Indian Tenders

Tender Notice

TDR 55883456
Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No 14/EWC(B)/2026-27
Tender ID 2026_MVVNL_1155142_2
Tender Brief Tender For Increasing Capacity Of 33/11 Kv Sub-Stations-Govindganj From 10+5 To 10+10 Mva, Jamour From 2×10+8 To 2×10+8+5 Mva, Banda From 3×5+3×10 To 4×5+3×10 Mva & Other Associates Works Under Edc Shahjahanpur In Business Plan 2026-27.
City Shahjahanpur
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 31400.0 /-
Tender Value INR 31.40 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Increasing Capacity Of 33/11 Kv Sub-Stations-Govindganj From 10+5 To 10+10 Mva, Jamour From 2×10+8 To 2×10+8+5 Mva, Banda From 3×5+3×10 To 4×5+3×10 Mva & Other Associates Works Under Edc Shahjahanpur In Business Plan 2026-27.

Key Dates

Publish Date 08-06-2026
Last Date of Bid Submission 15-06-2026
Tender Opening Date 15-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person SE EWC
Address Bareilly

BOQ Items

Name of Work:- Increasing capacity of 33/11 KV Sub-Stations-Govindganj from 10+5 to 10+10 MVA, Jamour from 2×10+8 to 2×10+8+5 MVA, Banda from 3×5+3×10 to 4×5+3×10 MVA & other associates works under EDC Shahjahanpur in Business Plan 2026-27.
Sl. No. Item Description
1Part (A) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S GOVINDGANJ FROM (5+10)MVA TO(2X10)MVA UNDER EDD-SHAHJAHANPUR, SHAHJAHANPUR
2Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
3welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
4Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
524 V Battery set with charger (To be provided by firm I.S.I. mark only of DC System with one float cum boost charger & battery set for 24V. System with 150A.H. Capacity with cabinet).
6Part (B) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S JAMOUR FROM 2X10+8 MVA TO 2X10+8+5 MVA (EDD-CHINOR) SHAHJAHANPUR
7Supply of following materials
8GI STRIP Flat 50x6mm
9Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
10MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
1133 KV Lightening Arrestor
1233 KV 400 A Bus Isolator
1333 KV VCB 800A 750 MVA
14Control pannel I/C for 33 KV Single T/F
1533 kv O/D CT CTR 200/100/1-1-1 A
1633 KV Post insulator
1711 KV VCB I/C CTR 600/300/5A
1811 KV VCB O/G CTR 200/100/5A
19M.S. Channel 125x65mm
20M.S.Angle 75x75x8mm
21MS Angles 50x50x6mm
22MS Channel 100x50x2028mm (For top channel & fuse set)
23M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
2411 KV 3x300 mm2 XLPE Cable
2511 KV 3x185 mm2 XLPE Cable
2611 KV Cable jointing Kit 3x185 mm2 I/D
2711 KV Cable jointing Kit 3x185 mm2 O/D
2811 KV Cable jointing Kit 3x300 mm2 I/D
2911 KV Cable jointing Kit 3x300 mm2 O/D
30PCC Pole 8.5m long.
3111 KV Pin Insulator with Pin
32Earthing Complete
33Stay set complete 16x1800mm
3411 KV disc insulator
3511 KV disc fitting
3610 SWG GI Wire
37Cost of ACSR Dog conductor
3833KV XLPE CALE 3*300SQMM
3933KV XLPE CALE BOX 3*300SQMM
40Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
41Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
42Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
43Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
44welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
45Supply of following materials for construction of power tf plinth
46Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
47Supply of bricks as per standard
48Supply of cement as per standard
49Supply of sand as per standard
50Supply of stone ballast 20mm as per standard
51Supply of steel rebar 12mm as per standard
52Supply of brick bat as per standard
53Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
54Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
55Bus Isolator Structure
56Fabrication of Structure
57C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
58Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
59Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
60Post insulator Structure
61Fabrication of Structure
62C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
63Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
64Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
6533 KV CT Structure
66Fabrication of Structure
67C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
68Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
69Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
70Lightening Arrestor Structure
71Fabrication of Structure
72C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
73Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
74Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
75Fuse Set Structure
76Fabrication of Structure
77C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
78Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
79Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
8033 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
81Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
8233 KV Bus Isolator
8333 KV Fuse Set (Provided by firm)
84Lightening Arrestor
8533 KV VCB
8633 KV CT
8733 KV Post insulator
88Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
89Control Cable 4x2.5 mm2
90Control Cable 2x2.5 mm2
91Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
92Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
93Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
94Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
9511 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
96Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
97Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
98Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
99Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
100Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
101Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
102Work related maintinance of old and used 5 MVA Transformer.
103Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
104Centrifusing of transformer oil.
105Replacement of damage brether and silica jel.(all required material will be provided by firm.)
106Replacement of damage WTI and OTI.(all required material will be provided by firm.)
107Painting of old transformer.(all required material will be provided by firm.)
108Replacement of damage buchholz relay(all required material will be provided by firm.)
109Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
110Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
111Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
112Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
113Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
114Providing of rubber matting sheet 8/10mm
115Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
116Carriage of old scrap material from site to store center.
117Making of 11kv Bus Bar on Power Transformer LT side
118Soil filling with supply of material
119Part (C) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S BANDA FROM 3X5+3X10 MVA TO 4X5+3X10 MVA (EDD-POWAYA ) SHAHJAHANPUR
120Supply of following materials
121GI STRIP Flat 50x6mm
122Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
123MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
12433 KV Lightening Arrestor
12533 KV 400 A Bus Isolator
12633 KV VCB 800A 750 MVA
127Control pannel I/C for 33 KV Single T/F
12833 kv O/D CT CTR 200/100/1-1-1 A
12933 KV Post insulator
13011 KV VCB I/C CTR 600/300/5A
13111 KV VCB O/G CTR 200/100/5A
132M.S. Channel 125x65mm
133M.S.Angle 75x75x8mm
134MS Angles 50x50x6mm
135MS Channel 100x50x2028mm (For top channel & fuse set)
136M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
13711 KV 3x300 mm2 XLPE Cable
13811 KV 3x185 mm2 XLPE Cable
13911 KV Cable jointing Kit 3x185 mm2 I/D
14011 KV Cable jointing Kit 3x185 mm2 O/D
14111 KV Cable jointing Kit 3x300 mm2 I/D
14211 KV Cable jointing Kit 3x300 mm2 O/D
143PCC Pole 8.5m long.
14411 KV Pin Insulator with Pin
145Earthing Complete
146Stay set complete 16x1800mm
14711 KV disc insulator
14811 KV disc fitting
14910 SWG GI Wire
150Cost of ACSR Dog conductor
15133KV XLPE CALE 3*300SQMM
15233KV XLPE CALE BOX 3*300SQMM
153Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
154Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
155Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
156Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
157welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
158Supply of following materials for construction of power tf plinth
159Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
160Supply of bricks as per standard
161Supply of cement as per standard
162Supply of sand as per standard
163Supply of stone ballast 20mm as per standard
164Supply of steel rebar 12mm as per standard
165Supply of brick bat as per standard
166Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
167Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
168Bus Isolator Structure
169Fabrication of Structure
170C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
171Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
172Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
173Post insulator Structure
174Fabrication of Structure
175C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
176Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
177Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
17833 KV CT Structure
179Fabrication of Structure
180C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
181Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
182Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
183Lightening Arrestor Structure
184Fabrication of Structure
185C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
186Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
187Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
188Fuse Set Structure
189Fabrication of Structure
190C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
191Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
192Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
19333 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
194Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
19533 KV Bus Isolator
19633 KV Fuse Set (Provided by firm)
197Lightening Arrestor
19833 KV VCB
19933 KV CT
20033 KV Post insulator
201Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
202Control Cable 4x2.5 mm2
203Control Cable 2x2.5 mm2
204Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
205Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
206Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
207Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
20811 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
209Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
210Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
211Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
212Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
213Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
214Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
215Work related maintinance of old and used 5 MVA Transformer.
216Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
217Centrifusing of transformer oil.
218Replacement of damage brether and silica jel.(all required material will be provided by firm.)
219Replacement of damage WTI and OTI.(all required material will be provided by firm.)
220Painting of old transformer.(all required material will be provided by firm.)
221Replacement of damage buchholz relay(all required material will be provided by firm.)
222Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
223Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
224Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
225Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
226Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
227Providing of rubber matting sheet 8/10mm
228Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
229Carriage of old scrap material from site to store center.
230Making of 11kv Bus Bar on Power Transformer LT side
231Soil filling with supply of material Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 090c02cb-323c-4b22-b4c5-17ccadcc9141.html Tender Documents 0 KB
Download BOQ_2170717.xls Tender Documents 0 KB
Download tenderform14.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.