218 | 52 | Nos |
| 241 | 23 | UPS/ INVERTERS/ISOLATORS WITH ENCLOUSER, MCCB WITH ENCLOUSER | |||
| 242 | 23.01 | 40 KVA UPS :- Supply, Installation,testing and commissioning of 440volt, 50 hz, 3phase AC input and output of 3 phase, 415volt, 50 hz. Supply should include batteries of UPS for 30 Minutes back up. The Installation shall be as per standard & specifications and manufacturer's manual and relavant codes and standards. BATTERIES : PANASONIC/ROCKET KOREA, 30 min backup- WITH RACK CAPACITY I/P ISOLATION TRANSFORMER AND SNMP & MODUBUS OPTIONS | item219 | 1 | Nos |
| 243 | 24 | 5KVA INVERTER:- Supply, Installation,testing and commissioning of 1 phase Inverter - 230volt, 50 hz, AC input and output 230volt AC , 50 hz, sine wave ; 60 mins. Back-up with maintenance free battery. The Installation shall be as per standard RRL specifications and manufacturer's manual and relavant codes and standards. Make - Luminous/Microtek/Sukam 5 kVA. | item220 | 1 | Nos |
| 244 | 25 | ENCLOSURES | |||
| 245 | 25.01 | 63A FP, MCB with ENCLOUSRE | item221 | 3 | Nos |
| 246 | 26 | CABLES/END TERMINATIONS - POWER AND CONTROL ARMOURED CABLES: The LT cable will be 1.1KV grade, XLPE insulated, FR PVC outer sheathed; GI wire/strip armoured having stranded Aluminium/ Copper conductor. Cables will be as per IS: 7098 Part I / II . Supply and Laying of XLPE Insulated FR PVC outer sheathed, inner extruded PVC sheath, 3/3.5 / 4 CORE, ARMOURED, stranded ALUMINIUM /COPPER conductor cables of 1.1KV ' class cables as per IS. | |||
| 247 | 26.01 | 3.5C x 400 Sq.mm. Al XLPE | item222 | 500 | Mtr |
| 248 | 26.02 | 3.5C x 300 Sq.mm. Al XLPE | item223 | 250 | Mtr |
| 249 | 26.03 | 3.5C x 240 Sq.mm. Al XLPE | item224 | 200 | Mtr |
| 250 | 26.04 | 3.5C x 185 Sq.mm. Al XLPE | item225 | 150 | Mtr |
| 251 | 26.05 | 3.5C x 150 Sq.mm. Al XLPE | item226 | 60 | Mtr |
| 252 | 26.06 | 3.5C x 120 Sq.mm. Al XLPE | item227 | 100 | Mtr |
| 253 | 26.07 | 3.5C x 95 Sq.mm. Al XLPE | item228 | 150 | Mtr |
| 254 | 26.08 | 3.5C x 70 Sq.mm. Al XLPE | item229 | 100 | Mtr |
| 255 | 26.09 | 3.5C x 50 Sq.mm. Al XLPE | item230 | 100 | Mtr |
| 256 | 26.1 | 3.5C x 35 Sq.mm. Al XLPE | item231 | 60 | Mtr |
| 257 | 26.11 | 4C x 25 Sq.mm. Al XLPE | item232 | 400 | Mtr |
| 258 | 26.12 | 4C x 16 Sq.mm. Al XLPE | item233 | 500 | Mtr |
| 259 | 26.13 | 4C x 10 Sq.mm. Alu XLPE | item234 | 500 | Mtr |
| 260 | 26.14 | 4C x 6 Sq.mm. Alu XLPE | item235 | 200 | Mtr |
| 261 | 26.15 | 4C x 4 Sq.mm. Alu XLPE | item236 | 250 | Mtr |
| 262 | 26.16 | 3C x 16 Sq.mm. Alu XLPE | item237 | 200 | Mtr |
| 263 | 26.17 | 3C x 6 Sq.mm. Alu XLPE | item238 | 1000 | Mtr |
| 264 | 26.18 | 3C x 4 Sq.mm. Alu XLPE | item239 | 1000 | Mtr |
| 265 | 26.19 | 2C x 2.5 Sq.mm Cu XLPE | item240 | 200 | Mtr |
| 266 | 26.2 | 4C x 2.5 Sq.mm Cu XLPE | item241 | 100 | Mtr |
| 267 | 26.21 | 3C x 1.5 Sq.mm Cu XLPE | item242 | 200 | Mtr |
| 268 | 26.22 | 2C x 2.5 Sq.mm Cu XLPE | item243 | 200 | Mtr |
| 269 | 26.23 | 2C x 1.5 Sq.mm Cu XLPE | item244 | 100 | Mtr |
| 270 | 27 | Supply and Laying of XLPE Insulated FR PVC outer sheathed, inner extruded PVC sheath,UNARMOURED, stranded COPPER conductor cables of 1.1KV ' class cables per IS 7098 part - 1. The cable shall either be ' laid in trench 0.5Mwide 0.75M deep / RCC ' Hume pipe of size 150mm / ready - made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets(2mm) tied at regular intervals of not less than 10 mtrs. | |||
| 271 | 27.01 | 1C x 70 Sq.mm Cu XLPE | item245 | 30 | Mtr |
| 272 | 27.02 | 1C x 16 Sq.mm Cu XLPE | item246 | 70 | Mtr |
| 273 | 27.03 | 1C x 10 Sq.mm Cu XLPE | item247 | 50 | Mtr |
| 274 | 27.04 | 1C x 6 Sq.mm Cu XLPE | item248 | 50 | Mtr |
| 275 | 27.05 | 4C x 50 Sq.mm Cu XLPE | item249 | 50 | Mtr |
| 276 | 27.06 | 4C x 70 Sq.mm Cu XLPE | item250 | 100 | Mtr |
| 277 | 28 | CABLE END TERMINATIONS:- Supply and making END TERMINARION with brass single compression glands for indoor terminations & solderless crimping type tinned Cu lugs for the following XLPE insulated PVC sheathed 1100 V grade, ARMOURED, stranded, ALUMINIUM/COPPER conductor cable including cost of ferrules, cable sockets, insulation tape and other accessories as required. Make - Dowells/Comet | |||
| 278 | 28.01 | 3.5C x 400 Sq.mm. Al XLPE | item251 | 30 | Nos |
| 279 | 28.02 | 3.5C x 300 Sq.mm. Al XLPE | item252 | 12 | Nos |
| 280 | 28.03 | 3.5C x 240 Sq.mm. Al XLPE | item253 | 12 | Nos |
| 281 | 28.04 | 3.5C x 185 Sq.mm. Al XLPE | item254 | 16 | Nos |
| 282 | 28.05 | 3.5C x 150 Sq.mm. Al XLPE | item255 | 10 | Nos |
| 283 | 28.06 | 3.5C x 120 Sq.mm. Al XLPE | item256 | 8 | Nos |
| 284 | 28.07 | 3.5C x 95 Sq.mm. Al XLPE | item257 | 10 | Nos |
| 285 | 28.08 | 3.5C x 70 Sq.mm. Al XLPE | item258 | 8 | Nos |
| 286 | 28.09 | 3.5C x 50 Sq.mm. Al XLPE | item259 | 12 | Nos |
| 287 | 28.1 | 3.5C x 35 Sq.mm. Al XLPE | item260 | 4 | Nos |
| 288 | 28.11 | 4C x 25 Sq.mm. Al XLPE | item261 | 20 | Nos |
| 289 | 28.12 | 4C x 16 Sq.mm. Al XLPE | item262 | 22 | Nos |
| 290 | 28.13 | 4C x 10 Sq.mm. Alu XLPE | item263 | 30 | Nos |
| 291 | 28.14 | 4C x 6 Sq.mm. Alu XLPE | item264 | 12 | Nos |
| 292 | 28.15 | 4C x 4 Sq.mm. Alu XLPE | item265 | 10 | Nos |
| 293 | 28.16 | 3C x 16 Sq.mm. Alu XLPE | item266 | 4 | Nos |
| 294 | 28.17 | 3C x 6 Sq.mm. Alu XLPE | item267 | 4 | Nos |
| 295 | 28.18 | 3C x 4 Sq.mm. Alu XLPE | item268 | 20 | Nos |
| 296 | 28.19 | 2C x 2.5 Sq.mm Cu XLPE | item269 | 4 | Nos |
| 297 | 28.2 | 4C x 2.5 Sq.mm Cu XLPE | item270 | 6 | Nos |
| 298 | 28.21 | 3C x 1.5 Sq.mm Cu XLPE | item271 | 4 | Nos |
| 299 | 28.22 | 2C x 2.5 Sq.mm Cu XLPE | item272 | 8 | Nos |
| 300 | 28.23 | 2C x 1.5 Sq.mm Cu XLPE | item273 | 10 | Nos |
| 301 | 28.24 | 1C x 70 Sq.mm Cu XLPE | item274 | 6 | Nos |
| 302 | 28.25 | 1C x 16 Sq.mm Cu XLPE | item275 | 10 | Nos |
| 303 | 28.26 | 1C x 10 Sq.mm Cu XLPE | item276 | 10 | Nos |
| 304 | 28.27 | 1C x 6 Sq.mm Cu XLPE | item277 | 12 | Nos |
| 305 | 28.28 | 4C x 50 Sq.mm Cu XLPE | item278 | 4 | Nos |
| 306 | 28.29 | 4C x 70 Sq.mm Cu XLPE | item279 | 4 | Nos |
| 307 | 29 | From DB'S to Equipment including termination | |||
| 308 | 29.01 | 1.5 MM² , 3 run Copper Flexible wire (For Light ) | item280 | 9000 | Mtr |
| 309 | 29.02 | 2.5 MM² , 3 run Copper Flexible wire (For power socket ) | item281 | 2000 | Mtr |
| 310 | 29.03 | 4 MM² , 3 run Copper Flexible wire (For MCS ) | item282 | 500 | Mtr |
| 311 | 29.04 | 4 MM² , 5 run Copper Flexible wire (For 3 PH MCS ) | item283 | 150 | Mtr |
| 312 | 30 | PVC CONDUIT PIPES | |||
| 313 | 30.01 | 20mm medium duty PVC Pipe | item284 | 1500 | Mtr |
| 314 | 30.02 | 25mm medium duty PVC Pipe | item285 | 2000 | Mtr |
| 315 | 30.03 | 20mm Junction Box | item286 | 500 | Mtr |
| 316 | 30.04 | 25mm Junction Box | item287 | 500 | Mtr |
| 317 | 31 | FLEXIBLE PVC PIPES | |||
| 318 | 31.01 | 20mm | item288 | 500 | Mtr |
| 319 | 31.02 | 25mm | item289 | 250 | Mtr |
| 320 | 31.03 | 32mm | item290 | 200 | Mtr |
| 321 | 32 | SWITCH BOARD (MODULAR):- SITC of following size of Concealed Boxes. | |||
| 322 | 32.01 | Two Module Box | item291 | 50 | Nos |
| 323 | 32.02 | Three Module Box | item292 | 30 | Nos |
| 324 | 32.03 | Four Module Box | item293 | 40 | Nos |
| 325 | 32.04 | Six Module Box | item294 | 20 | Nos |
| 326 | 32.05 | Eight Module Box | item295 | 20 | Nos |
| 327 | 32.06 | Twelve Module Box | item296 | 5 | Nos |
| 328 | 32.07 | Sixteen Module Box | item297 | 6 | Nos |
| 329 | 33 | SITC of following size of PVC Surface Boxes. | |||
| 330 | 33.01 | Two Module Box | item298 | 6 | Nos |
| 331 | 33.02 | Three Module Box | item299 | 3 | Nos |
| 332 | 33.03 | Four Module Box | item300 | 6 | Nos |
| 333 | 33.04 | Six Module Box | item301 | 6 | Nos |
| 334 | 33.05 | Eight Module Box | item302 | 10 | Nos |
| 335 | 34 | SITC of following size of SS plates. | |||
| 336 | 34.01 | One Module Plate | item303 | 20 | Nos |
| 337 | 34.02 | Two Module Plate | item304 | 30 | Nos |
| 338 | 34.03 | Three Module Plate | item305 | 30 | Nos |
| 339 | 34.04 | Four Module Plate | item306 | 40 | Nos |
| 340 | 34.05 | Six Module Plate | item307 | 20 | Nos |
| 341 | 34.06 | Eight Module Plate | item308 | 20 | Nos |
| 342 | 34.07 | Twelve Module Plate | item309 | 5 | Nos |
| 343 | 34.08 | Sixteen Module Plate | item310 | 6 | Nos |
| 344 | 35 | SITC of following Modular Accessories. | |||
| 345 | 35.01 | One way Switch 6A | item311 | 250 | Nos |
| 346 | 35.02 | Two way Switch 6A | item312 | 16 | Nos |
| 347 | 35.03 | One way Switch 16A | item313 | 30 | Nos |
| 348 | 35.04 | 6A, 3 pin socket | item314 | 50 | Nos |
| 349 | 35.05 | 16A, 3 pin socket | item315 | 30 | Nos |
| 350 | 35.06 | 16A, 3 pin socket outlet with 20A DP Switch | item316 | 10 | Nos |
| 351 | 35.07 | 32A, TPN socket outlet with 32A FP MCB in metal enclosure | item317 | 20 | Nos |
| 352 | 35.08 | 20A, 3 pin socket outlet with 20A DP MCB in metal enclosure | item318 | 25 | Nos |
| 353 | 35.09 | Switch Dummy | item319 | 50 | Nos |
| 354 | 36 | G.I LADDER & PERFORATED TYPE CABLE TRAYS/ FLOOR TRUNKING FOR VOICE , DATA & POWER OUTLETS: Supply, Installation , testing and commissioning of Hot Dip Galvanised perforated cable tray, G.I, 1.6mm thick for Electrical Cable with G.I Angle/Hitech Threaded rods with Anchor fasteners, Clamps, bolts,nuts including all the necessary fasteners as per RRL std specs | |||
| 355 | 36.01 | 50 x50 mm | item320 | 500 | Mtr |
| 356 | 36.02 | 100 x 50 mm | item321 | 200 | Mtr |
| 357 | 36.03 | 150 x 50 mm | item322 | 100 | Mtr |
| 358 | 36.04 | 300 x 50 mm | item323 | 500 | Mtr |
| 359 | 36.05 | 450 x 50 mm | item324 | 400 | Mtr |
| 360 | 36.06 | 600 x 100 mm | item325 | 200 | Mtr |
| 361 | 37 | Supply, Installation , testing and commissioning of Hot Dip Galvanised Ladder type MS painted cable tray with all accessories including anchor fasteners, couplers & fixing structures, as per RRL std specs G.I, 1.6mm thick for Electrical Cable with G.I Angle/Hitech Threaded rods with Anchor fasteners, Clamps, bolts,nuts including all the necessary fasteners as per RRL std specs | |||
| 362 | 37.01 | 300 x 100 mm | item326 | 150 | Mtr |
| 363 | 37.02 | 450 x 100 mm | item327 | 125 | Mtr |
| 364 | 37.03 | 600 x 100 mm | item328 | 100 | Mtr |
| 365 | 37.04 | 750 x 100 mm | item329 | 150 | Mtr |
| 366 | 37.05 | 1000 x 100 mm | item330 | 100 | Mtr |
| 367 | 38 | STRUCTURAL STEEL | |||
| 368 | 38.01 | Supply and fabrication of various sizes of angles/brackets/channels/frames, etc of Structural steel with one coat of red oxide & two coat of enamel approved paint for supporting equipment/cables, etc | item331 | 2500 | Kg |
| 369 | 39 | POWER RECEPTACLES:- Supply ,Installation, testing and commissioning of Plug and socket DB's with suitable MCBs and neutral links housed in Stainless steel enclosure,dulywired, with earthing facility. The rate shall include switch plates, chasing walls/floors fine finished plastering with wire mesh etc. | |||
| 370 | 39.01 | 10A, 3pin socket with 10A SP MCB | item332 | 11 | Nos |
| 371 | 39.02 | 10A, 3pin socket 2 Nos. with 10A SP MCB individual control | item333 | 51 | Nos |
| 372 | 39.03 | 25A,3 Phase power socket 2 Nos. with 25A TPN MCB individual control | item334 | 9 | Nos |
| 373 | 39.04 | 10A,3pin socket with 10A SP MCB and 25A,3 Phase power socket with 25A TPN MCB | item335 | 15 | Nos |
| 374 | 39.05 | 32A,3 Phase power socket with 32 TPN MCB | item336 | 11 | Nos |
| 375 | 39.06 | ON / OFF Push Button for AHU Starters | item337 | 50 | Nos |
| 376 | 39.07 | 25A FP MCB | item338 | 4 | Nos |
| 377 | 39.08 | 32A FP MCB | item339 | 5 | Nos |
| 378 | 39.09 | 40A FP MCB | item340 | 3 | Nos |
| 379 | 40 | SUPPLY & INSTALATION OF INTERNAL CLEAN ROOM LIGHT FIXTURES WITH REQUIRED ACCESSORIES- CLEAN ROOM FITTINGS-FLAME PROOF | |||
| 380 | 40.01 | 22W, 300 X 300MM LED SQUARE | item341 | 139 | Nos |
| 381 | 40.02 | 36W, 600 X 600MM LED SQUARE | item342 | 126 | Nos |
| 382 | 41 | NON - FLAME PROOF | |||
| 383 | 41.01 | 22W, 300 X 300MM LED SQUARE | item343 | 400 | Nos |
| 384 | 41.02 | 36W, 600 X 600MM LED SQUARE | item344 | 606 | Nos |
| 385 | 42 | INDUSTRIAL LIGHT FITTINGS | |||
| 386 | 42.01 | 10W PL Light | item345 | 22 | Nos |
| 387 | 42.02 | 1x40W Industrial Tube Fittings | item346 | 46 | Nos |
| 388 | 42.03 | 2x40W Industrial Tube Fittings | item347 | 157 | Nos |
| 389 | 43 | FLAME PROOF - INDUSTRIAL LIGHT FITTINGS | |||
| 390 | 43.01 | 1x40W Industrial Tube Fittings | item348 | 46 | Nos |
| 391 | 44 | EXTERNAL LIGHIT FIXTURES WITH REQUIRED ACCESSORIES:-Supply ,Installation & commissioning of following of prewired light fittings/ light tracks, complete The fitting shall be fixed with chain ,screws etc. & recessed mounted in false ceiling. Cost of chains Screws to be considered in these items. All fittings to be IP 65 certified. | |||
| 392 | 44.01 | 24W LED LIGHT COLUMN | item349 | 8 | Nos |
| 393 | 44.02 | 24W LED BOLLARD -Make : Klite/Wipro/Philips/Havels/ Bajaj | item350 | 5 | Nos |
| 394 | 44.03 | 20W LED PILLAR LUMINAIRIES-Pillar light with Cluster of LED lamps complete with Drivers & all required accessories- Make : Klite/Wipro/Philips/Havels/ Bajaj | item351 | 3 | Nos |
| 395 | 45 | Emergency Luminaire :- Light in each floor should be connected from UPS. | |||
| 396 | 45.01 | 22W ( Size - 300mm X 300mm ) | item352 | 75 | Nos |
| 397 | 45.02 | 36W ( Size - 600mm X 600mm ) | item353 | 30 | Nos |
| 398 | 45.03 | 2 X 40W Industrial fitting light | item354 | 20 | Nos |
| 399 | 46 | EXHAUST FANS:-SITC of exhaust fans with sheet metal blades of following sizes of white colour or architects/clients approved colour, Exhaust fans with necessary brackets anti corresive epoxy painting, ruber cushion accessories, connecting wire & other standard accessories complete as required. The scope of works includes minor civil work. | |||
| 400 | 46.01 | Supply & Installation of 225 mm dia, 900 rpm single phase exhaust fan | item355 | 5 | Nos |
| 401 | 46.02 | 450 mm impeller dia, 1400 rpm exhaust fan | item356 | 2 | Nos |
| 402 | 47 | CEILING FANS: | |||
| 403 | 47.01 | 75 watts ceiling fan - 48\" DIA | item357 | 3 | Nos |
| 404 | 47.02 | Fan Regulator | item358 | 3 | Nos |
| 405 | 48 | EARTHING SYSTEMS-EARTHING STATIONS: | |||
| 406 | 48.01 | Supply, providing, Installing, testing & commissioning of copper plate earthing station using 600x600x3mm Cu plate including excavation, backfilling, construction of inspection chamber, chamber cover (CI), disconnecting link etc.,as per IS-3043/spec. (UPS DEDICATED EARTHING & DG NEUTRAL) | item359 | 4 | Nos |
| 407 | 48.02 | Supply and Installation of earthing station as per IS standard complete with 1200 x 1200 x 12 mm C.I. plate earthing electrode plate, charcoal, 2 nos. 50 x6 mm G.I Conductor upto test link, 32 mm dia G.I watering pipe with funel,test link. The earthing chamber size shall be 450x450 mm with C.I Manhole chamber etc. as per drawing. The identification number shall be provided both inside and outside of equipment. (ALL PANEL & EQUIPMENT EARTH) | item360 | 10 | Nos |
| 408 | 48.03 | Supply and providing Pipe earthing as per IS 3043 with 3 Metre long 40 mm dia. 'B' class G.I pipe, with necessary accessories, including 300x300mm Cast iron Frame covering at the top. | item361 | 4 | Nos |
| 409 | 49 | EARTHING STRIPs/WIREs:- Supply and laying earth strips 0.5M below ground/exposed including connections by proper nut-bolts/welding. | |||
| 410 | 49.01 | 75 x 6 mm. G.I strip. | item362 | 200 | Mtr |
| 411 | 49.02 | 50 x 6 mm. G.I strip. | item363 | 1500 | Mtr |
| 412 | 49.03 | 50 x 6 mm Cu. strip | item364 | 500 | Mtr |
| 413 | 49.04 | 32 x 6 mm G.I strip | item365 | 50 | Mtr |
| 414 | 49.05 | 25 x 6 mm G.I strip | item366 | 500 | Mtr |
| 415 | 49.06 | 25 x 6 mm Cu. strip | item367 | 200 | Mtr |
| 416 | 49.07 | 25 x 3 mm G.I strip | item368 | 50 | Mtr |
| 417 | 49.08 | 25 x 3 mm Cu. Strip | item369 | 150 | Mtr |
| 418 | 49.09 | 10 SWG Cu. wire | item370 | 3000 | Mtr |
| 419 | 49.1 | 6 SWG Cu. wire | item371 | 500 | Mtr |
| 420 | 50 | Earth Bench:- Supply and clamping 30cm tinned Cu. Earth bench of the following sizes on the surface of wall for connecting earth continuity leads at required locations. | |||
| 421 | 50.01 | 25 x 3 mm | item372 | 10 | Nos |
| 422 | 50.02 | 25 x 6 mm | item373 | 6 | Nos |
| 423 | 51 | LIGHTNING PROTECTION SYSTEM ( BUILDING LIGHTENING ARRESTOR) | |||
| 424 | 51.01 | Supply, Installation, Testing & Commissioning of Advanced Lightening Protection System- Controlled Streamer Emmision (CSE) Technology complete with all accessories. | item374 | 3 | Set |
| 425 | 52 | Safety items:- Safety Equipments: Supply, Installation of below mention safety equipment including all labour and materials etc., complete as per directions of Engineer-In-Charge. | |||
| 426 | 52.01 | Fire buckets with stand-2 buckets. Bucket of round bottom, painted red, marked 'FIRE' & duly filled with river sand. | item375 | 3 | Set |
| 427 | 52.02 | Best quality LT Danger Boards for of approved shape and size as specified by the local electrical authorites written in English, hindi and local language | item376 | 5 | Nos |
| 428 | 52.03 | Best quality HT Danger Boards for of approved shape and size as specified by the local electrical authorites written in English, hindi and local language | item377 | 2 | Nos |
| 429 | 52.04 | Rubber mat suitable for operating voltage upto 1.1 KV | item378 | 8 | Nos |
| 430 | 52.05 | Rubber mat suitable for operating voltage upto 11 KV | item379 | 2 | Nos |
| 431 | 52.06 | Hand Gloves suitable for operating voltage upto 11 KV | item380 | 2 | Pair |
| 432 | 52.07 | Approved shock treatment chart written in English, Hindi and in local language. | item381 | 2 | Nos |
| 433 | 52.08 | First Aid Box | item382 | 2 | Nos |
| 434 | 52.09 | DCP fire extingusher 4.5 kg | item383 | 6 | Nos |
| 435 | 53 | APPENDIX B Electrical Control Panels and Cabling - HVAC Equipments Electrical panel consisting of main incomming starter (MCCB),metering section consisting of digitial voltmeter,ammeter and out going feeder for ahus, and Panel shall be totally enclosed ,completely dust proof, with hinged doors ,neoprene gasket and suitable locking arrangement. and push buttons,lamps,emergency stop switch , switch gears and AHU door indication etc. MCCB PANELS FOR AHUS,DEHUMIDIFIERS,HETERS, | |||
| 436 | 53.01 | PANNEL - I ( GROUND FLOOR) | item384 | 1 | Nos |
| 437 | 53.02 | PANNEL - II ( FIRST FLOOR) | item385 | 1 | Nos |
| 438 | 53.03 | PANNEL - III (SECOND & SERVICE FLOOR) | item386 | 1 | Nos |
| 439 | 53.04 | PANNEL - IV ( CHILLERS ,COOLING TOWER, PUMPS)] | item387 | 1 | Nos |
| 440 | 54 | Electrical Control Panels and Cabling - HVAC Equipments Electrical panel consisting of main incomming starter (MCCB),metering section consisting of digitial voltmeter,ammeter and out going feeder for ahus, and Panel shall be totally enclosed ,completely dust proof, with hinged doors ,neoprene gasket and suitable locking arrangement. and push buttons,lamps,emergency stop switch , switch gears and AHU door indication etc & consider VFD load with AHU panels. MCCB PANELS FOR AHUS,DEHUMIDIFIERS,HETERS, | |||
| 441 | 54.01 | PANNEL - I ( GROUND FLOOR) | item388 | 1 | Nos |
| 442 | 54.02 | PANNEL - II ( FIRST FLOOR) | item389 | 1 | Nos |
| 443 | 54.03 | PANNEL - III (SECOND & SERVICE FLOOR) | item390 | 1 | Nos |
| 444 | 55 | POWER CABLING & CONTROL CABLING -Armoured power cables. | |||
| 445 | 55.01 | 3C X 1.5 SQMM CU | item391 | 1100 | Rmt |
| 446 | 55.02 | 3C X 2.5 SQMM CU | item392 | 440 | Rmt |
| 447 | 55.03 | 3C X 10 SQMM AL | item393 | 150 | Rmt |
| 448 | 55.04 | 4C X 1.5 SQMM CU | item394 | 310 | Rmt |
| 449 | 55.05 | 4C X 2.5 SQMM CU | item395 | 150 | Rmt |
| 450 | 55.06 | 4C X 4 SQMM CU | item396 | 440 | Rmt |
| 451 | 55.07 | 4C X 6 SQMM AL | item397 | 110 | Rmt |
| 452 | 55.08 | 4C X 10 SQMM AL | item398 | 150 | Rmt |
| 453 | 55.09 | 4C X 16 SQMM AL | item399 | 310 | Rmt |
| 454 | 55.1 | 4C X 25 SQMM AL | item400 | 310 | Rmt |
| 455 | 55.11 | 4C X 50 SQMM AL | item401 | 220 | Rmt |
| 456 | 55.12 | 4C X 300 SQMM AL | item402 | 160 | Rmt |
| 457 | 56 | CONTROL CABLING:- Control Cabling from field devices to starter panels of AHU's to all individual motors . | |||
| 458 | 56.01 | 4 C X 1.5 SQ.MM. | item403 | 2500 | Rmt |
| 459 | 57 | DOUBLE COMPRESSION GLANDS | |||
| 460 | 57.01 | 20 MM | item404 | 168 | Nos |
| 461 | 57.02 | 25 MM | item405 | 72 | Nos |
| 462 | 57.03 | 32 MM | item406 | 8 | Nos |
| 463 | 57.04 | 50 MM | item407 | 8 | Nos |
| 464 | 58 | END TERMINALS | |||
| 465 | 58.01 | 3C X 1.5 SQMM CU | item408 | 240 | Nos |
| 466 | 58.02 | 3C X 2.5 SQMM CU | item409 | 88 | Nos |
| 467 | 58.03 | 3C X 10 SQMM AL | item410 | 8 | Nos |
| 468 | 58.04 | 4C X 1.5 SQMM CU | item411 | 88 | Nos |
| 469 | 58.05 | 4C X 2.5 SQMM CU | item412 | 38 | Nos |
| 470 | 58.06 | 4C X 4 SQMM CU | item413 | 185 | Nos |
| 471 | 58.07 | 4C X 6 SQMM AL | item414 | 26 | Nos |
| 472 | 58.08 | 4C X 10 SQMM AL | item415 | 38 | Nos |
| 473 | 58.09 | 4C X 16 SQMM AL | item416 | 88 | Nos |
| 474 | 58.1 | 4C X 25 SQMM AL | item417 | 76 | Nos |
| 475 | 58.11 | 4C X 50 SQMM AL | item418 | 38 | Nos |
| 476 | 58.12 | 4C X 300 SQMM AL | item419 | 26 | Nos |
| 477 | 59 | GI PERFORATED TYPE CABLE TRAY:- Factory fabricated GI perforated type cable tray made out of 14swg sheet steel. supporting angle frame at every 1.2 m, bottom angles, anchor fasteners, bolts and nuts etc. The tray shall be suspended from ceiling using anchor bolt and angle iron supports or threaded rods. The rate shall include all accessories like bends, elbows, tees, coupler plates, joints and fixing accessories etc., which will be measured as linear measurement. | |||
| 478 | 59.01 | 200 MM X 50 MM | item420 | 550 | Rmt |
| 479 | 59.02 | 250 MM X 50 MM | item421 | 550 | Rmt |
| 480 | 59.03 | 300 MM X 50 MM | item422 | 550 | Rmt |
| 481 | 59.04 | 450 MM X 50 MM | item423 | 425 | Rmt |
| 482 | 60 | EARTHING | |||
| 483 | 60.01 | 25 X 3 MM GI Earth Strip | item424 | 725 | Rmt |
| 484 | 60.02 | 25 X 6 MM GI Earth Strip | item425 | 425 | Rmt |
| 485 | 60.03 | 4 SQMM Copper wire | item426 | 1450 | Rmt |
| 486 | 61 | APPROVAL AND SANCTION | |||
| 487 | 61.01 | Professional charges for preparation of drawings, getting approval from the Electrical Inspectorate, submission of completion report , follow up action for getting sanction for energisation , complying all formalities with Electrical Inspectorate for getting power connection. All expenses in excluding statutory charges. Statutory charges shall be paid by the client. | item427 | 1 | Lot |
| 488 | 61.02 | Professional charges of preparation of documents, submission of completion report , follow up actions for getting power connection from KSEB, complying all formalities. All expenses excluding statutory charges. Statutory charges shall be paid by the client. | item428 | 1 | Lot |
| 489 | 62 | P.N. QUANTITY & SPECIFICATIONS MAY VARY AS PER FINAL DESIGN , SITE CONDITION . ANY REQUIRED ITEMS AS PER SITE CONDITION TO BE CONSIDERED.( WHICH IS NOT INCLUDED IN THIS LIST.) |
AI Tender Summary
Tender Timeline
Jul 25, 2019
11:30 IST
Tender Published
Tender notice published.
CompletedAug 14, 2019
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedAug 19, 2019
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender