Indian Tenders

Tender Notice

TDR 55883670
Tendering Authority Uttar Pradesh Projects Corporation Limited
Tender No 31/PCL/GM/Zone-6/Noida/2026-27 Dated 08.06.2026
Tender ID 2026_UPPRC_1158264_1
Tender Brief Tender For Fire Fighting Works At Government Medical College Saharanpur In District Saharanpur
City Government Medical College Saharanpur in District
State Uttar Pradesh
Document Fees INR 17700 /-
EMD INR 1293000.0 /-
Tender Value INR 6.46 Crore /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Fire Fighting Works At Government Medical College Saharanpur In District Saharanpur

Key Dates

Publish Date 09-06-2026
Last Date of Bid Submission 22-06-2026
Tender Opening Date 22-06-2026

Contact Information

Company Name Uttar Pradesh Projects Corporation Limited
Contact Person General Manager, UPPCL, Zone-6 Noida
Address K-2, Sector-116, Noida Gautambudha Nagar

BOQ Items

Name of Work:- Fire Fighting works at Government Medical College Saharanpur in District Saharanpur
Sl. No. Item Description
1Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 150 mm Dia
2Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 100 mm Dia
3Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 80 mm Dia
4Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 65 mm Dia
5Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 50 mm Dia
6Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 32 mm Dia
7Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows , tees ,hanger ,flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. (FOR SPRINKLER) 25 mm Dia
8Providing, Fixing,Testing & commissioning of 15 mm Dia quartzoid bulb type Sprinklers of rating 68 degree centigrade with required accessories. Pendant sprinkler / sprinkler
9Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects. 150 mm dia
10Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects. 80 mm dia
11Providing, installation, testing and commission of non-return valve of following sizes PN-10 as per design standerd IS: 5312 or BS:1868 with companion flanges, bolts, nuts, washers etc. complete in all respects.150 mm dia
12Testing and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
13Supplying Installation testing & Commissioning of 25 mm Air Release valve gunmental having rubber ball and with 25 mm BSP threaded male inlet including necessary accessories and connections complete in all respect.
14Supplying Installation testing & Commissioning of 25 mm Ball valve PN-1 gunmental as per IS:778 including necessary accessories and connections.
15Repairing & Painting of Weather proof standard fire hose cabinet box made out of 18 gauge MS sheet including two coats of post office red paint over one coat of primer with 4 mm, thick glass door on front painted \\"FIRE\\" in red luminious paint, The size of the box should be 750 mm X 600 mm X 250 mm size capable of accommodation a pair of hose with coupling and nozzel. The box should be floor mounted type with railway coach lock arrangement and lever for opening the door after breaking the glass complete.
16Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63mm dia male and female couplings duly bound with Gl wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel
17Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required:Stainless Steel (Grade 304)
18Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) 450 Ipm at 35 m Head
19Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) 900 Ipm at 35 m Head
20Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required..
21Providing & fixing of pressure gauge in ranging from 0 to 14 kg per sqmm ISI marked from approved manufacturers complete in all respects.
22Providing/Fixing of Cubical type floor mounted Fire pump Control panel fabricated from 16 G M.S. sheet duly powder coated finish of aproved shade and comprising of:a) One 63 amp. TP+NL M.C.C.B. with rotary handle of beacking capacity 35 KA.b) One Volt meter (0-500V) with selector switch.c) One set including lamps
23Supplying & laying of 2x1.5 sgmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
24Supply and laying of alluminium conductor PVC insulated armoured served sheathed cables 1100 volts grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on side and on top on surface the cable run shall be fied on M.S. clamps etc. of suitable size or as directed by the Engineer-in-charge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.25 sqmm 3-1/2 core
25Supply, Installation, Testing & commissioning os single/double sised sinage with 20 mtr viewing distance with built in LED, high efficiency L80 LED with 50000 hour life. Usage Exit sinage cum emergency light with function use either as an emergency luminaire or exit sign, with standalone testing system housing of polycarbonate. Glow wire test: 850 C RAL9003, Type of mounting: Wall or ceiling, Operation Mode Non- Maintained or maintained mode selectable, Connection voltage 230v +/- 5% [220V - 240V] compliant with EN standards, with IEC CB test certificate LED built in battry: Ni-Cd Duration 3 hours viewing distance 2+A300m, dimensions in mm 270x119x49
26P&F of Fire man axe made of carbon steel handle insulated with rubber tested to 20,000 Volts. Manufactured as per Indian standard IS:926.
27Providing and fixing pressure switch in M.S. pipe line including connection as required.
28Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fitting and base support for tank. [Sintex, Electroplast, Star, Lotus or equivalent having valid ISI license.
29Supply and fixing of Single way landing / Hydrant / Yard Hydrant valve 63 mm dia. Gun metal instantanous with female coupling with chain etc. complete. Single Headed Gunmetal
30Testing, servicing and fixing of Single way landing / Hydrant / Yard Hydrant valve 63 mm dia. Gun metal instantanous with female coupling with chain etc. complete.Single Headed Gunmetal
31Supplying Installation testing & Commissining of 6 zone, voice alarm controller with USB MP3 player (including 6 zone button pagingstation ) with seamles intrigration with main fire alarm panel for voice evacuation comlete as required.
32Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 25 mm dia (9\\")
33Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 32 mm dia (9\\")
34Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 50 mm dia (9\\")
35Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 80 mm dia (9\\")
36Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 100 mm dia (9\\")
37Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 150 mm dia (9\\")
38Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 25 mm dia
39Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 32 mm dia
40Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 50 mm dia
41Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 80 mm dia
42Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 100 mm dia
43Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 150 mm dia
44Drilling & Grounting of holes with DE-Walt Pure 150- Pro Chemical as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 16 mm dia (9\\")
45Testing, repairing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM),power supply unit (230 + 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. Two Loop Panel
46Supplying, installation, testing & commissioning of intelligent analog addressable photothermal (smoke cum heat) detector complete with mounting base complete as required.
47Supplying, installation, testing & commissioning of intelligent addressable thermal (heat) detector with rate of rise cum fixed tempreature thermistor complete with base as required.
48Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
49Testing & Commissioning of Intelligent Addressable Manual Call points- double action Break Glass cum pull station suitable for wall/column mounting.
50Testing & Commissioning of Intelligent Addressable Hooter cum multi carriar strobe unit as per specifications and customization of intensity selection as 15, 30 , 75 or 110 cd of strobe unit is possible by panel. Sounder sum strobe will be driven by supervised 24 V DC input and will give 80 db output at 3 m strobe unite will be synchronized 1 Hz strobe flash rate for better evacuation in complete facility.
51Testing & Commissioning Intelligent Addressable single Addressable Control Relay Module- Form \\"C\\" contact type.
52Supplying Installation testing & Commissining of 6 zone, voice alarm controller with USB MP3 player (including 6 zone button pagingstation ) with seamles intrigration with main fire alarm panel for voice evacuation comlete as required.
53Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows, tees, hanger, flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. 200 mm Dia
54Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows, tees, hanger, flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects.150 mm Dia
55Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows, tees, hanger, flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. 100 mm Dia
56Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows, tees, hanger, flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. 80 mm Dia
57Providing, Laying, Testing & Commissioning of C- class heavy duty MS pipe on surface Confirming to IS 1239 (part-1) for pipes upto 150mm dia and IS: 3589-1991 for pipes above 150mm including cutting & welding with fitting like elbows, tees, hanger, flenges, taper , reducers, nuts, neoprene gasket & washer including cutting, welding etc. fixing the pipe on the Wall / Ceiling with suitable clamp and painted with red oxide and PO red enamel paint complete in all resspects. 25 mm Dia
58Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects.200 mm dia
59Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects.150 mm dia
60Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects. 100 mm dia
61Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects.80 mm dia
62Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects. 150 mm dia
63Supplying, fixing, testing & commission of butterfly valve of PN-16 slim seal standerd lever operated type as per design standerd IS:1395 or BS:5155 with required flanges, nut bolts etc. complete in all respects.100 mm dia
64Supplying Installation testing & Commissioning of 25 mm Air Release valve gunmental having rubber ball and with 25 mm BSP threaded male inlet including necessary accessories and connections complete in all respect.
65Supplying Installation testing & Commissioning of 25 mm Ball valve PN-1 gunmental as per IS:778 including necessary accessories and connections.
66Supplying Installation testing & Commissioning of Foot valve including necessary accessories and connections. 150 mm dia
67Supplying Installation testing & Commissioning of Foot valve including necessary accessories and connections. 100 mm dia
68Repairing & Painting of Weather proof standard fire hose cabinet box made out of 18 gauge MS sheet including two coats of post office red paint over one coat of primer with 4 mm, thick glass door on front painted \\"FIRE\\" in red luminious paint, The size of the box should be 750 mm X 600 mm X 250 mm size capable of accommodation a pair of hose with coupling and nozzel. The box should be floor mounted type with railway coach lock arrangement and lever for opening the door after breaking the glass complete.
69Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63mm dia male and female couplings duly bound with Gl wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel
70Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required Stainless Steel (Grade 304)
71Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required..
72Providing & fixing of pressure gauge in ranging from 0 to 14 kg per sqmm ISI marked from approved manufacturers complete in all respects.
73Supplying fixing of Cast iron body 63 mm dia male instantaneous intel coupling with housing cabinet (500X400X400 for 2 way and 600X400 for 4 way) cap and chain for fire brigade correction conforming to IS:904 and making connection with fire fighting pipe or underground water tank completing the work in all respect as per the directions of the Engineer-in-charge. Four Way connection
74Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM),power supply unit (230 + 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. Ten Loop Panel
75Supplying & laying of 2x1.5 sgmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
76Supply and laying of alluminium conductor PVC insulated armoured served sheathed cables 1100 volts grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on side and on top on surface the cable run shall be fied on M.S. clamps etc. of suitable size or as directed by the Engineer-in-charge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.150 sqmm 3-1/2 core
77Supply and laying of alluminium conductor PVC insulated armoured served sheathed cables 1100 volts grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on side and on top on surface the cable run shall be fied on M.S. clamps etc. of suitable size or as directed by the Engineer-in-charge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 50 sqmm 3-1/2 core
78Supply and laying of alluminium conductor PVC insulated armoured served sheathed cables 1100 volts grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on side and on top on surface the cable run shall be fied on M.S. clamps etc. of suitable size or as directed by the Engineer-in-charge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 25 sqmm 3-1/2 core
79P&F of Fire man axe made of carbon steel handle insulated with rubber tested to 20,000 Volts. Manufactured as per Indian standard IS:926.
80Providing and fixing pressure switch in M.S. pipe line including connection as required.
81Supply and fixing of Single way landing / Hydrant / Yard Hydrant valve 63 mm dia. Gun metal instantanous with female coupling with chain etc. complete. Single Headed Gunmetal
82Surface dressing of road with painting between using 2.25 kg. of bitumen per sq.mt with 1.65 cum of stone chipping ,13.2 mm nominal size/100 sq.mt of road surface including corolidation.
83Supply, Installation, Testing & Commissioning of Electric Driven Main Fire Pump Suitable for auto operation & consisting of following: complete in all respect as required. Horizontal split Casing type, centrifugal, pump of cast iron body & bronze impeller with stainless steel shaft Mechanical seal at specified flow of 2280 lpm at 70 Meter head confirming to IS 1520. Suitable HP squirrel cage induction motor,TEFC synchronous speed 1500 RPM 60 HP (with permissible slip) suitable for operation on 415 volts, 3 phase 50Hz.AC with IP 55 protectiion for enclosure, horizontal foot mounted type with class- \\"F\\" insulation, conferming to IS-325 Common base frame fabricated out of M.S channel of suitable size flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications.
84Supply, Installation, Testing & Commissioning of Diesel Engine Driven main fire pump suitable for auto operation & consisting of following: complete in all respect as required. Horizontal split Casing type,centrifugal, pump of cast iron body & bronze impeller with stainless steel shaft, Mechanical seal at specified flow of 2280 lpm at 70 meter head confirming to IS 1520. Suitable HP 1500 RPM, 4 stroke, cold starting type Diesel Engine with Heat Exchanger confirming to relevant BIS & IS Standards, complete with all required accessories/system, fuel oil filter ,lubricant oil pump with filter, 1 set Starting batteries of 180AH capicity each with suitable angle iron stand,engine starting panel havng all the controls meters, Deisel tank for 8 hrs continuous running for Diesel Engine having minimum capicity of 200 Ltrs. (Tank made out of 3mm thick M.S.Sheet with filling cap, drain cock, diesel indicator duly mounted on M.S.angle) exhaust pipe of minimum 10 mtr. length, duly insulated with 50 mm thick glass wool with 1.0 mm.thick alluminium sheet cladding, exuast reidential silencer,stop solenold for auto stop in the event of fault with audio indications, painting etc. as required. Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications.
85Supplying, fixing, testing & commission of Electric Driven Pressurisation Pump (Jockey Pump) suitable for auto operation consisting of following complete in all respect as required.Horizontal type, centrifugal & suction type, pump of cast iron body & bronze impeller with stainless steel shaft Mechanical seal, gland packing & flow of 180 lpm at 70 Mtr. Head confirming to IS:-1520 Common base frame fabricated out of M.S channel of suitable able size flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications.
86Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection classIP 42 as required : INCOMING400A, 50kA 4 Pole MCCB, Ics=100% lcu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500Amps OUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps), Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification
87Testing & Commissioning of Electric Driven Main Fire Pump Suitable for auto operation & consisting of following: complete in all respect as required. Horizontal split Casing type, centrifugal, pump of cast iron body & bronze impeller with stainless steel shaft Mechanical seal at specified flow of 2280 lpm at 70 Meter head confirming to IS 1520. Suitable HP squirrel cage induction motor,TEFC synchronous speed 1500 RPM 60 HP (with permissible slip) suitable for operation on 415 volts, 3 phase 50Hz.AC with IP 55 protectiion for enclosure, horizontal foot mounted type with class- \\"F\\" insulation, conferming to IS-325 Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications.
88Testing & Commissioning of Diesel Engine Driven main fire pump suitable for auto operation & consisting of following: complete in all respect as required. Horizontal split Casing type,centrifugal, pump of cast iron body & bronze impeller with stainless steel shaft, Mechanical seal at specified flow of 2280 lpm at 70 meter head confirming to IS 1520. M.S fabricated Common base frame, flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications.
89Testing & commission of Electric Driven Pressurisation Pump (Jockey Pump) suitable for auto operation consisting of following complete in all respect as required. Horizontal type, centrifugal & suction type, pump of cast iron body & bronze impeller with stainless steel shaft Mechanical seal, gland packing & flow of 180 lpm at 70 Mtr. Head confirming to IS:-1520. Common base frame fabricated out of M.S channel of suitable able size flexible coupling, coupling guard, foundation bolt & pressure gauge with valve etc. Suitable cement concrete foundation duly plastered, with anti vibration pads etc. complete as per detailed specifications.
90SYSTEM CONTROLLERTesting & Commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection classIP 42 as required :INCOMING400A, 50kA 4 Pole MCCB, Ics=100% lcu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500AmpsOUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)
91SITC Automatic priming arrangement for all fire pumps including necessary pipe, fitting, water level controller, 1 HP pump, auto starter gate valve NRV's etc complete.
92Supply & fixing of CO2 type fire extinguisher, 4.5 kg. capacity (ISI Marked IS:2878 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
93Providing & erecting direction & place identification & other fire related informations for emergency retro- reflectorised sign as per IRC-67 made of high intensity grade sheeting. The retro reflective sheeting type-IV shall be tested for 3 year outdoor weathering test in Indian conditions as per IRC 67:2012 & proof of the same in form of government report shall be uploaded while quoting tender vide clause 801.3 fixed over aluminium sheeting, 2mm thick with area exceeding 0.9 sqm. Supproted on a mild steel single angle iron post 75x75x6 mm, 2 nos firmly fixed to the ground by means of property designed foundation with M-15 grade cement concrete 45x45x60 cm below ground level as per approved drawing complete. Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download BOQ_2170788.xls Tender Documents 0 KB
Download DWG31.pdf Tender Documents 0 KB
Download e19ae52e-aa44-41ad-97bb-05a8d0f862a2.html Tender Documents 0 KB
Download Tender31.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.