Asia-Pacific Economic Cooperation, APEC,APAC ( Asia Pacific)
20-10-2023
Work Detail
Project Overview: Emanuel County Schools Currently Seeking Proposals For Upgrading The Pumping Station At Swainsboro Primary School. The Proposal Should Include But Is Not Limited To Removal And Replacement Of Existing Pumps, Valves And Piping The Central Control Panel With Circuit Breakers; Motor Starters And Automatic Pumping Level Controls; Heater; Priming Pumps; Ventilator, And All Internal Wiring And Additional Components Needed.Stadard Equipment: Including But Not Limited To, Two Vertical, Close-Coupled, Vacuum-Primed Pumps Non-Clog Pumps, Each Capable Of Delivering 344 Gpm At 49 Tdh With A Required Static Suction Lift Of 16 , And Each Driven By 10 Hp, 1800 Rpm, 3 Phase, 60 Cycle, 460 Volt Motor; Valves, 4 Internal Piping; Central Control Panel With Circuit Breakers; Motor Starters And Automatic Pumping Level Controls; Heater; Priming Pumps; Ventilator, And All Internal Wiring, Relay Logic Float Switch Level Controls, High Water Alarm, Automatic Alternator, Vacuum Priming System, Pump Failure/Prime Failure Via Common Alarm Contact, Individual Running Time Meters, Removable Float Switch Access Cover Plate, Compound Pressure Gauges, Spare Mechanical Seal And Volute Gasket.