Construction Work – Heidi Abel Housing Estate_Bkp 244.0 Ventilation System. 4.4.1 Bkp244.1 Apartment Ventilation Exhaust Air Systems With Follow-Up Airflow Over The Facade Are Planned. The Outside Air Outlets Are Supplied By The Ventilation Contractor And Installed On Site By The Woodworker. The Wet Cells And Interior Reduits Are Equipped With Disc Valves (Continuous Operation, Co2 Regulation Via Room Sensors Per Apartment). The Kitchens Are Equipped With Recirculation Hoods And Activated Carbon Filters Supplied By The Customer. Exhaust Air Monoblocks Are Installed On The Roof To Convey Air. Waste Heat From The Exhaust Air Is Used Using Exhaust Air Devices And Heat Pumps (Supplied By The Heating Contractor). 4.4.2 Bkp244.2 Cellar Ventilation The Cellars Are Equipped With A Mechanical Ventilation System. Fresh Air Is Only Introduced When The Humidity In The Area Is Lower Than In The Basement Rooms. Periodic Ventilation Of The Basement Rooms Is Planned. Regulation Is Carried Out Using A Humidity Sensor. 4.4.3 Pump House The Pump House Is Equipped With A Mechanical Exhaust System. Of Course, Fresh Air Is Introduced When The Exhaust Fan Is Running. The Exhaust Air Is Equipped With An Activated Carbon Filter To Reduce Odors. Periodic Ventilation Of The Pump House Is Planned. During A Service Call, The Exhaust Fan Can Be Overridden Manually.