Indian Tenders

Tender Notice

TDR 55923582
Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No 25/SE(T)/GNZ/2026-27
Tender ID 2026_MVVNL_1159193_1
Tender Brief Tender For Increasing Capacity Of Distribution Transformers And Related Work At Sugamau, Omega And Upsidc Sub-Station In The Area Of Ee, 33 Kv Gomtinagar Against Business Plan 2026-27
City 33/11 kV S/S HAL POWER HOUSE LUCKNOW
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 34700.0 /-
Tender Value INR 34.69 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Increasing Capacity Of Distribution Transformers And Related Work At Sugamau, Omega And Upsidc Sub-Station In The Area Of Ee, 33 Kv Gomtinagar Against Business Plan 2026-27

Key Dates

Publish Date 11-06-2026
Last Date of Bid Submission 15-06-2026
Tender Opening Date 15-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person S.E., TECHNICAL, LUCKNOW
Address 33/11 kV S/S HAL POWER HOUSE LUCKNOW

BOQ Items

Name of Work:- Increasing Capacity of distribution transformers and related work at Sugamau, Omega and UPSIDC Sub-station in the area of EE, 33 KV Gomtinagar against Business Plan 2026-27
Sl. No. Item Description
1Dragging, loading, carriage and unloading of following store material with proper stacking from any ESC of Sitapur /Raibareli/Lesa Zone to JE's dump store and from store to work site.
233 KV Bus Isolator
3Post Insulator
433 KV Lightening Arrester
533 KV VCB 800 Amp., 750 MVA
633 KV CT 400/200/1 Amp.
733 KV Double T/F Control Pannel with structure.
8600/300/5 AMP, 350 MVA Incoming
9200/100/5 AMP, 350 MVA Outgoing
1011 KV 3x300 SQ MM XLPE
1111 KV 3x185 SQ MM XLPE
12MS Channel 125x65, 3.2Mtr. Long 1,2,3,4 No Pieces for Top channel. 13.10 Kg/Mtr.+wastage.
13MS Angles 75x75x6mm.
14Cost of ACSR Dog Conductor
15STP 11 Meter Long.
16MS Channel 100x50 mm (9.6 Kg/Mtr.).
17MS Channel 125x65 sqmm. Top Channel.
1811 KV Disc Fitting Dog/Racoon 70 KN B&S
1911 KV Disc Insulator Dog/Racoon 70 KN B&S
20MS Earthing Rod (120x2500)
21MS Angle 65x65x6mm for bracing and etc.
2211 KV 3x300 SQ MM XLPE Cable Outdoor
2311 KV 3x300 SQ MM XLPE Cable Indoor
2411 KV 3x185 SQ MM XLPE Cable Outdoor
2511 KV 3x185 SQ MM XLPE Cable Indoor
26Stay Wire 7/8 swg.
2711 KV Bus Coupler.
2824V Battery
2924V Battery Charger.
30Dismantling & safe shifting of existing & working 33/11 KV 05 MVA T/F from plinth to suitable storage place after opening jumper and cable connections as per instruction of Site Engineer.
31Extemsion and Repairing of Power Transformer Plinth for 10 MVA T/F.
32Plinth of Power T/F (5/10 MVA): Construction of plinth of size 3.46 x4.46 Mtr. For 5MVA T/F having 0.4 Mtr. above ground level. The work includes excavation of foundation, base concretion of CC 1:4:8 ratio (cement, fine sand & brick ballast) first class brick work in cement morter of rtio1:4 foundation CC in 1:4:8 ratio(cement, find sand & brick ballast) and RCC work in ratio 1:2:4 (cement, coarse sand and stone grit of 20mm gauge using MS bar of (All Material provide by contractor.
33Fabrication, Errection & Grouting of Substation Structure:
34Isolator Structure: Fabrication of Isolator Structure 3.5 mtr in height by using MS Channel 125x65 Sq.mm & Angle 75x65 Sq.mm as per Drg. digging of two no. pits of size 1.075x0.9x0.3 mtr. providing Stone Pad at the bottom of the pit and grouting of two legs of the isolator structure in CC(cement coarse sand and stone grit of 20mm gauge) of the ratio 1:4:8 in block of 1.075x0.3 mtr. including all civil material, T&P complete in all respect. The work includes dragging, shifting up to 40 Mtr., raising and erecting the two legs with runner on proper alignment and level and plumb. Both plinths of the isolator structure shall be properly finished with smoothing of edges.
35Lightening Arrestor, P.I. & CT Structure : Fabrication of Lightening Arrestor, P.I. & CT Structure 3.5 mtr. in height with using of MS Channel 125x65 Sq.mm. & Angle 75x75x6 as per Drg. digging of two no pits of size 1.075x0.9x0.3 mtr. providing stone pad at the bottom of the pit and grouting of two legs of the Structure in CC(cement coarse sand and stone grit of 20mm gauge) of the ratio 1:4:8 in block of 1.075x0.3 mtr. including all civil material, T&P complete in all respect. The work includes dragging, shifting up to 40 Mtr., raising and erecting the two legs with runner on proper alignment and level and plumb. Both plinths of the structure shall be properly finished with smoothing of edges.
36Plinth of VCB : Construction of Plinth of size 2.0 mtrx1.5mtrx0.9mtr. suitable for erection of upper structure of 33KV VCB including grouting of anchor bolts in proper alignment and level. Scope of work includes excavation of foundation base concreting in CC 1:3:6 (cement, find sand & brick ballast) 1st class brick work in cement mortor ratio 1:4:8 (cement, coarse sand and stone grit of 20mm gauge).
37Erection, installation and Testing of 33/11KV Power T/F (5/10 KVA)
38Erection, installation and Testing of 33/11KV (05/10 MVA) T/F in a levelled position of the plinth. The work includes shifting of T/F to the site & installation within the S/S premises, assembling, fixing and fitting of all accessories and filling of T/F oil to the desired level and ensuring that there is no leakage. All jumpering & connection are included in the scope of work.
39Boring Type Earthing : Earthing for power T/F by way of boring and lowering of 40mm dia,2.9 mm thick GI Pipe B class from ground upto the water level (minimum 60 feet deep) as per standard practice as per RESPO/REC Drg to ensure below 01 ohm resistance with making of earth pit of 300x300 mm & 1 feet deep with Cover.
40Neutral Stand : Fabrication and grouting (1:4:8) of MS Channel 100x50 mm in L Shape & in proper size and alignment to provide support for the two separate earthing strips (50x6)mm size for power transformer neutral including supply & fixing of two no. flexible copper bonds for neutral earthing as per Drg.
41Cable Stand (Suitable for 11 KV & 33 KV : Fabrication and erection of cable support made of two pieces of MS channel 125x65mm, 3.0 mtr. long joined to each other by means of 5 no. MS Fat 50x6mm pieces of size 150mm long each by welding at equal intervals as per drawing and grouting in block of size 300x300x700mm (1:4:8) complete with one coat of ready mixed primer and two coats of Al. Paint. This includes providing of four no. MS Clamp made of MS Flat holding the cable including nuts & bolts and fixing of XLPE cable.
42Installation of Isolators: Assembling and installation of line/ bus isolator on the isolator structure adjusting of opening mechanics in proper alignment so as to ensure smooth operation of the same. In case of line isolator proper operation of earth links shall also be ensured. The work includes fabrication & proper connection with earthmat by G.I. erth strip 50x6mm for proper earthing of as per norms of UPPCL flexing if required.
43Installation of P.I. & Lightening Arrestors : Assembling, installation & mounting of 3 No.(1set) L.A. & Post insulator on the L.A & P.I. Structure/complete with making earth connections (separate) and line connections. The work includes of febrication, fixing and earthing work as per norms of UPPCL.
44Installation of CT: Installation of 3 No.(1 set) CT on the CT Structure along with CT Junction Box. The work includes fabrication for proper fixing of C.T. If required and proper commissioning & testing in complete respect as per norms of UPPCL. (CT Junction Box to be provided by Contractor).
45Installation of VCB: Installation of 33KV VCB complete work including commissioning, testing & earthing.
46Installation of Switchgears in Control Room:
47Shifting carefully & installation safely 11KV I/C & O/G bus coupler switchgears from outside the switchgear room placing and fixing of switchgear on foundation providing G.I. Bolt & Nuts of proper size in proper position and alignment and checking, complete work with mounting ofP.T. on incoming S/G with proper testing & commissioning of switchgears.
48Fixing and making Bus Bar connections in between all switchgears after cleaning and tapping with H.T. Tape, empire tape and PVC tape properly, providing and fixing of 6 mm thick Bakelite separators and plugging of all opening & holes with plastic compound complete work as per satisfaction of site incharge.
49Shifting carefully and installation of 33KV Single Transformer Control Panel in Control Room including fixing, bolting & grouting of above as per site requirment including commisioning and testing work complete as per norms of UPPCL.
50HT Cable Laying :
51Laying & dressing of 11KV 3x300 Sq.mm U/G cable Double Ckt. from by excavation of earth in the trench 450mm wide, 900mm deep providing 150mm fine sand cushion below the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable. (All decentralized/consumable materials to be provided by Contractor Expect Cable) & in case of vipin khand, single Ckt. all other criteria is same as above.
52Laying & dressing of 11KV 3x300/3x185 Sq.mm U/G single ckt. if required double ckt cable from 5MVA T/F to 11KV Outgoing Switchgear by excavation of earth in the trench 450mm wide, 900mm deep providing 150mm fine sand cushion below & above the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable. (All decentralized/consumable materials to be provided by Contractor Expect Cable).
53Laying & dressing of 11KV 3X300 Sq. mm /3x185 Sq.mm U/G cable from 11 KV Switchgear in Existing Cable Trench of Switchgear room (All decentralized/consumable materials to be provided by Contractor Expect Cable).
54Hoisting of 11KV Cable for 11 KV switchgears & 33/11KV T/F of requried size.
55Making vertical/horizontal jumper connections using Panther/Dog Conductor with existing busbar gantry through PG Clamps and connecting all equipments with each other through connecting clamps. The work includes all the jumpes from busbar to T/F (1no. T/F bay)
56Construction of Cable trench of size 300x300mm including brick work 1:4 in wall of the trench, brick ballast work in 1:5:10 on foundation plaster 12mm thick with coarse sand 1:4 and surface finishing with cement, providing MS Strip at an interval of 0.5 Mt. and MS Angle (25x25x5mm) running on both the edges of trench.
57Construction of welded frame type control cable trench cover 0.5 Mt. long suitable for trench including cost of MS/Tor Bar.
58(a) Excavation of foundation pit in mix soil/normal soil, soft & hard rack and its back fillingand levelling etc. The size of the pit will be 800x900 mm and having a depth of 1/6 of the full length of the support. Erection of supports by providing stone pad, fixing all clamps and other accessories such as No. Plate, Danger Board, Barbed Wire (2Kg.), Painting etc. as per relevant RESPO/ RES. drawing . This includes any fabrication, if required.(b) Grouting of above supports with cement, concrete of ratio 1:4:8 (CC will be of cement coarse sand &brick ballast) Grouting will be done with the help of wooden/steel formers in a block of size
59Double Support STP 11 mtr. For Outgoing Feeder
60(a) Grouting of stay rods 1800x16 mm including all works of excavation grouting by , cement concrete in size 0.60x0.60x0.3 mtr. with ratio 1:4:8 as per relevant drawing including back filling of earth and proper ramming.(b) Fixing, tightening & nuzzling of stay with the poles and required tension as per RESPO/ RES. drawing. (Stay rod will be provided by contractor).
61Earthing of poles as per RESPO norms . (All the materials supplied by contractor)
62Supply and laying of following size Good Quality Armoured Copper Control Cable as per norms of UPPCL through underground/cable trench interlinking through proper termination between all equipment such as T/F Control panel/protection panel/Battery and Battery Charger/VCB/CTs junction box with the help of proper size cable gland/lug and ferrules including proper dressing with the help of proper size of cable tie. (All decentralized/consumable materials to be provided by Contractor).
63Cable Tray
642x2.5 Sq.mm
654x2.5 Sq.mm
66Painting of all structures and equipments of All Five Substations with good quality ISI Mark one coat of red oxide primer & two coats of Aluminium Paint.One JOB For One S/S .Total 5 S/S(All materials to be provided by Contractor).
67Providing and Fixing of Single Core PVC Cable, 1x240/400/630 sq.mm. & suitable size of Al. lug, nut bolt etc. fixing between Transformer incoming 3x300 Sq.mm XLPE Cable and Transformer 11 KV/LV Side Bushing connector for reducing of tension at LV Side Bushing. (All material supplied by cont.)
68Dismentiling & Extra Civil Works as per site requirement & repair as before.
69Fire Wall Between Power T/F (As per Annexure A& Drawing)
70Approch road in switchyard bu using Interlocking Tiles Edge Bar in Switch Yard and Leveling of Yard by local soil, fine sand and stone greet size 30 to 40 mm.
71Installation of 24 Volt Battery and it charger with connections to existing control circuit complete in all respects. (Exide/Amaron/Luminous Standard Quality.)
72Supply of 40 Watt LED Light
73Supply and fixing of Rubber mat 8/10mm, 2x4mtr. Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 8f2b0fea-6d3d-492c-b831-2213177f1aec.html Tender Documents 0 KB