Indian Tenders

Tender Notice

TDR 55885074
Tendering Authority Directorate Of Urban Affairs
Tender No 3224764-2026
Tender ID 2026_UAD_854951_1
Tender Brief Tender For Annual Plan - 2025-26 - Project No. 1876/26- Supply And Installation Of Ups At Dialysis Centre, Attadappa Under Buy Back Scheme.
City Attadappa, Kannur
State Kerala
Document Fees INR 2030 /-
EMD INR 7800.0 /-
Tender Value Refer document
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Annual Plan - 2025-26 - Project No. 1876/26- Supply And Installation Of Ups At Dialysis Centre, Attadappa Under Buy Back Scheme. , Supply, Installation, Testing And Commissioning Of 20.0Kva/240 Volt True On-Line Igbt Ups ( 3Phase-1Phase ) With Built-In Isolation Transformer Model With Following Configuration. Input : (I) Input Voltage : 360-480 V (Ii) Freequency : 50 Hz+/- 5% (Iii) Input Power Factor : 0.9. Output : (I) Voltage : 220/230V +/- 1%. (Ii) Regulation +/- 1%. (Iii) Frequency : 50 Hz (Iv) Frequency Regulation : +/- 0.05 Hz (V) Power Factor : 0.8 To Unity (Vi) Transient Response : 8%(10%~90%(Linear Load)) (Vii) Voltage Harmonic : 3% (Linear Load) (Viii)Over Load Capacity (%) : 100 To 110% : 5Minutes , 110 To 120% : 2Minutes (Ix) Crest Factor : 3:1. Battery : 20 Nos. 12 Volt/ 100 Ah Tubular Battery, C10 Series (Preferred Make : Exide/Amaron) Including Rack , Connectors & Accessories. Display : Led Indications : Ups On# Battery Low/High# Out Put Voltage Low/High-R,Y,B# Over Load - R/Y/B# Fault# Charger On# Input Voltage Low/High - R,Y,B. Lcd Indications: Input Voltage & Frequency - R, Y, B# Output Voltage & Frequency- R, Y, B# Battery Voltage# Load Level# Working Status# Fault Status. Warranty 2 Year On-Site Warranty For Ups And 3 Year Replacement Warranty For Battery, Including Buy Back Price Of Old 20.0 Kva Ups With With 20 Nos. 12V/100 Ah Tubular Battery , Supply, Installation, Testing And Commissioning Of 10.0Kva/192 Volt True On-Line Igbt Ups ( 3Phase-1Phase ) With Built-In Isolation Transformer Model With Following Configuration. Input : (I) Input Voltage : 360-480 V (Ii) Freequency : 50 Hz+/- 5% (Iii) Input Power Factor : 0.9. Output : (I) Voltage : 220/230V +/- 1%. (Ii) Regulation +/- 1%. (Iii) Frequency : 50 Hz (Iv) Frequency Regulation : +/- 0.05 Hz (V) Power Factor : 0.8 To Unity (Vi) Transient Response : 8%(10%~90%(Linear Load)) (Vii) Voltage Harmonic : 3% (Linear Load) (Viii)Over Load Capacity (%) : 100 To 110% : 5Minutes , 110 To 120% : 2Minutes (Ix) Crest Factor : 3:1. Battery : 16 Nos. 12 Volt/ 100 Ah Tubular Battery, C10 Series (Preferred Make : Exide/Amaron) Including Rack , Connectors & Accessories. Display : Led Indications : Ups On# Battery Low/High# Out Put Voltage Low/High-R,Y,B# Over Load - R/Y/B# Fault# Charger On# Input Voltage Low/High - R,Y,B. Lcd Indications: Input Voltage & Frequency - R, Y, B# Output Voltage & Frequency- R, Y, B# Battery Voltage# Load Level# Working Status# Fault Status. Warranty 2 Year On-Site Warranty For Ups And 3 Year Replacement Warranty For Battery , Including Buy Back Price Of Old 10.0Kva Ups With With 20 Nos. 12V/100 Ah Tubular Battery

Key Dates

Publish Date 09-06-2026
Last Date of Bid Submission 16-06-2026
Tender Opening Date 16-06-2026

Contact Information

Company Name Directorate Of Urban Affairs
Contact Person The Additional Secretary
Address Kannur Municipal Corporation. Civil Station Post, Kannur - 670 002

BOQ Items

Name of Work:- Annual Plan - 2025-26 - Project No. 1876/26- Supply and Installation of UPS at Dialysis Centre, Attadappa under Buy back Scheme.
Sl. No. Item Description
1Supply, Installation, Testing and Commissioning of 20.0KVA/240 Volt True On-line IGBT UPS ( 3Phase-1Phase ) with Built-in Isolation transformer model with following configuration. Input : (i) Input Voltage : 360-480 V (ii) Freequency : 50 Hz+/- 5% (iii) Input Power Factor : >0.9. Output : (i) Voltage : 220/230V +/- 1%. (ii) Regulation +/- 1%. (iii) Frequency : 50 Hz (iv) Frequency Regulation : +/- 0.05 Hz (v) Power Factor : >0.8 to unity (vi) Transient Response : <8%(10%~90%(Linear Load)) (vii) Voltage Harmonic : <3% (Linear Load) (viii)Over Load Capacity (%) : 100 to 110% : 5minutes , 110 to 120% : 2minutes (ix) Crest Factor : 3:1. Battery : 20 Nos. 12 Volt/ 100 Ah Tubular Battery, C10 Series (Preferred Make : Exide/Amaron) including Rack , Connectors & Accessories. Display : LED Indications : UPS ON# Battery Low/High# Out Put Voltage Low/High-R,Y,B# Over Load – R/Y/B# Fault# Charger ON# Input Voltage Low/High – R,Y,B. LCD Indications: Input Voltage & Frequency – R, Y, B# Output Voltage & Frequency- R, Y, B# Battery Voltage# Load Level# Working Status# Fault Status. Warranty 2 year on-site warranty for UPS and 3 year replacement warranty for Battery, including buy back price of old 20.0 KVA UPS with with 20 Nos. 12V/100 Ah Tubular Battery
2Supply, Installation, Testing and Commissioning of 10.0KVA/192 Volt True On-line IGBT UPS ( 3Phase-1Phase ) with Built-in Isolation transformer model with following configuration. Input : (i) Input Voltage : 360-480 V (ii) Freequency : 50 Hz+/- 5% (iii) Input Power Factor : >0.9. Output : (i) Voltage : 220/230V +/- 1%. (ii) Regulation +/- 1%. (iii) Frequency : 50 Hz (iv) Frequency Regulation : +/- 0.05 Hz (v) Power Factor : >0.8 to unity (vi) Transient Response : <8%(10%~90%(Linear Load)) (vii) Voltage Harmonic : <3% (Linear Load) (viii)Over Load Capacity (%) : 100 to 110% : 5minutes , 110 to 120% : 2minutes (ix) Crest Factor : 3:1. Battery : 16 Nos. 12 Volt/ 100 Ah Tubular Battery, C10 Series (Preferred Make : Exide/Amaron) including Rack , Connectors & Accessories. Display : LED indications : UPS ON# Battery Low/High# Out Put Voltage Low/High-R,Y,B# Over Load – R/Y/B# Fault# Charger ON# Input Voltage Low/High – R,Y,B. LCD indications: Input Voltage & Frequency – R, Y, B# Output Voltage & Frequency- R, Y, B# Battery Voltage# Load Level# Working Status# Fault Status. Warranty 2 year on-site warranty for UPS and 3 year replacement warranty for Battery , including buy back price of old 10.0KVA UPS with with 20 Nos. 12V/100 Ah Tubular Battery Please Enable Macros to View BoQ information

Other Detail

Information Source https://etenders.kerala.gov.in
Download FileName File Description File Size
Download makemodel.pdf Tender Documents 0 KB
Download prelagt.pdf Tender Documents 0 KB
Download Tendernotice_1.pdf Tender Documents 0 KB
Download 3941b468-1c9c-4b76-acc9-6ac80a6478d9.html Tender Documents 0 KB
Download BOQ_1444893.xls Tender Documents 0 KB
Download epayment.pdf Tender Documents 0 KB
Download Integrity.pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.