| 1 | Supply of 33 KV, 3 X 300 Sqmm standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) 33 KV grade. (Rate Analysis of Cost Data Book 2026) |
| 2 | \\"Supply and jointing heat shinkable kit for 33 KV 300sqmm 3core XLPE cable including cost of all material, labour, T & P etc. as per proper completion of work. In door Type (Rate Analysis of Cost Data Book 2026) |
| 3 | \\"Supply and jointing heat shinkable kit for 33 KV 300sqmm 3core XLPE cable including cost of all material, labour, T & P etc. as per proper completion of work. Out door Type (Rate Analysis of Cost Data Book 2026) |
| 4 | Supply and fixing of 33 KV stright through heat shrinkable cable jointing kit 300 Sqmm complete with labour T&P etc as per direction of E/Ic. (Rate Analysis of Cost Data Book 2026) |
| 5 | Supply/fabrication and Erection of 33 KV Double Pole Cable Exposure D/C complete with 410SP-55 11 mtr long ST Pole-2 Nos, 33 kv pin insulator with pin and nut-9 nos, top channel 100x50 mm, MS angle 65x65x6mm, LT XLPE cab le AL. 1x400sqmm-18mtr, danger board with clamp-2 nos, barbed wire, pole fencing-2 nos, aluminium lug- 12 nos, holding MS clamps-12 nos, nut bolts etc icluding painting of pole with aluminium paint over red oxide primer all complete direction of E/Ic. as per UPPCL specification |
| 6 | laying of 33 kv armoured XLPE cable with HDD Drilling method complete with labour T&P etc all as per direction. |
| 7 | Supply fabrication and erection of 33 KV / 11 KV Cable Hoisting with 150 mm dia MS/GI pipe, holding clamp, nut bolt etc as required all complete as per UPPCL norms (Shedule - 33)(Analysised on Lesa Cost Data Book/Lesa Estimate ) |
| 8 | S/F of HDPE pipes (upto Pn 6kg pressure Rating material Grade PE 80, Nominal Dia (OD) 160mm 9.1mm thicknes for cable Complete in all respect as per relevants IS Technical Specification. 110 sq.mm outer dia |
| 9 | Supply, testing and commissioning of 33 KV RMU Panel- 33KV, 630A, 25KA/1Sec, 3-Way, non extensible outdoor IP54, SF6 Gas insulated Ring Main Unit consist of: 1- No motor operated Vacuum Circuit Breaker (VCB), and 2 Nos motor operated load break Switch, with Suitable site replaceable bushing and full front door cover. Make of Vacuum interrupter shall be same as make of RMU. Having CT ratio 200-100/1Amp, accuracy class 0.5 (Configuration: 2 Nos LBS, 1 no VCB)Whose GTP Approved in MVVNL having valid CPRI/ERDA/NABL Lab type test report. |
| 10 | Construction of Solid B/W Transformer Plinth of size 1.5mx1.5mx1.25m above G.L.The top of the plinth shall be of RCC 15 cm thick with material & labour all complete as per direction of E/Ic. ( Rate Based on PWD schedule civil2019) |
| 11 | Supply of 33 kv cable /11 Kv Cable laying material for double circuit such as brick, sand stone slab of size 600x450x50mm complete with exacavation back filling, labour all complete as per direction of E/ic (Shedule 09) (Analysised on Lesa Cost Data Book/Lesa Estimate) |
| 12 | Supply and Eraction of Pipe Boring earthing Proper complition of work as for direction of E/I (Shedule - 53) (Analysised on Lesa Cost Data Book/Lesa Estimate ) |
| 13 | Supply and Fixing of Cable Route Marker as per direction of E/Ic. (Rate as per PCL Estimate) Please Enable Macros to View BoQ information |