| 1 | 1 | Taking down carefully existig copper / aluminium point wiring for light / fan / bell / socket 5/15 Amp points complete with fitting and fixtures such as switches, sockets, c/ rosess, holders and bracket fittings with battens / conduits / wires and making good the disturbed surfaces of walls and roofs etc to match with existing surface complete all as specified and directed. | | 1240 | Per Point |
| 2 | 2 | Taking down unserviceable and serviceable tube light fitting/ceiling light fittings/bldg security lights of any type carefully, old serviceable tube light fitting complete all as specified and directed. | | 376 | Each |
| 3 | 3 | Taking down carefully unserviceable main switches and distribution boards (single phase or three phase) of any capacity with Isolator / MCBs complete all as specified and directed.\n | | 35 | Each |
| 4 | 4 | Taking down/disconnecting carefully old unserviceable services connection from poles and DBs of any size complete all as directed and specified | | 270 | RM |
| 5 | 5 | Taking down carefully old unserviceable sub main wiring and making good disturbed surfaces and matching with existing complete all as specified and directed. | | 450 | RM |
| 6 | 6 | Dismantling house service brackets, any type complete all as specified and directed. | | 7 | Each |
| 7 | 7 | S&F Point wiring complete with 1100 volts grade PVC FRLS insulated unsheathed cable of copper conductor, multi stranded of size 1.5 Sqmm, single core, drawn through & including PVC rigid concealed conduit, medium grade of suitable size (not less than 20mm dia )duly ISI marked with all accessories such as bends, reducers, spacers, saddles, junction boxes, bakelite sheets, sizes for mounting switch/sockets, fan regulators etc complete with and including continuous earth wire of size 1.5 Sqmm, single core, PVC FRLS copper conductor, insulated, unsheathed,stranded (Green colour) connected to common earth dolly complete all as specified for following : \n(a) One light/fan/bell/Bldg security light point controlled by one single pole one way switch. | | 488 | Per Point |
| 8 | 8 | All as per item No 7 above but one 3 pin, 5 Amp, socket outlet on the independet board controlled by one single pole one way switch but not below the switch board. complete all as specified and directed. | | 110 | Per Point |
| 9 | 9 | All as per item No 7 above but one 3 pin 5 Amp, socket outlet point on the same board controlled by one single pole one way switch. complete all as specified and directed.\nNote for item No 07 to 09 : The rate of cutting chase for conduits and making good to existing surface wall are included in quoted rates where as applicable. | | 60 | Per Point |
| 10 | 10 | All as per item No.7 here-in-before but wiring with 2.5 sqmm copper cable and 2.5 Sqmm copper cable as continuous earth wire for one 6 pin 5/16 Amps socket out let on independent board complete all as specified and directed. Note : The rate of cutting chase for conduits and making good to existing surface wall are included in quoted rates where as applicable. | | 65 | Per Point |
| 11 | 11 | All as per item No.7 here-in-before but wiring with 4 sqmm copper cable and 4 Sqmm copper cable as continuous earth wire for one 6 pin 5/16 Amps socket out let on independent board complete all as specified and directed. Note : The rate of cutting chase for conduits and making good to existing surface wall are included in quoted rates where as applicable. | | 13 | Per Point |
| 12 | 12 | All as per Item No.7 above but copper cables drawn through existing PVC/steel conduit and accessories and in existing sunken boxes for One light /Fan/Bell point point controlled by one single pole one way switch. complete all as specified and directed.\n | | 367 | Per Point |
| 13 | 13 | All as per Item No.7 above copper cables drawn through existing PVC/steel conduit and accessories and in existing sunken boxes for One 3 pin, 5 Amp, socket outlet on the independet board controlled by one single pole one way switch but not below the switch board. complete all as specified and directed. | | 56 | Per Point |
| 14 | 14 | All as per Item No.7 here-in-before but copper cables drawn through existing PVC/steel conduit and accessories and in existing sunken boxes for One 3 pin, 5 Amp, socket outlet point on the same board controlled by one single pole one way switch. complete all as specified and directed. | | 36 | Per Point |
| 15 | 15 | All as per item No.10 above but wiring with 2.5 sqmm copper cable and 2.5 Sqmm copper cable as continuous earth wire drawn through existing PVC/Steel conduits, accessories and existing sunken boxes for one 6 pin 5/16 Amps socket out let on independent board. complete all as specified and directed. | | 35 | Per Point |
| 16 | 16 | All as per item No.10 above but wiring with 4 sqmm copper cable and 4 Sqmm copper cable as continuous earth wire drawn through existing PVC/Steel conduits, accessories and existing sunken boxes for one 6 pin 5/16 Amps socket out let on independent board. complete all as specified and directed. | | 10 | Per Point |
| 17 | 17 | S&F Switch piano flush type 5 amps, single pole one way ISI marked. complete all as specified and directed. | | 1072 | Each |
| 18 | 18 | S&F bell push flush type 5 amp single pole, one way duly ISI marked. complete all as specified and directed. | | 45 | Each |
| 19 | 19 | S&F Switch piano flush type 15 amps, single pole, one way ISI marked. complete all as specified and directed. | | 123 | Each |
| 20 | 20 | S&F Socket outlet 2 in 1, 3 pin, 5 Amps, piano flush type . complete all as specified and directed. | | 262 | Each |
| 21 | 21 | S&F Socket outlet, 2 in one 6 pin 5 and 15 Amps piano flush type duly ISI marked. complete all as specified and directed. | | 123 | Each |
| 22 | 22 | S&F Ceiling rose surface type, bakelite 65 x 50mm, 2 to 3 terminals duly ISI marked.complete all as specified and directed. | | 592 | Each |
| 23 | 23 | S&F Lamp holder insulated body threaded dome pattern,suitable for bracket / batten fitting ISI marked complete all as specified and directed. | | 222 | Each |
| 24 | 24 | S&F Fan regulator AC,step type socket size single phase 230 volts,50 Hz,duly ISI marked complete all as specified and directed. | | 156 | Each |
| 25 | 25 | S&F in replacement of LED 20 W indoor decorative batten with extruded aluminium housing fixed to wall/ ceiling etc complete with efficient heat dissipation with polycarbonate diffuser & integrated electronic driver. Make-Havells, Model-ENDURALINEARNEOBS20WLED830SPCWH or Equivalent of Philips/C&S. as approved by GE | | 165 | Each |
| 26 | 26 | Refixing only Tube Light fittings complete all as specified and directed.\nNote: Old Tube Light fittings as retrived from item No 2 here-in-before shall be used. | | 71 | Each |
| 27 | 27 | S&F in replacement Surface and wall mounted LED 18 Watt batten with polycarbonate housing & integrated electronic driver. Make- Havells Cat part No-LHEXBQP7IN1W018 or equivalent CG/Bajaj as approved by GE. complete all as specified and directed. | | 35 | Each |
| 28 | 28 | S&F LED bulb of 10 watt complete all as specified and directed.Make-Havells,Model No-LED ADORE 10W B22 CDL BALL LAMP or other equivalent make as approved by GE. | | 222 | Each |
| 29 | 29 | S&F Bell AC 230 volts, single phase complete all as specified and directed | | 45 | Each |
| 30 | 30 | S&Fin replacement Recess and surface mounting LED flat panel 2'x2' made of CRCA sheet duly powder coated with high efficient LEDs & glare free full opal diffuser .IP20 of 36 W . Make-Crompton Cat part No POLARIS III-LCTLSN-36-CDL or equivalent Havells/ Bajaj as approved by GE. | | 41 | Each |
| 31 | 31 | S & F bldg LED Security light fittings 25 watts .including GI bracket bend to shape made out of GI pipe light grade 25 mm of suitable size up to 1.2 mtr long etc complete with MS clamps duly painted with two coats of aluminium paint with nuts/bolts/washers and all fixing arrangements to pole/wall including connecting up with 2 core cable all as specified and directed. Make- Crompton,Model-ASTRA, Cat Part No-LSTS-25-CDL or Equivalent of Havells/Bajaj. as approved by GE | | 32 | Each set |
| 32 | 32 | S&F street light fitting LED Street light 15 Watt 5700K made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening separate driver compartment with IP 65 protection and impact resistance of IK07. Make- CG cat part No-LSTS-15-CDL or equivallent of Crompton Greaves/ Havells including GI Bracket for street light fitting bend to shape made out of GI pipe light grade '25mm of suitable size upto 1.2 mtr long etc complete with MS clamps duly painted with two coat of aluminum paint with nuts/bolts/washers and all fixing arrangement to pole /wall including connecting up with 2 core cable complete all as specified and directed. | | 32 | Each set |
| 33 | 33 | S&F in repair Factory made sheet metal enclosures single door type made out of CRCA 1.2 mm thick M.S sheet, powder coated, concealed in wall, TPN DB with 200 Amps rated bus bar, 8 way, 415 volts, vertical type, dust and vermin proof,suitable for incorporation of MCBs duly cocealled in wall, factory made,including making good distrubbed surfaces with matching colour, complete all as specified and directed. | | 2 | Each |
| 34 | 34 | S&F in repair Factory made sheet metal enclosures single door type made out of CRCA 1.2 mm thick M.S sheet, powder coated, concealed in wall, TPN DB with 200 Amps rated bus bar, 6 way, 415 volts, vertical type, dust and vermin proof,suitable for incorporation of MCBs duly cocealled in wall, factory made,including making good distrubbed surfaces with matching colour, complete all as specified and directed. | | 1 | Each |
| 35 | 35 | S&F in repair Factory made sheet metal enclosures single door type made out of CRCA 1.2 mm thick M.S sheet, powder coated, concealed in wall, TPN DB with 200 Amps rated bus bar, 4 way, 415 volts, vertical type, dust and vermin proof,suitable for incorporation of MCBs duly cocealled in wall, factory made,including making good distrubbed surfaces with matching colour, complete all as specified and directed. | | 9 | Each |
| 36 | 36 | S&F Sheet metal enclosures double door, factory made, made out of CRCA mild steel sheet 1.2 mm thick with matellic painting, FP-42 protection surface mounting 240 volts, 200 Amp rated enameled neutral bus bar 12 way dust and vermin proof suitable for incorporation of Isolator / MCBs. duly concealed in wall and making good the distrubed surface and colour matching complete all as specified and directed. Make - Make - HPL/Standard/Havells as approved by GE | | 1 | Each |
| 37 | 37 | S&F Sheet metal enclosures single door, factory made, made out of CRCA mild steel sheet 1.2 mm thick with matellic painting, FP-42 protection surface mounting 240 volts, 200 Amp rated enameled neutral bus bar 8 way dust and vermin proof suitable for incorporation of Isolator / MCBs. duly concealed in wall and making good the distrubed surface and colour matching complete all as specified and directed. Make : - Make - HPL/Standard/Havells as approved by GE | | 10 | Each |
| 38 | 38 | S&F Sheet metal enclosures single door, factory made, made out of CRCA mild steel sheet 1.2 mm thick with matellic painting, FP-42 protection surface mounting 240 volts, 200 Amp rated enameled neutral bus bar 4 way dust and vermin proof suitable for incorporation of Isolator / MCBs. duly concealed in wall and making good the distrubed surface and colour matching complete all as specified and directed. Make : - Make - HPL/Standard/Havells as approved by GE | | 12 | Each |
| 39 | 39 | S&F of Isolator/MCCB Thermal based release adjustable type 4 pole 100 Amps 50 Hz 415 Volts with rupturing capacity 16 KA including testing,complete all as specified and as directed. | | 2 | Each |
| 40 | 40 | S&F of Isolator/MCCB Thermal based release adjustable type 4 pole 63 Amps 50 Hz 415 Volts with rupturing capacity 16 KA including testing,complete all as specified and as directed. | | 10 | Each |
| 41 | 41 | S&F in repairs MCB, SPN, 63 Amps, 240 volts duly ISI marked, complete all as specified and directed. | | 23 | Each |
| 42 | 42 | S&F in repairs MCB, SP 240 volts,6 Amps to 32 Amps, 10 KA complete all as specified and directed. | | 152 | Each |
| 43 | 43 | S&F MCB four pole 415volts, 100Amps, 10 KA complete all as specified and directed. | | 15 | Each |
| 44 | 44 | S&F Sub main wiring with two single core 2 x 10 sqmm PVC insulated and unsheathed stranded copper conductor alongwith earth wire 4 sqmm drawn in 25 sqmm PVC rigid conduit connected to main board complete all as specified and directed (Two number cable and one number earth wire shall measured together as unit length). | | 100 | RM |
| 45 | 45 | S&F Sub main wiring with two single core 2 x 6 sqmm PVC insulated and unsheathed stranded copper conductor alongwith earth wire 4 sqmm drawn in 25 sqmm PVC rigid conduit connected to main board complete all as specified and directed (Two number cable and one number earth wire shall measured together as unit length). | | 190 | RM |
| 46 | 46 | S&F Sub main wiring with two single core 2 x 4 sqmm PVC insulated and unsheathed stranded copper conductor alongwith earth wire 2.5 sqmm drawn in 25 sqmm PVC rigid conduit connected to main board complete all as specified and directed (Two number cable and one number earth wire shall measured together as unit length). | | 160 | RM |
| 47 | 47 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium\nconductor, served with inner sheathing of PVC tape and overall PVC sheathed in\nservice connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of 10 Sqmm complete all as specifed and directed | | 270 | RM |
| 48 | 48 | M&L for House service bracket (hook type complete with 3.0m long G.I. pipe 40mm dia Med. grade, two nos 900 bends M.S. hook and stay or guy complete all as specifed and directed. | | 7 | Each |
| 49 | 49 | S&F as in repairs XLPE insulated, armoured,1100 volts grade, heavy duty cable of size 25 Sqmm nominal cross section, 4 core, flat or circular, PVC FRLS insulated aluminium conductor, served with inner sheathing of galvanized steel wire or tape and over-all PVC FRLS sheathed in service connections, laid in trenches, duct, through pipe, in floor, on pole including jointing and testing, complete all as specified and directed. | | 200 | RM |
| 50 | 50 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep and not exc 10 Sqm on plan,for laying of cable and getting out,complete all as specified and directed. | | 40.5 | Cum |
| 51 | 51 | M&L Dry and clean fine sand for cable cushioning to underground cable protection, complete all as specified and directed.(Excavation and earth work measured separately).Note- Punned down thickness shall be measured and paid | | 12.15 | cum |
| 52 | 52 | S&F in repair Cover to underground cable with one layer of bricks using sub class ‘B’ bricks (old size) laid flat across the cable complete all as specified and directed. (Excavation and earth work measured and paid separately). | | 1.304 | PER 1000 Nos |
| 53 | 53 | Returning, filling in, earth including spreading, leveling watering and well ramming in layers each not exceeding 25cm thick each layer, complete all as specified and directed. | | 23.4 | Cum |
| 54 | 54 | Removal of surplus soil to a distance not exc. 50 metre and depositing where directed at a level not exc. 1.5 metre above the starting point complete all as specified. | | 14.5 | Cum |
| 55 | 55 | S&F in replacement Electronic ballast pre wired AC supply 230 V 50 Hz suitable for 36 watt tube light fittings ISI marked.complete all as complete all as specified and directed.. | | 90 | Each |
| 56 | 56 | Supply and fix fluorescent tube rod 36/40 watt ISI marked. complete all as specified and directed. | | 85 | Each |
| 57 | 57 | M & L earthing complete with galvanized steel plate elecrode of size 60 cm x 60cm x 6.3 mm thick burried directly in ground vertically to a depth not less than 2.5 mtr below the ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level. Earth plate surrounded by 15mm thick packed alternative layers of charcoal dust and comman salt, earth lead GI wire of 4mm dia (8 SWG) by means of bolts , nuts, check nuts and washers of galvanised iron with thimbles. The other end of GI earth wire is connected to main switch board and protected by light grade GI pipe of 15 mm bore. provision of 20mm bore light grade GI pipe for watering including GI funnel and wire mesh for watering . Pipe shallbe provided vertically upto top level of earth pit and then taken horrizontally to the earth pit including necessary execution and earth works, PCC chamber in Cement concrete ( 1:3:6 ) type C-2 using 40 mm graded stone aggregate and RCC cover and complete all as shown in electrical plate No 3 of MES schedule (Part-I) of 2009 complete all as specified and directed. \nNote: Necessary earth work is included in quoted unit rate. | | 14 | Each set |