Indian Tenders

Tender Notice

TDR 55883498
Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No 09/EWC(B)/2026-27
Tender ID 2026_MVVNL_1155120_2
Tender Brief Corrigendum : Tender For Increasing Capacity Of 33/11 Kv Sub-Stations- Ujhani Town From 10+5 To 10+2×5 Mva, Kunwargaon From 3×5 To 2×5+10 Mva, Bhooda Bhadrol From 2×5 To 3×5 Mva, Alapur From 3×5 To 2×5+10 Mva & Other Associates Works Under Edc Badaun In Business P
City Badaun
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 30100.0 /-
Tender Value INR 30.10 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Increasing Capacity Of 33/11 Kv Sub-Stations- Ujhani Town From 10+5 To 10+2×5 Mva, Kunwargaon From 3×5 To 2×5+10 Mva, Bhooda Bhadrol From 2×5 To 3×5 Mva, Alapur From 3×5 To 2×5+10 Mva & Other Associates Works Under Edc Badaun In Business Plan 2026-27.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 15-06-2026 09/EWC(B)/2026-27 Date 18-06-2026

Key Dates

Publish Date 15-06-2026
Last Date of Bid Submission 18-06-2026
Tender Opening Date 18-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person SE EWC
Address Bareilly

BOQ Items

Name of Work:- Increasing capacity of 33/11 KV Sub-Stations- Ujhani Town from 10+5 to 10+2×5 MVA, Kunwargaon from 3×5 to 2×5+10 MVA, Bhooda Bhadrol from 2×5 to 3×5 MVA, Alapur from 3×5 to 2×5+10 MVA & other associates works under EDC Badaun in Business Plan 2026-27.
Sl. No. Item Description
1Part (A) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S UJANI TOWN FROM (5+10) MVA TO (2X5+10)MVA BADAUN.
2Supply of following materials
3GI STRIP Flat 50x6mm
4Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
5MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
633 KV Lightening Arrestor
733 KV 400 A Bus Isolator
833 KV VCB 800A 750 MVA
9Control pannel I/C for 33 KV Single T/F
1033 kv O/D CT CTR 200/100/1-1-1 A
1133 KV Post insulator
1211 KV VCB I/C CTR 600/300/5A
1311 KV VCB O/G CTR 200/100/5A
14M.S. Channel 125x65mm
15M.S.Angle 75x75x8mm
16MS Angles 50x50x6mm
17MS Channel 100x50x2028mm (For top channel & fuse set)
18M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
1911 KV 3x300 mm2 XLPE Cable
2011 KV 3x185 mm2 XLPE Cable
2111 KV Cable jointing Kit 3x185 mm2 I/D
2211 KV Cable jointing Kit 3x185 mm2 O/D
2311 KV Cable jointing Kit 3x300 mm2 I/D
2411 KV Cable jointing Kit 3x300 mm2 O/D
25PCC Pole 8.5m long.
2611 KV Pin Insulator with Pin
27Earthing Complete
28Stay set complete 16x1800mm
2911 KV disc insulator
3011 KV disc fitting
3110 SWG GI Wire
32Cost of ACSR Dog conductor
3333KV XLPE CALE 3*300SQMM
3433KV XLPE CALE BOX 3*300SQMM
35Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
36Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
37Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
38Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
39welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
40Supply of following materials for construction of power tf plinth
41Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
42Supply of bricks as per standard
43Supply of cement as per standard
44Supply of sand as per standard
45Supply of stone ballast 20mm as per standard
46Supply of steel rebar 12mm as per standard
47Supply of brick bat as per standard
48Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
49Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
50Bus Isolator Structure
51Fabrication of Structure
52C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
53Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
54Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
55Post insulator Structure
56Fabrication of Structure
57C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
58Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
59Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
6033 KV CT Structure
61Fabrication of Structure
62C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
63Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
64Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
65Lightening Arrestor Structure
66Fabrication of Structure
67C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
68Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
69Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
70Fuse Set Structure
71Fabrication of Structure
72C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
73Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
74Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
7533 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
76Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
7733 KV Bus Isolator
7833 KV Fuse Set (Provided by firm)
79Lightening Arrestor
8033 KV VCB
8133 KV CT
8233 KV Post insulator
83Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
84Control Cable 4x2.5 mm2
85Control Cable 2x2.5 mm2
86Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
87Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
88Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
89Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
9011 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
91Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
92Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
93Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
94Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
95Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
96Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
97Work related maintinance of old and used 5 MVA Transformer.
98Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
99Centrifusing of transformer oil.
100Replacement of damage brether and silica jel.(all required material will be provided by firm.)
101Replacement of damage WTI and OTI.(all required material will be provided by firm.)
102Painting of old transformer.(all required material will be provided by firm.)
103Replacement of damage buchholz relay(all required material will be provided by firm.)
104Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
105Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
106Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
107Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
108Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
109Providing of rubber matting sheet 8/10mm
110Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
111Carriage of old scrap material from site to store center.
112Making of 11kv Bus Bar on Power Transformer LT side
113Soil filling with supply of material
114Part (B) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S KUNWARGAON FROM (3X5)MVA TO (2X5+10)MVA (BADAUN)
115Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
116welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
117Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
118Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
119Repairing of complete switchyard fencing and its painting.
120Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
121Part (C)- WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S BHOODA BHADROL FROM (2X5) MVA TO (3X5)MVA BADAUN.
122Supply of following materials
123GI STRIP Flat 50x6mm
124Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
125MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
12633 KV Lightening Arrestor
12733 KV 400 A Bus Isolator
12833 KV VCB 800A 750 MVA
129Control pannel I/C for 33 KV Single T/F
13033 kv O/D CT CTR 200/100/1-1-1 A
13133 KV Post insulator
13211 KV VCB I/C CTR 600/300/5A
13311 KV VCB O/G CTR 200/100/5A
134M.S. Channel 125x65mm
135M.S.Angle 75x75x8mm
136MS Angles 50x50x6mm
137MS Channel 100x50x2028mm (For top channel & fuse set)
138M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
13911 KV 3x300 mm2 XLPE Cable
14011 KV 3x185 mm2 XLPE Cable
14111 KV Cable jointing Kit 3x185 mm2 I/D
14211 KV Cable jointing Kit 3x185 mm2 O/D
14311 KV Cable jointing Kit 3x300 mm2 I/D
14411 KV Cable jointing Kit 3x300 mm2 O/D
145PCC Pole 8.5m long.
14611 KV Pin Insulator with Pin
147Earthing Complete
148Stay set complete 16x1800mm
14911 KV disc insulator
15011 KV disc fitting
15110 SWG GI Wire
152Cost of ACSR Dog conductor
15333KV XLPE CALE 3*300SQMM
15433KV XLPE CALE BOX 3*300SQMM
155Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
156Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
157Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
158Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
159welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
160Supply of following materials for construction of power tf plinth
161Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
162Supply of bricks as per standard
163Supply of cement as per standard
164Supply of sand as per standard
165Supply of stone ballast 20mm as per standard
166Supply of steel rebar 12mm as per standard
167Supply of brick bat as per standard
168Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
169Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
170Bus Isolator Structure
171Fabrication of Structure
172C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
173Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
174Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
175Post insulator Structure
176Fabrication of Structure
177C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
178Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
179Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
18033 KV CT Structure
181Fabrication of Structure
182C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
183Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
184Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
185Lightening Arrestor Structure
186Fabrication of Structure
187C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
188Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
189Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
190Fuse Set Structure
191Fabrication of Structure
192C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
193Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
194Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
19533 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
196Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
19733 KV Bus Isolator
19833 KV Fuse Set (Provided by firm)
199Lightening Arrestor
20033 KV VCB
20133 KV CT
20233 KV Post insulator
203Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
204Control Cable 4x2.5 mm2
205Control Cable 2x2.5 mm2
206Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
207Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
208Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
209Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
21011 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
211Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
212Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
213Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
214Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
215Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
216Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
217Work related maintinance of old and used 5 MVA Transformer.
218Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
219Centrifusing of transformer oil.
220Replacement of damage brether and silica jel.(all required material will be provided by firm.)
221Replacement of damage WTI and OTI.(all required material will be provided by firm.)
222Painting of old transformer.(all required material will be provided by firm.)
223Replacement of damage buchholz relay(all required material will be provided by firm.)
224Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
225Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
226Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
227Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
228Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
229Providing of rubber matting sheet 8/10mm
230Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
231Carriage of old scrap material from site to store center.
232Making of 11kv Bus Bar on Power Transformer LT side
233Soil filling with supply of material
234Part - (D) -WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S ALAPUR FROM (3X5)MVA TO (2X5+10)MVA (BADAUN)
235Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
236welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
237Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
238Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
239Repairing of complete switchyard fencing and its painting.
240Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement) Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 536c7a73-b92f-4c37-a79f-e436c8f23010.html Tender Documents 0 KB
Download BOQ_2170613.xls Tender Documents 0 KB
Download tenderform9.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.