| 1 | Dismantling of old damaged panel from site with all damaged switchgears, measurement instrument, indicating lights, relay and Removing of complete wiring and mechanical connection at site and shifting at safe place as per instruction by engineer in charge. |
| 2 | Fabrication LT PANEL. SIZE: 2000H X 2000 L made out of 14 SWG CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets with IP 54 protection. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized. The bus-bar support insulator will be made of materials such as SMC/DMC. The bus bar will be covered with heat shrinkable PVC sleeve throughout in red, yellow & blue color to identify three phases & black for neutral. The bus-bar support insulator made of non-deteriorating, vermin proof, non-hygroscopic materials such as SMC/DMC |
| 3 | Incomer form Main L.T Panel 200 Amp. TPN MCCB 50 KA Make : L&T/Siemens |
| 4 | Digital Ammeter with built in selector switch supply 60-300Volt ac |
| 5 | CT200/5A,CI-1.0, Make :L&T, Rishabh |
| 6 | RYB Indicating Light LED TPYE |
| 7 | Out Going MCB 63 Amp.415 V DP 50KA Make: L&T/Siemens |
| 8 | MCCB 100 Amp.415 V TPN Make: L&T/Siemens |
| 9 | Direct-on-Line Starters in Sheet-Steel Enclosure Type MN / ML (Motor Rating AC-3 Duty, 415V, 50Hz, 3-Ph) Suitable for 30 HP Make : DJB Approved |
| 10 | DOL Star-Delta Motor Starter Suitable for 2 HP Make : DJB Approved |
| 11 | Digital Ammeter with built in selector switch supply 0-10A ac |
| 12 | Digital Voltmeter with built in selector switch supply 0-400Volt. ac |
| 13 | Indicating LED lights sets R.Y.B. & ON 415V Make: siemens/ vaishno/ L&T |
| 14 | Fixing of above components in fabricated panel as like new indicating light, Ammeter, Voltmeter, CT,MCCB,MCB in existing panel, feeder modification ,providing /fixing of base frame for fitting of for fixing of panel |
| 15 | Earthing with G.I earth pipe 4.5 meter long,40mm dia. Including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe with charcoal/coke and salt as per requirement the site SOR DJB 10.2 |
| 16 | Providing and fixing 25mmX5 mm G.I strip on surface or in recess for connections etc. as requirement. SOR DJB 5.15 |
| 17 | New generation energy saving and environmental friendly long life 70 watt LED street light made up of pressure die cast aluminum housing with high efficiency LED as lighting source and lens embedded PC cover having Bottom Opening separate driver compartment with IP66 protection and impact resistance of IK08 with fitting all accessories pipe nut bolt etc. as per requirement at site |
| 18 | Testing & commissioning of the APFC panel with relevant IS as follow:- Check equipments specification- Continuity and ear thing-MCCB mechanism and alignment-Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth.- All functional tests-Checking for all tightness of nuts and bolts-Setting of APFC relay parameters to achieve target PF -Alignments of doors etc.-interlocking tests Please Enable Macros to View BoQ information |