Tender Brief Tender For Increasing Capacity Of 33/11 Kv Sub-Stations-Dataganj Rural From 10+5 To 2×10 Mva, Sahaswan Town From 10+5 To 2×10 Mva, Qadarchok From 5+10 To 2×5+10 Mva,Ujhani Rural From 2×10 To 2×10+5 Mva & Other Associates Works Under Edc Badaun In Bus
City Badaun
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 30500.0 /-
Tender Value INR 30.50 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Increasing Capacity Of 33/11 Kv Sub-Stations-Dataganj Rural From 10+5 To 2×10 Mva, Sahaswan Town From 10+5 To 2×10 Mva, Qadarchok From 5+10 To 2×5+10 Mva,Ujhani Rural From 2×10 To 2×10+5 Mva & Other Associates Works Under Edc Badaun In Business Plan 2026-27.

Key Dates

Publish Date 08-06-2026
Last Date of Bid Submission 15-06-2026
Tender Opening Date 15-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person Bareilly
Address Bareilly

BOQ Items

Name of Work:- Increasing capacity of 33/11 KV Sub-Stations-Dataganj rural from 10+5 to 2×10 MVA, Sahaswan Town from 10+5 to 2×10 MVA, Qadarchok from 5+10 to 2×5+10 MVA,Ujhani Rural from 2×10 to 2×10+5 MVA & other associates works under EDC Badaun in Business Plan 2026-27.
Sl. No. Item Description
1Part (A) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S DATAGANJ RURAL FROM (5+10)MVA TO (2X10)MVA (BADAUN)
2Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
3welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
4Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
5Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
6Repairing of complete switchyard fencing and its painting.
7Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
8Shifting and dragging of existing 33/11 KV 10 MVA transformer from plinth to road side to its plinth along with its erection including fixing of all assessories and carriage & top up of T/F oil.
9Part (B) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S SAHASWAN TOWN FROM (5+10)MVA TO (2X10)MVA (BADAUN)
10Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
11welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
12Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
13Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
14Repairing of complete switchyard fencing and its painting.
15Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
16Part (C)-WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S QADARCHOK FROM (5+10) MVA TO (2X5+10)MVA BADAUN.
17Supply of following materials
18GI STRIP Flat 50x6mm
19Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
20MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
2133 KV Lightening Arrestor
2233 KV 400 A Bus Isolator
2333 KV VCB 800A 750 MVA
24Control pannel I/C for 33 KV Single T/F
2533 kv O/D CT CTR 200/100/1-1-1 A
2633 KV Post insulator
2711 KV VCB I/C CTR 600/300/5A
2811 KV VCB O/G CTR 200/100/5A
29M.S. Channel 125x65mm
30M.S.Angle 75x75x8mm
31MS Angles 50x50x6mm
32MS Channel 100x50x2028mm (For top channel & fuse set)
33M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
3411 KV 3x300 mm2 XLPE Cable
3511 KV 3x185 mm2 XLPE Cable
3611 KV Cable jointing Kit 3x185 mm2 I/D
3711 KV Cable jointing Kit 3x185 mm2 O/D
3811 KV Cable jointing Kit 3x300 mm2 I/D
3911 KV Cable jointing Kit 3x300 mm2 O/D
40PCC Pole 8.5m long.
4111 KV Pin Insulator with Pin
42Earthing Complete
43Stay set complete 16x1800mm
4411 KV disc insulator
4511 KV disc fitting
4610 SWG GI Wire
47Cost of ACSR Dog conductor
4833KV XLPE CALE 3*300SQMM
4933KV XLPE CALE BOX 3*300SQMM
50Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
51Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
52Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
53Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
54welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
55Supply of following materials for construction of power tf plinth
56Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
57Supply of bricks as per standard
58Supply of cement as per standard
59Supply of sand as per standard
60Supply of stone ballast 20mm as per standard
61Supply of steel rebar 12mm as per standard
62Supply of brick bat as per standard
63Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
64Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
65Bus Isolator Structure
66Fabrication of Structure
67C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
68Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
69Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
70Post insulator Structure
71Fabrication of Structure
72C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
73Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
74Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
7533 KV CT Structure
76Fabrication of Structure
77C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
78Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
79Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
80Lightening Arrestor Structure
81Fabrication of Structure
82C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
83Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
84Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
85Fuse Set Structure
86Fabrication of Structure
87C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
88Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
89Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
9033 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
91Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
9233 KV Bus Isolator
9333 KV Fuse Set (Provided by firm)
94Lightening Arrestor
9533 KV VCB
9633 KV CT
9733 KV Post insulator
98Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
99Control Cable 4x2.5 mm2
100Control Cable 2x2.5 mm2
101Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
102Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
103Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
104Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
10511 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
106Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
107Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
108Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
109Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
110Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
111Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
112Work related maintinance of old and used 5 MVA Transformer.
113Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
114Centrifusing of transformer oil.
115Replacement of damage brether and silica jel.(all required material will be provided by firm.)
116Replacement of damage WTI and OTI.(all required material will be provided by firm.)
117Painting of old transformer.(all required material will be provided by firm.)
118Replacement of damage buchholz relay(all required material will be provided by firm.)
119Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
120Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
121Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
122Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
123Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
124Providing of rubber matting sheet 8/10mm
125Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
126Carriage of old scrap material from site to store center.
127Making of 11kv Bus Bar on Power Transformer LT side
128Soil filling with supply of material
129Part (D) -WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S UJHANI RURAL FROM (2X10) MVA TO (5+2X10)MVA BADAUN.
130Supply of following materials
131GI STRIP Flat 50x6mm
132Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
133MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
13433 KV Lightening Arrestor
13533 KV 400 A Bus Isolator
13633 KV VCB 800A 750 MVA
137Control pannel I/C for 33 KV Single T/F
13833 kv O/D CT CTR 200/100/1-1-1 A
13933 KV Post insulator
14011 KV VCB I/C CTR 600/300/5A
14111 KV VCB O/G CTR 200/100/5A
142M.S. Channel 125x65mm
143M.S.Angle 75x75x8mm
144MS Angles 50x50x6mm
145MS Channel 100x50x2028mm (For top channel & fuse set)
146M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
14711 KV 3x300 mm2 XLPE Cable
14811 KV 3x185 mm2 XLPE Cable
14911 KV Cable jointing Kit 3x185 mm2 I/D
15011 KV Cable jointing Kit 3x185 mm2 O/D
15111 KV Cable jointing Kit 3x300 mm2 I/D
15211 KV Cable jointing Kit 3x300 mm2 O/D
153PCC Pole 8.5m long.
15411 KV Pin Insulator with Pin
155Earthing Complete
156Stay set complete 16x1800mm
15711 KV disc insulator
15811 KV disc fitting
15910 SWG GI Wire
160Cost of ACSR Dog conductor
16133KV XLPE CALE 3*300SQMM
16233KV XLPE CALE BOX 3*300SQMM
163Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
164Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
165Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
166Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
167welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
168Supply of following materials for construction of power tf plinth
169Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
170Supply of bricks as per standard
171Supply of cement as per standard
172Supply of sand as per standard
173Supply of stone ballast 20mm as per standard
174Supply of steel rebar 12mm as per standard
175Supply of brick bat as per standard
176Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
177Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
178Bus Isolator Structure
179Fabrication of Structure
180C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
181Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
182Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
183Post insulator Structure
184Fabrication of Structure
185C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
186Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
187Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
18833 KV CT Structure
189Fabrication of Structure
190C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
191Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
192Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
193Lightening Arrestor Structure
194Fabrication of Structure
195C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
196Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
197Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
198Fuse Set Structure
199Fabrication of Structure
200C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
201Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
202Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
20333 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
204Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
20533 KV Bus Isolator
20633 KV Fuse Set (Provided by firm)
207Lightening Arrestor
20833 KV VCB
20933 KV CT
21033 KV Post insulator
211Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
212Control Cable 4x2.5 mm2
213Control Cable 2x2.5 mm2
214Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
215Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
216Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
217Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
21811 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
219Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
220Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
221Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
222Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
223Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
224Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
225Work related maintinance of old and used 5 MVA Transformer.
226Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
227Centrifusing of transformer oil.
228Replacement of damage brether and silica jel.(all required material will be provided by firm.)
229Replacement of damage WTI and OTI.(all required material will be provided by firm.)
230Painting of old transformer.(all required material will be provided by firm.)
231Replacement of damage buchholz relay(all required material will be provided by firm.)
232Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
233Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
234Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
235Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
236Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
237Providing of rubber matting sheet 8/10mm
238Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
239Carriage of old scrap material from site to store center.
240Making of 11kv Bus Bar on Power Transformer LT side
241Soil filling with supply of material Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download BOQ_2170630.xls Tender Documents 0 KB
Download cfc060c8-a338-427b-8881-ce89a8e78495.html Tender Documents 0 KB
Download tenderform10.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.