Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No 18/EWC(B)/2026-27
Tender ID 2026_MVVNL_1155337_2
Tender Brief Corrigendum : Tender For Increasing Capacity Of 33/11 Kv Sub-Stations Richha From 2×10 To 2×10+5 Mva,Rithora From 2×10 To 2×10+5 Mva & Other Associates Works Under Edc Bareilly In Business Plan 2026-27
City Bareilly
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 27800.0 /-
Tender Value INR 27.80 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Increasing Capacity Of 33/11 Kv Sub-Stations Richha From 2×10 To 2×10+5 Mva,Rithora From 2×10 To 2×10+5 Mva & Other Associates Works Under Edc Bareilly In Business Plan 2026-27

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 15-06-2026 18/EWC(B)/2026-27 Date 18-06-2026

Key Dates

Publish Date 15-06-2026
Last Date of Bid Submission 18-06-2026
Tender Opening Date 18-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person SE EWC
Address Bareilly

BOQ Items

Name of Work:- increasing capacity of 33/11 KV Sub-Stations Richha from 2×10 to 2×10+5 MVA,Rithora from 2×10 to 2×10+5 MVA & other associates works under EDC Bareilly in Business Plan 2026-27
Sl. No. Item Description
1Part (A) -WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S RICHHA (BAREILLY)
2Supply of following materials
3GI STRIP Flat 50x6mm
4Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
5MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
633 KV Lightening Arrestor
733 KV 400 A Bus Isolator
833 KV VCB 800A 750 MVA
9Control pannel I/C for 33 KV Single T/F
1033 kv O/D CT CTR 200/100/1-1-1 A
1111 KV VCB I/C CTR 600/300/5A
1211 KV VCB O/G CTR 200/100/5A
13M.S. Channel 125x65mm
14M.S.Angle 75x75x8mm
15MS Angles 50x50x6mm
16MS Channel 100x50x2028mm (For top channel & fuse set)
17M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
1811 KV 3x300 mm2 XLPE Cable
1911 KV 3x185 mm2 XLPE Cable
2011 KV Cable jointing Kit 3x185 mm2 I/D
2111 KV Cable jointing Kit 3x185 mm2 O/D
2211 KV Cable jointing Kit 3x300 mm2 I/D
2311 KV Cable jointing Kit 3x300 mm2 O/D
24PCC Pole 8.5m long.
2511 KV Pin Insulator with Pin
26Earthing Complete
27Stay set complete 16x1800mm
2811 KV disc insulator
2911 KV disc fitting
3010 SWG GI Wire
31Cost of ACSR Dog conductor
3233KV XLPE CALE 3*300SQMM
3333KV XLPE CALE BOX 3*300SQMM
34Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
35Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
36Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
37Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
38welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
39Supply of following materials for construction of power tf plinth
40Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
41Supply of bricks as per standard
42Supply of cement as per standard
43Supply of sand as per standard
44Supply of stone ballast 20mm as per standard
45Supply of steel rebar 12mm as per standard
46Supply of brick bat as per standard
47Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
48Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
49Bus Isolator Structure
50Fabrication of Structure
51C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
52Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
53Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
54Post insulator Structure
55Fabrication of Structure
56C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
57Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
58Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
5933 KV CT Structure
60Fabrication of Structure
61C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
62Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
63Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
64Lightening Arrestor Structure
65Fabrication of Structure
66C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
67Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
68Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
69Fuse Set Structure
70Fabrication of Structure
71C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
72Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
73Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
7433 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
75Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
7633 KV Bus Isolator
7733 KV Fuse Set (Provided by firm)
78Lightening Arrestor
7933 KV VCB
8033 KV CT
8133 KV Post insulator
82Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
83Control Cable 4x2.5 mm2
84Control Cable 2x2.5 mm2
85Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
86Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
87Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
88Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
8911 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
90Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
91Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
92Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
93Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
94Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
95Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
96Work related maintinance of old and used 5 MVA Transformer.
97Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
98Centrifusing of transformer oil.
99Replacement of damage brether and silica jel.(all required material will be provided by firm.)
100Replacement of damage WTI and OTI.(all required material will be provided by firm.)
101Painting of old transformer.(all required material will be provided by firm.)
102Replacement of damage buchholz relay(all required material will be provided by firm.)
103Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
104Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
105Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
106Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
107Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
108Providing of rubber matting sheet 8/10mm
109Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
110Carriage of old scrap material from site to store center.
111Making of 11kv Bus Bar on Power Transformer LT side
112Soil filling with supply of material
113Part (B) -WORK SPECIFICATION FOR IINCREASING CAPACITY OF 33/11KV S/S RITHORA (BAREILLY)
114Supply of following materials
115GI STRIP Flat 50x6mm
116Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
117MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
11833 KV Lightening Arrestor
11933 KV 400 A Bus Isolator
12033 KV VCB 800A 750 MVA
121Control pannel I/C for 33 KV Single T/F
12233 kv O/D CT CTR 200/100/1-1-1 A
12311 KV VCB I/C CTR 600/300/5A
12411 KV VCB O/G CTR 200/100/5A
125M.S. Channel 125x65mm
126M.S.Angle 75x75x8mm
127MS Angles 50x50x6mm
128MS Channel 100x50x2028mm (For top channel & fuse set)
129M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
13011 KV 3x300 mm2 XLPE Cable
13111 KV 3x185 mm2 XLPE Cable
13211 KV Cable jointing Kit 3x185 mm2 I/D
13311 KV Cable jointing Kit 3x185 mm2 O/D
13411 KV Cable jointing Kit 3x300 mm2 I/D
13511 KV Cable jointing Kit 3x300 mm2 O/D
136PCC Pole 8.5m long.
13711 KV Pin Insulator with Pin
138Earthing Complete
139Stay set complete 16x1800mm
14011 KV disc insulator
14111 KV disc fitting
14210 SWG GI Wire
143Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
144Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
145Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
146Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
147welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
148Supply of following materials for construction of power tf plinth
149Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
150Supply of bricks as per standard
151Supply of cement as per standard
152Supply of sand as per standard
153Supply of stone ballast 20mm as per standard
154Supply of steel rebar 12mm as per standard
155Supply of brick bat as per standard
156Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
157Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
158Bus Isolator Structure
159Fabrication of Structure
160C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
161Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
162Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
163Post insulator Structure
164Fabrication of Structure
165C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
166Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
167Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
16833 KV CT Structure
169Fabrication of Structure
170C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
171Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
172Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
173Lightening Arrestor Structure
174Fabrication of Structure
175C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
176Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
177Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
178Fuse Set Structure
179Fabrication of Structure
180C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
181Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
182Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
18333 KV VCB structure size (1.5x1.5x1.5) including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
184Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
18533 KV Bus Isolator
18633 KV Fuse Set (Provided by firm)
187Lightening Arrestor
18833 KV VCB
18933 KV CT
19033 KV Post insulator
191Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
192Control Cable 4x2.5 mm2
193Control Cable 2x2.5 mm2
194Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
195Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
196Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
197Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
19811 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
199Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
200Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
201Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
202Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
203Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
204Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
205Work related maintinance of old and used 5 MVA Transformer.
206Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
207Centrifusing of transformer oil.
208Replacement of damage brether and silica jel.(all required material will be provided by firm.)
209Replacement of damage WTI and OTI.(all required material will be provided by firm.)
210Painting of old transformer.(all required material will be provided by firm.)
211Replacement of damage buchholz relay(all required material will be provided by firm.)
212Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
213Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
214Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
215Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
216Providing of rubber matting sheet 8/10mm
217Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
218Carriage of old scrap material from site to store center.
219Making of 11kv Bus Bar on Power Transformer LT side
220Soil filling with supply of material Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 9fb27d5e-fde0-4f34-9e2c-3a4313f480e1.html Tender Documents 0 KB
Download BOQ_2170778.xls Tender Documents 0 KB
Download tenderfrom18.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.