Tender Brief Tender For Supply, Installation, Testing and Commissioning Of Air Conditioning System At Different Ejlases Under District Court C Us Asansol ,Paschim Bardhaman...........Electrical Installation Work.
City Asansol
State West Bengal
Document Fees Refer document
EMD INR 64729.0 /-
Tender Value Refer document
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Supply, Installation, Testing and Commissioning Of Air Conditioning System At Different Ejlases Under District Court C Us Asansol ,Paschim Bardhaman...........Electrical Installation Work.

Key Dates

Publish Date 10-06-2026
Last Date of Bid Submission 25-06-2026
Tender Opening Date 29-06-2026

Contact Information

Company Name Public Works Department
Contact Person Sr.Superintending Engineer
Address Office of the Sr. Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103

BOQ Items

Name of Work:- S.I.T.C of Air Conditioning System at different Ejlases under District Court C us Asansol ,Paschim Bardhaman………..Electrical Installation Work.
Sl. No. Item Description
1I. CABLE AND CABLE LAYING :
2Supplying only the following 1.1 KV grade PVC insulated A/Al. Cable as below:[Havells/RR/PolyCab/EIC Approved]:i).4 core 70 sq mm. [For AC New & Existing VTPN DB]
3Laying of the following PVC A/Al cable on wall/surface including S & F MS saddles with GI (HOT DIP) Wire earthing attachment, making holes etc. as necessary mending good damages and painting as below:i).4core 50sq mm to 4core 90sq. Mm. with 2X10SWG GI (Hot Dip) Wire.
4Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed
5Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.i). Above 35 sqmm to 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc.
6Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core
7Supplying & fixing medium gauge GI Pipe of 100mm dia ( ISI-Medium) Protection with necessary fittings and jointing metarials as required
8Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. With 25x25x3mm angle iron support.i). 300x50x1.25mm (18SWG)
9ii). 200x50x1.25mm (18SWG)
10Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.i). 300x50x1.25mm (18SWG)
11ii). 200x50x1.25mm (18SWG)
12Supply & Fixing of perforated GI cable tray tee with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.i). 300x50x1.25mm (18SWG)
13ii). 200x50x1.25mm (18SWG)
14Laying of cable as below, on existing Cable Tray and binding & laying properly with suitable size GI wire .(i). From 70sqmm to 150sqmm.
15Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.i). 8 SWG.
16II. CABLE AND WIRE END FINISHING :
17Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :i).For 4 core 70 sq mm.
18Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials.i).For 4 core 70 sq mm.
19Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes.................i).2.5 sq mm.
20ii).4.0 sq mm.
21iii).6.0 sq mm.
22iv).10.0 sq mm.
23III. LT-PANEL BOARD :
24LT-FEEDER BOX AT JUDICIAL COURT :S.I.T.C of Outdoor Type LT-Feeder Pillar Boxes of IP-54 protected,415V,3Ø,4 wire, 50Hz as suitable size(approve by EIC) made with 3mm thick MS-CRCA steel sheet body & canopy of 5mm thick (TATA/ JINDAL/SAIL) as body meterial on 50mmX50mmX6mm angle iron frame, cubical compart-mentalized floor-mounted,dust and vermin proof powder coated box ,having front side & rear side openable hinged door with door handle and double pad locking arrangement.The enclosure exterior shall be painted with polyurathene paint (colour Light Gray&D.A Gray) There should be proper ventilation spout at the centre of the top edge on either side. The feeder box should be erected by 4nos. /6 nos. MS/C channel leg attachment of suitable size & length fixed over suitable brick structure with plaster and neat cement finish by punning work and to be painted the basement by two coats of paint over two coat of primer.must be attached name plate tray.
25Interconnection between 415 V TPN-SFU units of following sizes (As per direction of EIC)in LT-Panel Chamber and neccy connection as required from Bus-Bar Chamber with suitable size copper wire or by copper bar with proper socketting. Bus-Bar will be supported by FRP/DMC insulator.The Panel Board should be provided with following accessories item, complete as required with Rotary Handle with necessary spader link for MCCB/Main Switch/Change Over operation.[Make: L&T/SIEMENS/ABB/As per choice of EIC][A] METERING :(i) Digital flush pattern type voltmeter (0-500 Volt) with built in selector switch - 1 Set.(ii) Digital flush pattern type ammeter with built in selector switch and one set of 3 Nos. CTs(Kappa Make) of ratio 250/5A 1st-Class accuracy and 15VA buden - 1 Set.(iii) 3 Nos. phase indication LED lamps(R,Y,B) with inbuilt MCB protection etc. as required - 1 Set.(iv) EI Danger Board (6”X4”) – 2No.
26[B] INCOMER:i).415V, 250 Amp TPN Cubical type Switch Disconnector Fuse Unit with suitable HRC-DIN Fuse-link. – 1No.ii).415 Volt 415 Amp Electrolyte Copper Bus bar of 4 x 40mm x 5mm) - 1 Set.[C] OUTGOING :i).415V, 125 Amp TPN Cubical type Switch Disconnector Fuse Unit with suitable HRC-DIN Fuse-link. – 7No.ii).415V, 100 Amp TPN Cubical type Switch Disconnector Fuse Unit with suitable HRC-DIN Fuse-link. – 2No.
27IV. LINE PROTECTIVE DEVICEs WITH ALLIED DISTRIBUTION BOARDs :
28Supply and Installation of double-reversible-door Vertical TPN MCB Distribution board enclosure only,suitable for flush mounting and surface mounting with 160-250Amp CU busbar for each phase, with 2 nutral bar,2 earth bar and cable ties for cable management,pre-fitted masking sheet with IP-43 protection, moisture proof & damp proof heavy meterial concealed in wall or total established on angle iron frame on wall(40mmx6mm)& mending good the damages to original finish with wall matching putty & painting & suitable for MCCB incomer & TP MCB/SP MCB as outgoing,Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. #[Make : Legrand /Simens/Eqv Make.]#i).8WAY: Upto 160 A Enclosure... [For Three Phase AC Power][Judical Court Building - 4nos, Heritage Building - 4nos, Civil Court Building - 1nos., New record Court Building - 1nos]
29Supplying and fixing double door Horizontal-TPN-MCB DB housing for Four pole Isolator as incomer and DP-MCBs /SP-MCBs ('C'-curve,10kA,16-32A) as outgoing with IP-43 protection, concealed in wall after cutting the wall & mending good the damages to original finish & necy. wall matching putty & paint as required or total establishment on angle iron frame(25mmX6mm)on wall incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as required inside the box. #[Make : Legrand /Siemens/ABB Make]#i).6 Way Enclosure... [For Single Phase AC Power Existing & new ][Judical Court Building - 2nos, Heritage Building - 2nos]
30Supplying and fixing 240/415V, following rating MCCBs & MCBs (Legrand Make) of Breaking capacity 10kA for MCBs & 35kA for MCCBs & \\"C\\"characteristics on existing din rail for newly installed DBs and necessary connection as required. #[Make : Legrand Ekinox/Siemens/ABB Make]#i).100A FP MCB Isolator
31ii).6-32A(10kA) SPMCBs.
32iii).32A(10kA) TP MCBs.
33iv).63A(10kA) TP MCBs.
34v).125A(35kA) FP MCCBs.
35Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm/32mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.i). 2x56/0.3 (4sqmm)+1x36/0.3(2.5sqmm) ECC.
36ii). 4x80/0.4 (10 sqmm)+2x84/0.3(6sqmm) ECC. [VTPN to New TPNDB & Existing]
37iii). 4 x 84/0.3 (6 sqmm) + 2 x 56/0.3 (4 sqmm) ECC. [VTPN -Starter-Loop Box t- 3- AC-ODU]
38Cutting Channel of size (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles.25 mm dia 3 mm thick polythene pipe without earth continuity wire.
39V. EARTHING :
40Excavation of soil for installation of Earth Electrode and filling & ramming.For Morrum Soil.
41Extra for treatment of soil by using salt & charcoal or coke .
42Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. Long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. Long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. Below the ground level as below:a) By TATA-Medium GI pipe.
43Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mmX6 mm on wall having clearance of 6mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
44Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having 6 mm clearance from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
45Connecting the equipments to earth busbar including S & F 6 SWG GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.
46VI. MISCELLANEOUS :
47Supply & Fixing Moisture proof,water-proof outdoor type IP-65 protected 6-Module PVC cable looping box (Legrand Plexo3 6019 96/ Hensel/ L&T/ Siemens) body enclosure comprising of one no. 415 V,32Amp FP Isolator on din channel ('C'-curve,Legrand make), with 4 way copper terminal and having lined with rubber gasketed top cover should be fixed on ms channel by screws,nuts,bolts washers etc, necy. socketting, rubber gasketted entry and exit as mending the good damages as original with proper finishing at terminal end is required.
48Supply & Fixing 415V,Three phase DOL starter for AC Controller 5HP & 7.5 HP,13-21A O.L relay setting. [L&T ML2 DOL(Heavy Duty) - SS90702POCO for 440V should be fixed on angle iron frame with neccesary connection by suitable size of copper wire and mending good the damages to original finish as per direction of EIC.
49Supply & Fixing of 21 Amp Single Phase Motor Starter (Make-Electron OLP 3+ Air Conditioner Starter With Digital Display/Similar (For 1.5/2.0 Tons) power switch in Modular GI box with necessary connection with suitable size of copper wire as required.
50Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. Please Enable Macros to View BoQ information

Other Detail

Information Source https://tenders.wb.gov.in/nicgep/app
Download FileName File Description File Size
Download 5fb77e6e-a00f-4852-a681-39873a417f6a.html Tender Documents 0 KB
Download BOQ_5084003.xls Tender Documents 0 KB
Download new2911.pdf Tender Documents 0 KB
Download Tendernotice_1 (12).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.