Indian Tenders

Tender Notice

TDR 55883364
Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No 19/EWC(B)/2026-27
Tender ID 2026_MVVNL_1155363_2
Tender Brief Corrigendum : Tender For Increasing Capacity Of 33/11 Kv Sub-Stations Fatehganj East From 2×5 To 10+5 Mva, Katai Mill From 10+5 To 2×10 Mva, Baheri Rural From 10+8+5 To 2×10+8 Mva, Deorania From 3×5 To 2×5+10 Mva, Aliganj From 2×10 To 2×10+5 Mva,Rahtuiya From 10+5
City Bareilly
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 32500.0 /-
Tender Value INR 32.50 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Increasing Capacity Of 33/11 Kv Sub-Stations Fatehganj East From 2×5 To 10+5 Mva, Katai Mill From 10+5 To 2×10 Mva, Baheri Rural From 10+8+5 To 2×10+8 Mva, Deorania From 3×5 To 2×5+10 Mva, Aliganj From 2×10 To 2×10+5 Mva,Rahtuiya From 10+5 To 10+2×5 Mva & Other Associates Works Under Edc Bareilly In Business Plan 2026-27

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 15-06-2026 19/EWC(B)/2026-27 Date 18-06-2026

Key Dates

Publish Date 15-06-2026
Last Date of Bid Submission 18-06-2026
Tender Opening Date 18-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person SE EWC
Address Bareilly

BOQ Items

Name of Work:- increasing capacity of 33/11 KV Sub-Stations Fatehganj East from 2×5 to 10+5 MVA, katai mill from 10+5 to 2×10 MVA, Baheri rural from 10+8+5 to 2×10+8 MVA, Deorania from 3×5 to 2×5+10 MVA, Aliganj from 2×10 to 2×10+5 MVA,Rahtuiya from 10+5 to 10+2×5 MVA & other associates works under EDC Bareilly in Business Plan 2026-27
Sl. No. Item Description
1Part (A) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S FATEHGANJ EAST (BAREILLY)
2Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
3welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
4Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
5Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
6Repairing of complete switchyard fencing and its painting.
7Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
8Part (B) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S KATAI MILL (BAREILLY)
9Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
10welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
11Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
12Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
13Repairing of complete switchyard fencing and its painting.
14Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
15Repairing of Plinth for Power Transformer (all required material provided by firm)
16Part (C) - WORK SPECIFICATION FOR FOR INCREASING CAPACITY OF 33/11 KV S/S BAHERI RURAL (BAREILLY)
17Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
18welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
19Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
20Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
21Repairing of complete switchyard fencing and its painting.
22Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
23Part (D) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11 KV S/S DEORANIA (BAREILLY)
24Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 15 Mtr. Depth below G/L including welding etc. by boaring process at TF neutral and body earthing including cost of all required material as GI Pipe of size 40mm dia, round bar 32 mm dia, etc.
25welding & laying of G.I. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures. All required material will be provided by firm.
26Shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site in switchyard at store centre substation alongwith proper disconnection of its HT, LV, control cable and earthing connection and doing connection of HT (33kv) and LT(11kv) side of 10MVA power transformer after installation of 10MVA power transformer.
27Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth to alongwith its erection including fixing of all assessories and carriage & top up of T/F oil.
28Repairing of complete switchyard fencing and its painting.
29Hiring of D/G Set 63 KVA 3 Phase for Testing of T/F (as per site requirement)
30Repairing of Plinth for Power Transformer (all required material provided by firm)
31Part (E) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S ALIGANJ (BAREILLY)
32Supply of following materials
33GI STRIP Flat 50x6mm
34Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
35MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
3633 KV Lightening Arrestor
3733 KV 400 A Bus Isolator
3833 KV VCB 800A 750 MVA
39Control pannel I/C for 33 KV Single T/F
4033 kv O/D CT CTR 200/100/1-1-1 A
4111 KV VCB I/C CTR 600/300/5A
4211 KV VCB O/G CTR 200/100/5A
43M.S. Channel 125x65mm
44M.S.Angle 75x75x8mm
45MS Angles 50x50x6mm
46MS Channel 100x50x2028mm (For top channel & fuse set)
47M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
4811 KV 3x300 mm2 XLPE Cable
4911 KV 3x185 mm2 XLPE Cable
5011 KV Cable jointing Kit 3x185 mm2 I/D
5111 KV Cable jointing Kit 3x185 mm2 O/D
5211 KV Cable jointing Kit 3x300 mm2 I/D
5311 KV Cable jointing Kit 3x300 mm2 O/D
54PCC Pole 8.5m long.
5511 KV Pin Insulator with Pin
56Earthing Complete
57Stay set complete 16x1800mm
5811 KV disc insulator
5911 KV disc fitting
6010 SWG GI Wire
61Cost of ACSR Dog conductor
6233KV XLPE CALE 3*300SQMM
6333KV XLPE CALE BOX 3*300SQMM
64Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
65Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
66Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
67Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
68welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
69Supply of following materials for construction of power tf plinth
70Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
71Supply of bricks as per standard
72Supply of cement as per standard
73Supply of sand as per standard
74Supply of stone ballast 20mm as per standard
75Supply of steel rebar 12mm as per standard
76Supply of brick bat as per standard
77Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
78Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
79Bus Isolator Structure
80Fabrication of Structure
81C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
82Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
83Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
84Post insulator Structure
85Fabrication of Structure
86C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
87Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
88Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
8933 KV CT Structure
90Fabrication of Structure
91C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
92Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
93Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
94Lightening Arrestor Structure
95Fabrication of Structure
96C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
97Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
98Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
99Fuse Set Structure
100Fabrication of Structure
101C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
102Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
103Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
10433 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
105Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
10633 KV Bus Isolator
10733 KV Fuse Set (Provided by firm)
108Lightening Arrestor
10933 KV VCB
11033 KV CT
11133 KV Post insulator
112Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
113Control Cable 4x2.5 mm2
114Control Cable 2x2.5 mm2
115Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
116Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
117Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
118Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
11911 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
120Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
121Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
122Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
123Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
124Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
125Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
126Work related maintinance of old and used 5 MVA Transformer.
127Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
128Centrifusing of transformer oil.
129Replacement of damage brether and silica jel.(all required material will be provided by firm.)
130Replacement of damage WTI and OTI.(all required material will be provided by firm.)
131Painting of old transformer.(all required material will be provided by firm.)
132Replacement of damage buchholz relay(all required material will be provided by firm.)
133Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
134Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
135Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
136Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
137Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
138Providing of rubber matting sheet 8/10mm
139Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
140Carriage of old scrap material from site to store center.
141Making of 11kv Bus Bar on Power Transformer LT side
142Soil filling with supply of material
143Part (F) - WORK SPECIFICATION FOR INCREASING CAPACITY OF 33/11KV S/S RAHTUIYA (BAREILLY)
144Supply of following materials
145GI STRIP Flat 50x6mm
146Loading, unloading and safe carriage of the following materials from any Store Centre of Electricity store division bareilly to the site of work including measuring, weighing, loading, unloading at both ends and proper stacking at safe site.
147MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge 24x9x2+3% @6.3 Kg./M
14833 KV Lightening Arrestor
14933 KV 400 A Bus Isolator
15033 KV VCB 800A 750 MVA
151Control pannel I/C for 33 KV Single T/F
15233 kv O/D CT CTR 200/100/1-1-1 A
153Post insulator
15411 KV VCB I/C CTR 600/300/5A
15511 KV VCB O/G CTR 200/100/5A
156M.S. Channel 125x65mm
157M.S.Angle 75x75x8mm
158MS Angles 50x50x6mm
159MS Channel 100x50x2028mm (For top channel & fuse set)
160M.S angle lron 65x65x6mm, 2700mm long @ 5.8 Kg/Mt (bracing)
16111 KV 3x300 mm2 XLPE Cable
16211 KV 3x185 mm2 XLPE Cable
16311 KV Cable jointing Kit 3x185 mm2 I/D
16411 KV Cable jointing Kit 3x185 mm2 O/D
16511 KV Cable jointing Kit 3x300 mm2 I/D
16611 KV Cable jointing Kit 3x300 mm2 O/D
167PCC Pole 8.5m long.
16811 KV Pin Insulator with Pin
169Earthing Complete
170Stay set complete 16x1800mm
17111 KV disc insulator
17211 KV disc fitting
17310 SWG GI Wire
174Cost of ACSR Dog conductor
17533KV XLPE CALE 3*300SQMM
17633KV XLPE CALE BOX 3*300SQMM
177Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
178Laying of M.S. Bar of 32mm dia for making the complete earthmat in the trenches in S/s Yard of 750mm depth and 500mm width with their straightening, cutting accordingly and welding with overlap joint of 100mm cross joint, T joint.
179Making and driving of 3 Mtr. Long electrodes from 32mm dia M.S. Bar having one end conical 150mm long by heat tempering including cutting upto 750mm depth from ground level and welding with earth mat.
180Making of triangular bridge by using M.S. electrodes and G.I. Strip 50x6mm with providing of well type pipe earthing upto 20 Mtr. Depth below G/L including welding etc. by boaring process at LA and two side of 11 KV S/G including cost of GI Pipe of size 40mm dia 15 Mtr Long of ISI mark.(all material provided by firm)
181welding & laying of G.S. strip 50x6mm size with structures and all equipments in switchyard and control room, M.S. Bar including cutting, binding and proper fixing etc. complete. The welding and laying of G.S. Strips to L.A. with full length of structures and also the M.S. bridge near L.A. structures.
182Supply of following materials for construction of power tf plinth
183Supply of 90 LBS Rail pieces for T/F (44.64 KG. PER MTR.)
184Supply of bricks as per standard
185Supply of cement as per standard
186Supply of sand as per standard
187Supply of stone ballast 20mm as per standard
188Supply of steel rebar 12mm as per standard
189Supply of brick bat as per standard
190Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above from ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. ( Only erection )
191Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing, depth 0.5 Mtr. below ground level & 0.5 Mtr. above from solid soil ground level.(all decentralised material provided by firm )
192Bus Isolator Structure
193Fabrication of Structure
194C.C. in 1:2:4 for grouting of structure (0.9X0.3X1.3)X2 meter with 0.3 meter above ground level
195Plastering in 1:4 mm thick [(0.9X0.3)+(0.9+0.35)X2]X2
196Excavation of earth in all type of soil [(0.9X0.3X(1.0+0.075)]X2
197Post insulator Structure
198Fabrication of Structure
199C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
200Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
201Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
20233 KV CT Structure
203Fabrication of Structure
204C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
205Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
206Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
207Lightening Arrestor Structure
208Fabrication of Structure
209C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
210Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
211Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
212Fuse Set Structure
213Fabrication of Structure
214C.C. in 1:2:4 for grouting of structure (0.3X0.3X1.3)X2 meter with 0.3 meter above ground level
215Plastering in 1:4 mm thick [(0.3X0.3)+(0.3+0.35)X2+(0.3X0.35)X2]X2
216Excavation of earth in all type of soil [(0.3X0.3X(1.0+0.075)]X2
21733 KV VCB structure including erection , CC in 1:2:4 for grouting, plastering in 1:4 mm thick & excavation of earth in all type soil
218Mounting and installation, including Mechnical & electrical fixing and adjusting of the following equipments on their respective structures including proper adjustment:
21933 KV Bus Isolator
22033 KV Fuse Set (Provided by firm)
221Lightening Arrestor
22233 KV VCB
22333 KV CT
22433 KV Post insulator
225Complete laying and termination of copper control cable in PVC Pipe 4\\" dia from 5 MVA power T/F and 33 KV VCB in the out door switch yard in the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings.
226Control Cable 4x2.5 mm2
227Control Cable 2x2.5 mm2
228Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing from bus bar to L.A., C.T., V.C.B., Bus Isolator etc. complete with sagging and making vertical/Horizontal jumper connections through PG clamps and connecting all the equipments with each others through connecting clamps, (All type of insulator, fitting, PG clamp etc. provided by Firm).
229Making of M.S. Angle Ladder type frame of Angle (75x75x6mm) & M.S. Strip (50x6mm) near power transformer for power cable with concreting in 1:4:8 ratio of cement, sand & coarse aggregate and proper clamping (50x6mm) of the same with transformer cable (All type of, grouting material etc. will be provided by The firm).
230Making of M.S. Angle frame of (75x75x6mm) in the shape of \\"L\\" to connect T/F Neutral by copper flexible strip with proper clamping including cost of copper strip. Earthing of Power T/F Neutral shall be done separately including welding with M.S. bar Electrode bridge 1 No. after making in triangular shape and proper connection with well type earthing etc. Grouting of structure will be done in 1:4:8 ratio of cement, sand & coarse aggregate ( All type laying material will be provided by the Firm except steel cables ).
231Laying of 11KV cable of different size from power T/F to control room I/C and control room to D/P outside Sub-Station over a pad of river sand . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 11 KV cables ).
23211 KV Cable hoisting with GI Pipe 6\\" dia (All type of material provided by the Firm).
233Laying of 33KV 3x300 mm2 xlpe cable from existing bus bar gantry to proposed 33 kv bay with support of ladder . Cable shall be laid 500mm below the ground in the yard by covering three sides with Ist Class brick and Ganga sand (All type laying material will be provided by the Firm except 33 KV cables ).
234Termination and hosting of 33 KV 3x300 mm2 XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with suitable connectors.
235Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 6\\" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 03 Nos. feeders name plate on D/P. (all type of grouting material provided by the Firm).
236Erection of 11 KV incoming, outgoing and bus coupler panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
237Erection & testing of single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
238Termination of 11 KV Different size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of T/F switch gear panels and double poles by providing suitable connectors.
239Work related maintinance of old and used 5 MVA Transformer.
240Attending of leakage of power transformer (Replacement of damage gasket kit etc)(all required material will be provided by firm.)
241Centrifusing of transformer oil.
242Replacement of damage brether and silica jel.(all required material will be provided by firm.)
243Replacement of damage WTI and OTI.(all required material will be provided by firm.)
244Painting of old transformer.(all required material will be provided by firm.)
245Replacement of damage buchholz relay(all required material will be provided by firm.)
246Replacement of damaged 33kv, 11kv bushings (all required material will be provided by firm.)
247Carriage and top up of transformer oil from any store/workshop of Bareilly Zone 1, Bareilly Zone 2
248Shifting of existing 11 KV VCB panel and re arrange its in control room including its power cable, control cable and busbar connections.
249Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
250Making of cable trench of size 750 mm deep and 750 mm wide and 9 inch wall by Ist class bricks in the ratio 1:6 Base concreting of the wall to be done in ratio 1:6:12 and plaster 12mm thick in ratio 1:4. with trench cover for laying of control cables and 11 KV cables in ssitchyard as per RESSPO. All material will be supllied by the firm.
251Providing of rubber matting sheet 8/10mm
252Shifting and dragging of 33/11kv 5mva tf from road side to its plinth along with its erection including fixing of all assessories and top of oil.
253Carriage of old scrap material from site to store center.
254Making of 11kv Bus Bar on Power Transformer LT side
255Soil filling with supply of material Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download 89e24790-7882-4612-8c6e-6e6fc8dd2543.html Tender Documents 0 KB
Download BOQ_2170494.xls Tender Documents 0 KB
Download tenderfrom19.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.