Tender For Mainenance T And Repairs To Low Tension Lt Distribution System Including Allied Works Under Ge Dssc Wellington
Tender Value
30 Lakhs
Estimated cost
Bid Submission
05 Aug 2019
0 days left
EMD
60000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Wellington → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Mainenance T And Repairs To Low Tension Lt Distribution System Including Allied Works Under Ge Dssc Wellington
BOQ
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
|---|---|---|---|---|---|
| 1 | 1 | Excavation in trenches not exceeding 1.5m wide and n.exc 1.5 m in depth for laying of cables / foundation etc., in hard/dense soil and getting out etc, complete all as specified and directed by Engr-in-Charge. | 527 | CUM | |
| 2 | 2 | Returning, filling in, including spreading levelling, watering and well ramming in layers not exc 25 cm in thick using excavated soil all as specified and directed by Engr-in-Charge. | 302 | CUM | |
| 3 | 3 | Removing of excavated soil to a distance not exc 50m and depositing where directed at level n.exc 1.5m from the starting point all as specified and directed by Engr-in-Charge. | 225 | CUM | |
| 4 | 4 | Supply and laying well burnt old size sub class 'B' bricks in trenches for cable protection of U/G cables all as specified and directed by Engr-in-Charge. | 16670 | Each | |
| 5 | 5 | Supply, spreading and compacting of approved river bed sand / M sand in trenches for cable cushion on both top and bottom of cable, including ramming all as specified and as directed by Engr-in Charge. \nNote: Punned thickness will only be measured for payment purpose | 158 | CUM | |
| 6 | 6 | Laying/ Fixing only in trenches / through pipe on bare in road crossings / paths / drains / ducts / floors / along poles / walls ceilings etc, of UG armoured cable, XLPE insulated with stranded aluminium conductor, 1100 V Grade of cross sectional area 3.5 Core 400 Sqmm and connecting up with proper lugs and glands including taking down/up unserviceable / damaged UG LT cable of any size and type from trenches / pole / wall etc after necessary electrical disconnection complete all as specified and directed by the Engr-in-Charge. \nNote : (i) Cable shall be issued under Sch 'B' free for laying/Fixing only (ii) Quoted rate shall be inclusive of transport of cable from MES store to work place. (iii) Quoted rate shall also be inclusive of connecting cable using proper lugs and glands. | 293 | RM | |
| 7 | 7 | M&L for grass and bushes cutting, area cleaning and removal of debris and spraying chemical as per manufacturer's instructions on weediciding spraying and disposal of the bushes at specified locations not exc 250m all as specified and directed by Engr-in-Charge. \nNote: The contractor shall take care of existing cable lines and other external equipments at site. Any damages shall be replaced by contractor with out any extra cost to the department. | 1000 | Sqm | |
| 8 | 8 | M&L for preparation of old painted steel surface of Out Door / Indoor LT/HT Panels, ChangeOver Boxes, Junction Boxes of any size/type etc after cleaning of oils, wax, lubricants, grease, Rusty Scales etc complete of any type of surface and applying one coat of synthetic enamel paint of existing colour paint using spray gun and neatly writing down the distribution details in blue coloured paint all as specified and directed by Engr-in-Charge. | 200 | Each Job | |
| 9 | 9 | Taking down unserviceable/damaged GI tubing of any size and type from trenches/pole/wall etc after necessary electrical disconnection complete all as specified and directed by Engr-in-Charge. | 150 | RM | |
| 10 | 10 | Supply and laying light grade GI pipe (ISI Marked) as cable protection to be fixed on wall/pole/trenches/floors with necessary clamps as per existing or in road crossing as ordered of following sizes complete all as specified and directed by Engr-in-Charge :- \nNote :- Unit rate quoted rate is deemed to be inclusive of MS clamps if required to be fixed on pole. Make: Tata/Jindal/Prakash\n(a) 80 mm | 50 | RM | |
| 11 | 11 | (b) 50 mm | 50 | RM | |
| 12 | 12 | (c) 40 mm | 50 | RM | |
| 13 | 13 | S&F straight through joint heat shrink type for LT UG Cable including joint kits for making joint suitable for aluminium conductor of size 25 sqmm to 50 Sqmm x 4/3.5 core including preparation of damaged cable and taking up loop and testing complete of Make: 3M, Code No: MHS X 1.1KV (HSLA-2/4C) or Equiv in Raychem RPG/Denson all as specified and directed by Engr-in-Charge. | 5 | Each | |
| 14 | 14 | S&F straight through joint heat shrink type for LT UG Cable including joint kits for making joint suitable for aluminium conductor of size 70 sqmm to 120 Sqmm x 3.5 core including preparation of damaged cable and taking up loop and testing complete of Make: 3M, Code No: MHS X 1.1KV (HSLA-3/4C) or Equiv in Raychem RPG/Denson all as specified and directed by Engr-in-Charge. | 5 | Each | |
| 15 | 15 | S&F straight through joint heat shrink type for LT UG Cable including joint kits for making joint suitable for aluminium conductor of size 150 sqmm to 185 Sqmm x 3.5 core including preparation of damaged cable and taking up loop and testing complete of Make: 3M, Code No: MHS X 1.1KV (HSLA-4/4C) or Equiv in Raychem RPG/Denson all as specified and directed by Engr-in-Charge. | 3 | Each | |
| 16 | 16 | S&F straight through joint heat shrink type for LT UG Cable including joint kits for making joint suitable for aluminium conductor of size 240 sqmm to 300 Sqmm x 3.5 core including preparation of damaged cable and taking up loop and testing complete of Make: 3M, Code No: MHS X 1.1KV (HSLA-5/4C) or Equiv in Raychem RPG/Denson all as specified and directed by Engr-in-Charge. | 2 | Each | |
| 17 | 17 | M & L for cutting the existing hard standing/PCC/WBM road at adepth not less than 45 cm and 25 cm in width for passing of cable through GI pipe, returning filling in, complete including finishing the surfaces by providing top 30 mm thick cement concrete type B-1 (1:2:4) using 20 mm graded stone aggregate, bottom filled with excavated earth and remain finishing to a unifirm smooth surface complete all as specified and directed by Engr-in-Charge. \nNote: GI pipe will be measured and paid seperately | 200 | RM | |
| 18 | 18 | Repairs to LT panel out door type including taking out 4 Nos old damaged / unserviceable door hinges and welding with new hinges of size as per existing and providing one locking arrangement incl cutting of the panel to suit the existing MCCB all as specified and directed by Engr-in-Charge. \nNote: Cost of cutting /Welding work if any incl necessary nuts/bolts etc is deemed to be included in the unit quoted rates. | 60 | Each Job | |
| 19 | 19 | S&F in repairs MCCB, 4 pole, (Ics=100% of Icu) 400Amps 50 Hz, 415V, adj Thermal & Fixed Magnetic setting with rupturing capacity of 50 KA incl cutting the frame of existing panel to suit the new MCCB incl taking down the old MCCB complete of Make : L&T Cat No: CM98404OORO or equiv in ABB/Siemens all as specified and directed by Engr-in-Charge. \nNote: The cost of making good is deemed to be included in the quoted rates | 5 | Each | |
| 20 | 20 | S&F in repairs MCCB, 4 pole, (Ics=100% of Icu) 250Amps 50 Hz, 415V, adj Thermal & Fixed Magnetic setting with rupturing capacity of 36 KA incl cutting the frame of existing panel to suit the new MCCB incl taking down the old MCCB complete of Make : L&T Cat No: CM98065OOPO or equiv in ABB/Siemens all as specified and directed by Engr-in-Charge. \nNote: The cost of making good is deemed to be included in the quoted rates | 5 | Each | |
| 21 | 21 | S&F in repairs MCCB, 4 pole, (Ics=100% of Icu) 200Amps 50 Hz, 415V, adj Thermal & Fixed Magnetic setting with rupturing capacity of 25 KA incl cutting the frame of existing panel to suit the new MCCB incl taking down the old MCCB complete of Make : L&T Cat No: CM90634OONO or equiv in ABB/Siemens all as specified and directed by Engr-in-Charge. \nNote: The cost of making good is deemed to be included in the quoted rates | 10 | Each | |
| 22 | 22 | S&F in repairs MCCB, 4 pole, (Ics=100% of Icu) 100Amps 50 Hz, 415V, adj Thermal & Fixed Magnetic setting with rupturing capacity of 30 KA incl cutting the frame of existing panel to suit the new MCCB incl taking down the old MCCB complete of Make : L&T Cat No: CM97933OOK2 or equiv in ABB/Siemens all as specified and directed by Engr-in-Charge. \nNote: The cost of making good is deemed to be included in the quoted rates | 20 | Each | |
| 23 | 23 | S&F in repairs MCCB, 4 pole, (Ics=100% of Icu) 63Amps 50 Hz, 415V, adj Thermal & Fixed Magnetic setting with rupturing capacity of 30 KA incl cutting the frame of existing panel to suit the new MCCB incl taking down the old MCCB complete of Make : L&T Cat No: CM97933OOH2 or equiv in ABB/Siemens all as specified and directed by Engr-in-Charge. \nNote: The cost of making good is deemed to be included in the quoted rates | 20 | Each | |
| 24 | 24 | M&L for earthing complete with galvanised steel plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25mtrs deep below ground level) with top edge of plate not less than 1.5mtrs below normal ground level, connected to GI earth strip of size 32 x 6mm by means of bolts,nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 connected to earthing test point on completion with and including 40 mm bore medium grade GI protection pipe (7.5mtr long) & watering pipe of 20mm bore medium grade GI pipe for earth including PCC chamber pit with cover, watering arrangement with funnel, common salt, charcoal filling, including necessary excavation, earth work & taking down old earthing items in any type of soil complete all as specified and directed by Engr-in-Charge.\nNote: If the desired earth resistance is not obtained, the earth will be redone at no extra cost for the full satisfaction of Engr-in-Charge | 15 | Each | |
| 25 | 25 | M&L for Brickwork with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in (1:4) all as specified and directed by Engr- in-Charge. | 20 | Cum | |
| 26 | 26 | M&L for plastering /rendering in CM (1:4) 10mm thick on fair faces of brick work or concrete surfaces finished fair and even without using extra cement all as specified and directed by Engr- in-Charge. | 25 | Sqm | |
| 27 | 27 | Taking out the existing stone aggregate, sand etc for reuse after cleaning and relaying the same in the area of transformer, plinth, Sub Stns and Panel board yard all as specified and directed by Engr-in- Charge. | 10 | Cum | |
| 28 | 28 | M&L for loose filling of 20 mm graded stone aggregates in plinths of out door transformer, sub stns, panel boards yard complete all as specified and directed by Engr-in-Charge. | 20 | Cum | |
| 29 | 29 | S&F Air termination, single pointed aluminium lightening rod of 12mm dia and 300mm long all as specified and directed by Engr-in-Charge. | 25 | Each | |
| 30 | 30 | Supply and lay Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as specified and directed by Engr-in-Charge. | 75 | RM | |
| 31 | 31 | M&L for connecting / tightening properly of loose / hanging down conductor along with replacement of damaged / broken insulator blocks with new insulators and appropriate fasteners for insulators all as specified and directed by Engr-in-Charge. | 30 | Job | |
| 32 | 32 | S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw all as specified and directed by Engr-in-Charge. | 20 | Each | |
| 33 | 33 | Supply only Aluminum tubular lugs of the following sizes:-\n(a) 16 sqmm to 25 sqmm | 20 | Each | |
| 34 | 34 | (b) 35 sqmm to 50 Sqmm | 20 | Each | |
| 35 | 35 | (c) 70 sqmm to 95 sqmm | 20 | Each | |
| 36 | 36 | (d) 120 sqmm to 185 sqmm | 20 | Each | |
| 37 | 37 | (e) 240 sqmm to 300 sqmm | 20 | Each | |
| 38 | 38 | Supply only copper tubular lugs of the following sizes:-\n(a) 6 sqmm | 30 | Each | |
| 39 | 39 | (b) 10 sqmm | 30 | Each | |
| 40 | 40 | (c) 16 sqmm | 30 | Each | |
| 41 | 41 | (d) 25 sqmm | 30 | Each | |
| 42 | 42 | (e) 35 sqmm | 30 | Each | |
| 43 | 43 | Supply only electrical insulation gloves, Type-4, Test potential 25KV, Working voltage 17KV as per IS 4770 complete all as specified and directed by Engr-in-Charge. Make: Raychem RPG, Cat No: ES-HP-EST4-WH or equiv in any ISI approved make | 10 | Each pair | |
| 44 | 44 | Supply only Electrical clamp meter, CAT III 600V safety rated, capable of measurement of current upto 400A AC, AC/DC Voltage, resistance measurement with backlit and hold function complete all as specified and directed by Engr-in-Charge. Make : Fluke, Cat No:302+ or equiv in Megger/Rishab | 2 | Each | |
| 45 | 45 | Taking down unserviceable/damaged XLPE cable of size upto 35 Sqmm 3.5 Core of any type from trenches/pole/wall etc after necessary electrical disconnection complete all as specified and directed by Engr-in-Charge. | 700 | RM | |
| 46 | 46 | Taking down unserviceable/damaged XLPE cable of size from 50 sqmm to 120 Sqmm 3.5 Core of any type from trenches/pole/wall etc after necessary electrical disconnection complete all as specified and directed by Engr-in-Charge. | 900 | RM | |
| 47 | 47 | Taking down unserviceable/damaged XLPE cable of size from 150 sqmm to 185 Sqmm 3.5 Core of any type from trenches/pole/wall etc after necessary electrical disconnection complete all as specified and directed by Engr-in-Charge. | 550 | RM | |
| 48 | 48 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 200 | RM | |
| 49 | 49 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 200 | RM | |
| 50 | 50 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 300 | RM | |
| 51 | 51 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 200 | RM | |
| 52 | 52 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 200 | RM | |
| 53 | 53 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 250 | RM | |
| 54 | 54 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 250 | RM | |
| 55 | 55 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 250 | RM | |
| 56 | 56 | Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge. Make: Havells/KEI/Gloster/Polycab | 300 | RM | |
| 57 | 57 | Supply only electrical safety gumboots ISI approved with steel toe cap of size 9 UK complete all as specified and directed by Engr-in-Charge. | 10 | Each Pair | |
| 58 | 58 | M&L for cable route indicator using RCC post 1.20 mtr long, top 100 x 100 mm & bottom 200 x 200 mm, in cement concrete (1:2:4) type B1 (using 20mm graded stone aggregate) suitably reinforced with height not less than 50 cm above GL with engraved marking \" MES HT CABLE \" in bold letters during refilling of the trench complete all as specified and directed by Engr-in-Charge. \nNOTE : The spacing between two consecutive cable route indicators shall not be more than 50.0 meters & also shall be provided at each & every bend or corner. | 50 | Each | |
| 59 | 59 | M&L for Chain link fencing incuding line wires , any mesh , any size and type fixed to any type of standard rails/ angles with straining bolts , incl provn of binding wire incl taking down the unseviceable chain link fencing all as specified and directed by Engr-in-Charge. | 300 | Kg | |
| 60 | 60 | M&L for MS angle iron post struts in fencing including cutting top to shapes as directed drilling holes, notching for wire etc conforming to Fe-290 Gde-E165 and painting with one coat of redoxide primer and two coats of aluminium paint and taking down old unservicable angle iron fencing post all as specified and directed by Engr-in-Charge. | 200 | Kg | |
| 61 | 61 | M&L for preparation of old painted steel surface of LT/HT street light steel tubular poles above GL/Coping including cross arms channels, Flat iron Clamps in LT/HT OH line by scrap- ping with wire brush and applying one coats of aluminium paint including pole numbering all as specified and directed by Engr-in-Charge. | 280 | Job | |
| 62 | 62 | M&L for PCC platform of size 600 x 500 x 150 mm in PCC (1:2:4) type B1 (using 20mm graded stone aggregate) after taking down the existing LT panel of size 500 x 400 mm and reinstalling the same on the new platform incl disconnection and reconnection of LT cables, dismantling of existing platform complete all as specified and directed by Engr-in-Charge | 1 | Each Job | |
| 63 | 66 | Supply, install, commissioning & testing of CPRI type tested maintenance free, low carbon copper coated earth rod of 3.0 metre electrode having diameter 17.2 mm with copper coating thickness of 250 micron tested as per IEC 62561-2 provided with universal clamp made of SS to connect earth rod with the flat conductor. Earth conductivity enhancing compound shall be of 25 Kg/pit & tested as per IEC 62561-7, TCLP tested. The above arrangements shall be provided with heavy duty earth chamber of 5000 Kg load bearing capacity complete including excavation, returning & filling & removal of earth all as specified & as directed by the Engr-In-Charge.\nMAKE : Cat Part No 5450012, 5450068, 5450058 & 5450030 (for different components) of make OBO or equivalent.\nIMPORTANT NOTES : 1) Design / drawing / BOM of the complete Chemical Earthing system showing the layout & dimensions is to be obtained from OEM strictly keeping in view the actual ground/site requirement & the same is to be got approved from Engr-In-Charge before placing final order to the manufacturer.\n2) Anything missed out in the technical specifications but technically required for efficient working of the earthing system is deemed to be included in the quoted rates.\n3) The entire installation & testing work is to be got done from the OEM or their auth Rep/Sister Concern/Channel Partners only.\n4) The quantity of earth conductivity enhancing compound indicated above is generally for normal/good soils. In case the soil resistivity is high, the quantity should be increased & cost of the same is deemed to be included in the unit quoted rates.\n5) On completion of the complete work/job the Contr is to perform earth resistance tests for each earthing job in the presence of the Engr-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of relevant Standards/IS then the job is to be redone without any extra cost to the Dept till the results are satisfactory. | 14 | Each Job |
AI Tender Summary
Tender Timeline
Jul 23, 2019
11:30 IST
Tender Published
Tender notice published.
CompletedAug 05, 2019
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedAug 07, 2019
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender