| 1 | 1 | Supply of ESE Air Terminal ESE -60. Early streamer Emission type Air Terminal should offer Radius of protection 79Mtrs in level I. Air Terminal comprised of separate electrically isolated dual panels surrounding an Earthed central finial should be coated with chrome for environmental protection. The upper section of the central finial shall be rated to withstand 40KA impulse current and it should be made up of solid brass rod and its length should be more than 85mm above the surrounding panels. The insulation material used to electrically isolate the panel shall be comprised of base polymer which provides high UV resistance with die electric strength of 24-38KV/MM & ESE terminal shall withstand a minimum switching impulse voltage of 500KV. Its adapter should be made up of non conductive material DELRIN, which should provide good abrasion resistance, Good mechanical strength, pretty good heat resistance, good electric &dielectric properties & Low water absorption. Terminal performance should be tested as per NFC 17-102:2011. Performance should be tested in European Accredited lab after 2011 also its impulse current withstand test should be carried out in CPRI for 40KA 5+ve & 5-ve test. Terminal should be non electronic& does not require any battery backup or power supply for operation because of battery life & sustainability. Supplier should show on site testing of Continuity of Air Terminal Tip to Adapter. Protection Radius : 79Mtr Level I @ 5mtr Height | BI01010001010000000000000515BI0100001113 | 3 | Nos |
| 2 | 2 | Supporting Mast: The mounting pole used to support the lightning air terminal shall either be a supporting mast or Free standing mast at a ideal height of 05 metres above to be area protected or as per required level of protection. If any height restrictions are there then min height should be 2mtr but radius of protection will change according to height. The mounting pole and supports shall be securely fixed with brackets and guy wires where required to withstand maximum locally recorded wind velocity. Mounting Pole shall be non corrosive and made up of medium class GI pipe of 2\" dia having base plate at bottom for securely fixing mast on rooftop. Also PVC insulated metallic wire rope should be used for guying purpose. The down conductor shall pass through the centre of the pole for the entire length of the pole and it will be out at bottom of the pole. All the mounting accessories should be non corrosive and made up of SS. Supporting Guyed Mast : 05Mtr x 2\" dia with base plate, guying kit and mounting accessories. | BI01010001010000000000000515BI0100001114 | 3 | Nos |
| 3 | 3 | Supply of 70sq.mm cross section down conductor of single core flexible Copper cable made of min. 990 Nos copper strands of 3mm dia and having PVC insulation of min. 3mm thickness and overall dia of 16mm. It should be fixed using SS/GI saddles & fixtures every 0.5mtr. Single core flexible Cu. Cable 70Sq.mm with SS saddles. | BI01010001010000000000000515BI0100001115 | 210 | Mtrs |
| 4 | 4 | Chemical Earthing 80- of 3Mtr. Length.: Maintenance Free Safe Earthing Electrodes with ISI G.I. Pipe dia 75 mm as Secondary electrode with wall thickness of 3.6 mm and the Primary Earthing Electrode will be 50mmX6mmX1no M.S. hot dipped galvanized strip filled with a highly conductive & non-corrosive compound in between the Primary Earthing and the secondary Earthing, the Surface Area in mm will be 7,06,500 for 3mtrs length and Cross Sectional Primary conducting area is 300 sq.mm. A Solid G.I. Base Plate seals the unit at the bottom (MES-GFC ground Filling compound will be provided in 25 kgs Bags) (2 bags required each electrode). | BI01010001010000000000000515BI0100001116 | 9 | Nos. |
| 5 | 5 | Ground Filling Compound filled surrounding to earthing electrode. It should absorb the moisture from surrounding area and it should be non corrosive in nature. It should maintain the constant ohmic value for long life. It should be supplied in packing of 25kgs bag. (2 Bags required for each earthing electrode.) | BI01010001010000000000000515BI0100001117 | 18 | Bags. |
| 6 | 6 | Lightning Strike Recorder (L.S.R.): Supply of Australian make L.S.R. It should be non electronic& non- resettable type having 7 digits display &enclosed in an IP-67 enclosure with minimum sensitivity of 1000A & maximum capacity of 220KA tested on 8/20 micro second wave from as per IEC 60-1: 1989. It should be non electronic type and does not require external power supply for working. Supplier should do on site testing of LSR, where impulse generates should be used to show working of LSR. After impulse current passing through LSR it should change the counter reading. LSR. | BI01010001010000000000000515BI0100001118 | 3 | Nos. |
| 7 | 7 | Installation Charges: 1) Mounting lightning terminal on mast., 2) Fixing the mast on the top of the roof.3) Lying the down conductor from terminal to earth point.4) Clipping the cable in the building wall.5) Making 9nos of 10 ft. hole with a dia of 100mm.6) Pouring of chemicals with earthing pipe into the hole.7) Lying of copper cable to connect the earth pit to creat tripod. | BI01010001010000000000000515BI0100001119 | 3 | Sets |
| 8 | 8 | N.B: The bidders are required to Quote their rates excluding of Goods & Service Tax (GST). GST as applicable will be paid extra. The existing rule of Govt. and any amendment made in future will be followed. | BI01010001010000000000000515BI0100001120 | | |