Fire-Prevention Installation Works – Renovation Of Town Hall With Cultural Center: Fire Extinguishing Technology. In Accordance With The Fire Protection Concept, The Town Hall Will Have Full-Surface Sprinklers (Ground Floor To 4Th Floor, All Areas, As Well As The Foyer/Cloakroom On The 1St Basement And Storage On The 1St Basement). The Design Of The Central Water Storage And The Sprinklers On The Areas Is Carried Out According To The Following Parameters: - Sprinkler System Class 1 (Very High Availability) - Fire Hazard Class For Meeting Places (Foyer Area Ground Floor) Oh4 - Effective Area Oh4, Wet System: 360 M² - Max. Permissible Protective Area Per Sprinkler: 12 M²