Indian Tenders

Tender Notice

TDR 55923232
Tendering Authority Public Works Department
Tender No EESectt_nit_08_26-27
Tender ID 2026_CEPWD_566745_4
Tender Brief Tender For Electric Work In Renovation Of Fountain Work At Main Statue Of Gandhi Ji Platform, 2 Nos. Fountain In Main Lawn And Fountain At Chowk No 3 At Main Building Rajasthan Secretariat, Jaipur.
City Electric work/EESECTT
State Rajasthan
Document Fees INR 500 /-
EMD INR 40000.0 /-
Tender Value INR 20 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Electric Work In Renovation Of Fountain Work At Main Statue Of Gandhi Ji Platform, 2 Nos. Fountain In Main Lawn And Fountain At Chowk No 3 At Main Building Rajasthan Secretariat, Jaipur.

Key Dates

Publish Date 11-06-2026
Last Date of Bid Submission 21-06-2026
Tender Opening Date 22-06-2026

Contact Information

Company Name Public Works Department
Contact Person EXECUTIVE ENGINEER
Address THE EXECUTIVE ENGINEER P.W.D. ELECT. DIVISION, SECTT

BOQ Items

Name of Work:- Electric Work in Renovation of Fountain Work at Main Statue of Gandhi Ji Platform, 2 Nos. Fountain in Main Lawn and Fountain at chowk No 3 at Main Building Rajasthan Secretariat, Jaipur.
Sl. No. Item Description
1S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required.
220 mm
325 mm
4Supply and Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required.
51.5 Sq.mm 3 core flat / Round
62.5 Sq.mm 3 core flat / Round
74.0 Sq.mm 3 core flat / Round
8Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required.
9Single pole MCB (With B / C curve tripping characteristics)
106 A to 32 A rating
11Four pole MCB (With B / C curve tripping characteristics)
1250/63 A rating
13SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
14(a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
15(b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
16[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )
17(d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
18(e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
19(f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )
20(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
21(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted)
22Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves.
23Electrolytic grade Aluminium bus bar 6010 grade
24Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required.
25Red/yellow/Green colour
26Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor confirming to IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required.
274 pole Power contactors with following AC 1 Rating
2840 Amp
29Providing & Fixing of Electromechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required.
30One day reserve (Electromechanical type )
31P & F of Direct on line (DOL) / Star - Delta Starter as per IEC type-2 Co-ordination chart of OEM in Existing Panel with circuit breaker having inbuilt overload protection or separate thermal Overload relay , Short circuit, phase loss protection, suitable Contactors, including wiring between switchgears, Indicating lamps for R,Y,B,ON,OFF, Push button for ON, OFF, Volt meter, Ammeter, selector switch for local/remote, auto/manual/OFF operation. Cast resin CT's, provision for potential free contacts making connection, testing etc. as required.
32Direct on line (DOL) Starter with following Motor rating
33Motor rating 0.75 KW
34Star - Delta Starter with following Motor rating
35Motor rating 5.5 KW
36SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate.
374 pole MCCB With Thermal Magnetic release
38125 Amp , 25 kA, adjustable O/L & Fixed S/C setting,
39Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size.
4010.0 Sq. mm
414 core
4235.0 Sq. mm
433.5 core
44Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth.
45SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
46(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
47(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
48© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
49(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
50(e) Testing of earth resistance for value of 5 ohms or less as required.
51(f) Test certificates for confirming above standards from OEM is mandatory.
5217.2 mm thick and 3 Mtr. Long
53Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required.
548 SWG tinned copper Wire
55Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass with suitable lenses on LED / integrated lens diffuser to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated metal case potted driver as a unique BIS R number (as per IS 15885) having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate(Fitting & driver both have separate BIS R number). The System level Luminaire efficacy >=130 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , LED driving output current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K as required.
56High Power LED Flood Light Minimum lumen output 10400 lm
57Providing & Fixing of IK08 IP65 protected 600-800 mm height LED Bollard Luminarie with base plate made of powder coated die cast aluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per engineers choice. LED driving output current <750mA. as required.
58Minimum lumen output 800 lm Bollard
59Providing & Fixing of IK08 IP66 / IP67 protected Rectangular shape LED Step Luminarie made of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 60 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . driver current <750mA as required.
60Minimum lumen output 630 lm Step light
61Providing & Fixing of IK08 IP65 / IP66 protected LED Up - Down Luminarie Wall / Surface mounting made of powder coated die cast alluminium housing with with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 80 Lumen/W. COB LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per engineers choice. LED driving output current <750mA. as required.
62Minimum lumen output 800 lm Up-Down Luminary
63P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra).
6450 mm
65SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal. The motor body of single phase pump shall be of SS and rest of all shall be of cast iron. Shaft of three phase pump shall be of SS 410 grade. All casting parts should be cathod electro deposition (CED) coated. Motor winding shall be 100% copper wire material. Dynamically balanced rotating parts to ensure min. vibration etc. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect.
661.0 HP, 1-Ø, (12 -27) Mtr, (200- 30) LPM
677.5 HP, 3-Ø, (12 -32) Mtr, (1650-400) LPM
68SITC of IP 54 OEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Coordination Chart and made out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection(for three phase pumps), Illuminated ON / OFF push buttons, ammeter, voltmeter, indicating lamps, 2P/4P MCB etc. suitable for following rating motors complete in all respect.
69For single phase Submersible / Monoblock pump
700.5 HP to 1.5 HP (DOL starter)
71For Three phase Submersible / Mono block pump
727.5 HP to 10.0 HP ( DOL starter )
73SITC of Decorative Pole of total Height 4000mm(4-Meter), Bottom Having Casted iron & made out of 132mm dia Ribbed MS pipe 2000mm length & upper part 89mm Dia with 1000mm length.Height of Pole Arm made of 76 mm dia m.s. pipe will be 1000mm having Width 1150mm for Single Arm & 2300mm for Double Arm for fixting the ornamnetal street light.The pole shall have window opening with flush Door with locking arrangment at bottom of the pole to accomodate electrical accessories like MCB, The Decorative pole shall be duly pre treated & painted in UV ray resistant PU coating in approved colour (antique copper finish) the pole shall be erected on CC Foundation 550mm X 550mm X 1000mm size with 4Nos Foundation bolt 20mm X 750mm length.The pole should having cast iron base at the bottom with base plate 550x550x12mm & Joint ring at step down of the pole complete as per attached drawing .
744-Meter Decorative Pole single Arm
75SITC of IP65 Protected Decorative LED Ornamnetal Street Light Suspended Lanterns Made up of Aluminium Spun Canopy with Die Cast Aluminium Spigot.Fitted with Glare free Opctically Designed Prismatic Diffuser Protected LED Decorative Street Light 45W 220-240V 50Hz Integrated Driver Shall be High efficiancy Having system life of 25000 Burning Hours 70% of Initial Lumen Maintained, system efficacy Should gearter than or equal to 75Lumen/W. Power Factor > 0.95 CRI >70 complete in all respect.
7645W Ornamnetal Street Light WW/CW
77SITC of IP67 & IK10 Energy effficent 18W+/-10% LED Ground Mounted Ground Burial Light Made up of Die cast Aluminium, Front Cover SS finish frame with Toghened Glass, Lumen Maintain 50000 hours @ L70,Optic:PC /PMMA material, beam angle 25° ,Operating Voltage Range: 140V~ 270V,CCT 3000K,Lumen Efficacy 75Lum/W* CRI>70, Driver efficency >85%, Underground Mounted
78Ground Burial of Wattage 18W in WW/GREEN
79SITC of IP67 & IK10 Energy effficent 24W+/-10% LED Ground Mounted Ground Burial Light Made up of Die cast Aluminium, Front Cover SS finish frame with Toghened Glass, Lumen Maintain 50000 hours @ L70,Optic:PC /PMMA material, beam angle 25° ,Operating Voltage Range: 140V~ 270V,CCT 3000K,Lumen Efficacy 75Lum/W* CRI>70, Driver efficency >85%, Underground Mounted
80Ground Burial of Wattage 24W in WW/GREEN
81ADD GST Please Enable Macros to View BoQ information

Other Detail

Information Source https://eproc.rajasthan.gov.in
Download FileName File Description File Size
Download 16900954-400e-47dd-ac2d-144c850a1604.html Tender Documents 0 KB
Download BOQ_1008286.xls Tender Documents 0 KB
Download Tendernotice_1 (21).pdf Tender Documents 0 KB
Download Tendernotice_2 (2).pdf Tender Documents 0 KB
Download Tendernotice_3 (1).pdf Tender Documents 0 KB
Download Tendernotice_4.pdf Tender Documents 0 KB
Download Tendernotice_5.pdf Tender Documents 0 KB
Download Tendernotice_6.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.