| Sl. No. | Item Description |
| 1 | Redevelopment of Thiruvananthapuram Railway Station – Foundation work of Departure Concourse (DCC) |
| 2 | Schedule A - Civil works DSR 2021 Items |
| 3 | Schedule B1 - Civil works USSOR 2021 ITEM |
| 4 | Schedule B2 - USSOR 2021 - Cement |
| 5 | Schedule B3 - DSR 2021 - Steel |
| 6 | Schedule B4 - Market Rate |
| 7 | Schedule C - Water supply & Sanitary |
| 8 | Schedule D - Electrical Works |
| 9 | Schedule E - Fire |
| 10 | Schedule A - Civil works DSR 2021 Items |
| 11 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed. All kinds of soil |
| 12 | 100 mm thick cement concrete flooring with concrete of mix M15 |
| 13 | Close timbering in case of shafts, wells, cesspits, manholes and the like including strutting, shoring and packing cavities (wherever required) etc. complete. (Measurements to be taken of the face area timbered). Depth exceeding 1.5 m but not exceeding 3 m |
| 14 | Providing and laying in position cement concrete of M10 excluding the cost of centering and shuttering - All work up to plinth level: |
| 15 | Centering and shuttering including strutting, propping etc. and removal of form work for Foundations, footings, bases for columns |
| 16 | Providing and laying in position machine batched and machine mixed cement concrete of design mix M-40 grade cement concrete for in reinforced cement concrete work, using with cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction ofEngineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately. All work upto plinth level |
| 17 | Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concretepile cap |
| 18 | Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand(zone-III) : 4 graded stone aggregate 20mm nominal size). |
| 19 | Providing and laying factory made Precast concrete solid blocks of 200 mmthickness of grade M10 made of C&D waste from approved manufacturer infoundation and plinth in: |
| 20 | Providing and laying in position machine batched and machine mixed cement concrete of design mix M-40 grade in reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level |
| 21 | Providing and laying in position machine batched and machine mixed design mix M-35 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level |
| 22 | Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc |
| 23 | Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform |
| 24 | Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers |
| 25 | Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 26 | Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases) |
| 27 | Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and walls Under 20 cm wide |
| 28 | Providing and laying autoclaved aerated cement blocks masonry with 150mm/ 230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately). |
| 29 | 12 mm cement plaster of mix: 1:4 ( 1 cement : 4 fine sand) |
| 30 | Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface :Water thinnable cement primer |
| 31 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 32 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.New work (two or more coats) over and including water thinnable priming coat with cement primer |
| 33 | Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge. Granite work |
| 34 | Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 35 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followedwith water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry |
| 36 | Providing and fixing of rolling shutters |
| 37 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : |
| 38 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) |
| 39 | Providing and laying vitrified floor tiles in different sizes (thickness to bespecified by the manufacturer) with water absorption less than 0.08%and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 40 | 40 mm thick marble chips flooring rubbed and polished to granolithicfinish, under layer 34 mm thick cement concrete 1:2:4 (1 cement : 2coarse sand : 4 graded stone aggregate 12.5 mm nominal size) and toplayer 6mm thick with white, black, chocolate, grey, yellow or green marble chips of sizes from 1 mm to 4 mm nominal size, laid in cementmarble powder mix 3:1 (3 cement : 1 marble powder) by weight inproportion of 4:7 (4 cement marble powder mix : 7 marble chips) byvolume, including cement slurry etc. complete :Dark shade pigment with ordinary cement |
| 41 | Schedule B1 - USSOR 2021 |
| 42 | Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of garde M-25 of 750mm diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavatedearth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). |
| 43 | Providing, fabricating and installing casing pipe for bored piles of 750mm dia with 6mm thickness of steel plate including all labour, materials, pumping and bailing out water wherever required, complete as per technical specifications as directed by Engineer in charge |
| 44 | Dewatering of natural or accumulated water from any location. Payment to be done for Horsepower of pump multiplied by pumpinghours. |
| 45 | Extra for chiselling, in addition to boring of piles, if chiselling is required to be carried out in hard rock or big stone boulders larger than 30 cm, manually or by any other suitable means, |
| 46 | Schedule B2 - DSR 2021 Item - Steel |
| 47 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 48 | Schedule B3 - USSOR 2021 Item -Cement |
| 49 | Ordinary Portland Cement 53 grade of approved brands/makes |
| 50 | Schedule B4 - Non (DSR/USSOR) Item -Civil works |
| 51 | Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge |
| 52 | Providing and fixing of Fire Rated Door Double leaf including all fittings as per the sketch and specification attached as Ann 1 |
| 53 | Providing and fixing of FRP Door (750 X 2100) including all fittings as per the sketch and specification attached as Ann 2 |
| 54 | Providing and fixing of WPC door including all fittings as per the sketch and specification attached as Ann 3 |
| 55 | Providing and fixing of Glazed wooden ventilators as per the sketch and specification attached as Ann 4 |
| 56 | Providing and fixing of Glazed wooden window with all fittings as per the sketch and specification attached as Ann 5 |
| 57 | Providing and fixing of fully glazed fire-rated door for lift lobby including all fittings as per the sketch and specification attached as Ann 6 |
| 58 | Providing and laying Porcelain tile in wall in different sizes (thickness tobe specified by the manufacturer) with water absorption less than 0.08%and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement:4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm includinggrouting the joints with white cement and matching or pigments ,epoxy filling etc. Thetiles must be cut with the zero chipping diamond cutter only .Laying oftiles will be done with the notchtrowel, plier, wedge, clips of requiredthickness,leveling system and rubber mallet for placing the tiles gentlyand easily.Porcelain tile of size (1200 x600) |
| 59 | Providing and laying Porcelain tile floors in different sizes (thickness tobe specified by the manufacturer) with water absorption less than 0.08%and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement:4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm includinggrouting the joints with white cement and matching or pigments ,epoxy filling etc. Thetiles must be cut with the zero chipping diamond cutter only .Laying oftiles will be done with the notchtrowel, plier, wedge, clips of requiredthickness,leveling system and rubber mallet for placing the tiles gentlyand easily.Porcelain tile of size (600 x600) |
| 60 | Providing and fixing balcony door including all fittings |
| 61 | Providing and laying Porcelain tile in wall in different sizes (thickness tobe specified by the manufacturer) with water absorption less than 0.08%and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement:4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm includinggrouting the joints with white cement and matching or pigments ,epoxy filling etc. Thetiles must be cut with the zero chipping diamond cutter only .Laying oftiles will be done with the notchtrowel, plier, wedge, clips of requiredthickness,leveling system and rubber mallet for placing the tiles gentlyand easily.Porcelain tile of size (1200 x600) |
| 62 | Schedule C- Water supply & Sanitary |
| 63 | Supplying, installing, testing & commissioning at site in position of colour or white vitreous china following Water Closet of approved make and model with P/S Trap, bolts, nuts, UF Soft Close Slim Seat Cover, Hinges, Dual Flush Cistern with fitting and fixing accessories, PVC brass hinges and rubber buffers with all necessary fittings / accesories required to complete including cutting and making good the walls and floors wherever required as per the direction of Engineer in charge.Wall Mouted Europian Water Closet (EWC) with concealed cistern |
| 64 | Supplying, installing, testing & commissioning at site in position colour or white vitreous china clay following Wash Basin of approved make with C.I. brackets, 32 mm C.P. brass waste of standard pattern with all accessories required for complete installation, including painting of fittings and brackets, cutting and making good the walls wherever require with all accessories required for complete installation as per the direction of Engineer in charge.Falt Back Wash Basin with half pedastal |
| 65 | Supplying, installing, testing & commissioning at site in position of following with exposed part kit and aerator, Connecting legs & wall flanges, 15mm. nominal bore, including all necessary accessories required for complete installation, all as per manufacturer's instruction and to the approval of the Engineer-in-charge. |
| 66 | Supplying, installing, testing & commissioning at site in position approved make C.P. Ablution Spray Health Faucet with wall hook, 8 mm dia, 1 meter long spirochrome flexible tube, back flow preventer, etc. necessary nuts with all accessories required to complete including cutting and making good the walls wherever required and as per the direction of Engineer in charge. |
| 67 | Supplying, installing, testing & commissioning at site in position approved make 15mm dia, C.P. brass Angle Valve with CP wall flange etc. complete with all accesories required and as per the direction of Engineer in charge. |
| 68 | Supplying, installing, testing & commissioning at site in position approved make Soap Dispenser etc. complete with all accesories required and as per the direction of Engineer in charge. |
| 69 | Supplying, installing, testing & commissioning at site in position approved make CP Towel Ring with CP wall flange etc. complete with all accesories required and as per the direction of Engineer in charge. |
| 70 | Supplying, installing, testing & commissioning at site in position approved make following Flexible Braided Connectors, 15mm. nominal bore, 450mm. Long with higher thermal stability for cold and hot water, etc. complete with all accesories required and as per the direction of Engineer in charge. |
| 71 | Supplying, installing, testing & commissioning at site in position approved make approved make Bevelled Edge Mirror of superior glass complete with C.P. brass screws and washers etc. complete with all accesories required and as per the direction of Engineer in charge. |
| 72 | Supplying, laying, Testing and commissioning at site in position uPVC pipe of 32mm OD -10Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, 'Y', couplings, adapters & clamping with Universal clamps 1metre spacing, Anchor fasteners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For sunken drain - Internal) |
| 73 | Supplying, laying, Testing and commissioning at site in position uPVC pipe of 50mm OD 6 Kgf/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, 'Y', couplings, adapters & clamping with Universal clamps/U bolt 1metre spacing, Anchor fasteners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For Soil & Waste pipes -Internal). |
| 74 | Supplying, laying, Testing and commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters, rodding eye & clamping with Universal clamps, Anchor fasteners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site.(For Soil & Waste pipes - Internal).75 mm OD |
| 75 | 110 mm OD |
| 76 | Supplying, laying, Testing and commissioning at site in position uPVC pipe (SWR) of 4kg/cm2 (IS:4985) / Type A (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site. (For Vertical & Horizontal piping for Rainwater & Vent).75 mm OD |
| 77 | 110 mm OD |
| 78 | Supplying, laying, Testing and commissioning at site in position Ring uPVC pipe (SWR) of 110mm OD Type B (IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735) fittings with bosses where required eg. Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Universal clamps, Anchor fastners, Threaded rod, nuts, washers etc complete, including cutting and making good the walls and floors as required at site.(For Vertical & Horizontal Shaft piping). |
| 79 | Supplying, Installing, Testing & Commissioning at site in position of approved make following uPVC Fabricated Multi Floor Trap, Deep Seal (7”) - 110 X 50/75 mm dia inlet / outlet with suitable supporting on GI slotted rails (1.6mmthick) full threaded rod, Anchor fasteners etc. complete in all respects as per the drawing, specification and direction of engineer in charge. |
| 80 | Supplying, Installing, Testing & Commissioning at site in position of approved make Heavy Duty Stainless Steel Square Flat cut lock anti Cockroach Trap made of Grade 304 stainless steel for 110 mm floor traps complete in all respects as per the drawing, specification and direction of engineer in charge. |
| 81 | Supplying and installing at site in position Roof Drain assembly -110mm dia consisting of epoxy coated cast iron (CI) hopper, aluminium ring, and aluminium dome-type grating, complete with SS 304 grade stainless steel screws for secure fixing. The unit shall be suitable for roof drainage applications, designed to effectively collect and channel rainwater, preventing clogging and ensuring durability under external weather conditions. |
| 82 | Supplying, laying, Testing and commissioning at site in position uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, with all specials etc. of approved make, complete with all necessary Fittings including elbows, unions, tees, reducers, couplings, nipples, brass threaded fittings, etc. for jointing pipes by solvent welding using manuacturer recomended solvent, exposed on walls complete with clamping in position with exposed on walls complete with clamping in position with G.I. \\"U\\" bolts (8 mm thick) on G.I. slotted rails (1.6 mm thick), Rail legs (2.5 mm thick) of approved make, as per specification, drawing and direction of Engineer in charge. Internal / External work - Exposed on wall / Ceiling and Shaft20 mm dia. Pipes. |
| 83 | 25 mm dia. Pipes. |
| 84 | 32 mm dia. Pipes. |
| 85 | Supplying, Installing, Testing & Commissioning at site in position of approved make full way lever operated Forged Brass Ball valve (PN 25) of brass body with forged brass hard chrome plate with all necessary fittings including Male Adapter (Brass Threads) in position as per specification, drawing and direction of Engineer in charge.20 mm dia. |
| 86 | 32 mm dia. |
| 87 | Supplying, Installing, Testing & Commissioning at site, in position, of 20mm dia Automatic Air Release Valves made of Brass of approved make, for water supply pipes. The valve shall function to automatically release trapped air from the pipeline system, thereby ensuring smooth and efficient water flow. The work shall be carried out as per technical specifications, approved drawings, and the direction of the Engineer-in-Charge. |
| 88 | Supplying, Installing, Testing & Commissioning at site in position of approved make 65mm dia Brass Float valve (PN 10) with PP float & nipple with brass threaded insert, brass back nuts, piston and bolts etc. complete in all respect as per specification, drawing and direction of Engineer in charge. |
| 89 | Supplying, Installing, Testing & Commissioning at site in position of approved make Multi Jet Water Meter - 32mm dia with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser, retrofitable for pulse output and conforming to ISO-4064 Class B complete in all respect as per specification, drawing and direction of Engineer in charge. |
| 90 | Supplying, Installing, Testing & Commissioning at site in position of approved make Pressure Reducing Station - 32mm dia Screwed end complete with GM / Bronze body Pressure Reducing Valves, suitable for a maximum inlet pressure of upto 25 bars reduce to anywhere between, Pressure Gauges with siphon connections on upstream and down stream etc. complete in all respect as per specification, drawing and direction of Engineer in charge. |
| 91 | Supplying, laying, Testing & Commissioning at site in position of approved make PVC pipe of IS 4985 (160mm dia 6 kg/cm2), as per provisions of IS: 1742-1983 (Code of practice for building drainage), joining the pipes with all necessary Fittings including bends, couplers, sockets, connections, reducers, etc. by solvent welding using manuacturer recomended solvent. Pipes to be laid to true line with proper PCC supports at appropriate intervals as required. Work includes all cutting, jointing, earth work excavation, backfilling, compacting, and testing the pipeline for leak-proof performance, all complete as per drawings, specifications, and direction of the Engineer-in-Charge. |
| 92 | Supplying, laying, Testing & Commissioning at site in position of approved make PVC pipe of IS 4985 (110mm dia 4 kg/cm2), as per provisions of IS: 1742-1983 (Code of practice for building drainage), joining the pipes with all necessary Fittings including bends, couplers, sockets, connections, reducers, etc. by solvent welding using manuacturer recomended solvent. Pipes to be laid to true line with proper PCC supports at appropriate intervals as required. Work includes all cutting, jointing, earth work excavation, backfilling, compacting, and testing the pipeline for leak-proof performance, all complete as per drawings, specifications, and direction of the Engineer-in-Charge. (Rain Water Pipe) |
| 93 | Providing, laying, and Testing & Commissioning at site uPVC Pipes of 32mm nominal outer dia, Schedule 40, conforming to ASTM D 1785, including all required uPVC fittings as per ASTM D 2466, for external water supply work. The scope includes cutting, jointing using one-step using manuacturer recomended solvent. Pipes to be laid to true line with proper PCC supports at appropriate intervals as required., earth work excavation, backfilling, compacting, and testing the pipeline for leak-proof performance, all complete as per drawings, specifications, and direction of the Engineer-in-Charge.External work |
| 94 | Providing, laying, and Testing & Commissioning at site uPVC Pipes of 32mm nominal outer dia, Schedule 40, conforming to ASTM D 1785, including all required uPVC fittings as per ASTM D 2466, for external water supply work. The scope includes cutting, jointing using one-step using manuacturer recomended solvent. Pipes to be laid to true line with proper PCC supports at appropriate intervals as required., earth work excavation, backfilling, compacting, and testing the pipeline for leak-proof performance, all complete as per drawings, specifications, and direction of the Engineer-in-Charge.External work |
| 95 | Schedule D - Electrical Works |
| 96 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 97 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 98 | Wiring for stair case light points with 2.5 sq.mm FRLS PVC insulated copper conductor single core cable in and including surface / recessed medium class PVC conduit and all accessories required for complete installation etc , with 1 way modular switch, modular plate, suitable GI box medium class PVC conduit and all accessories required etc and earthing the point with 2.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required and instructed by engineer in charge/consultant. (Note - Staircase light point shall be controlled by a single switch located inside fire control room in ground floor as per latest fire norms)One light point controlled by one way switch (At ground floor) |
| 99 | Loop wiring for Light point |
| 100 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 x 1.5 sq.mm + 1 x 1.5 sq.mm earth wire |
| 101 | 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earth wire |
| 102 | 2 x 4 sq.mm +1 x 4 sq.mm earth wire |
| 103 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 104 | 25 mm |
| 105 | 32 mm |
| 106 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 107 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 108 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 109 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 110 | Supply and fixing 3 pin, 6A ceiling rose on the existing junction box / wooden block including connection etc as required. |
| 111 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (8 + 12), Double door |
| 112 | 6 way (8 + 18), Double door |
| 113 | Supplying and fixing of following ways surface/ recess mounting, Vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (8 + 12), Double door |
| 114 | Supplying and fixing of following ways surface/ recess mounting, Vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 way (4 + 24), Double door |
| 115 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 116 | Supply and fixing of Perforated Cable tray with horizontal & vertical bends, reducers, Tee's, cross over, suitable supports and brackets and other accessories as required confirming to IEC-61537. The Tray shall be galvanized for corrosion protection confirming to DIN EN 10346 / ISO 1461. The trays should be tested for a max. safe working load of 150 Kgs with a span distance of 1.5 meters and the deflection should be within the limits as per standard. The safety factor shall be 1.7 times of the safe working load. The perforated tray shall be supplied with the standard length of 3 Mtr. Make: OBO Bettermann or Equivalent50 mm width X 60mm Height |
| 117 | Supply and fixing of Cable Ladder with horizontal & vertical bends, reducers, Tee's, Cross over, supports, brackets and other accessories as required confirming to IEC-61537. The Cable Ladder shall be made of 1.5mm thick sheet steel up to 600mm & 2.0mm thick up to 1000mm.The cable Ladder shall be galvanized for corrosion protection confirming to ISO 1461. The cable ladder should be tested for safe working load of 225 Kg/ Mtr with a span distance of 2 Mtr the deflection should be within the limits as per standard. The cable ladder shall be supplied in standard length of 3000 mm. The rung size shall be of 30x15mmm size suitable for fixing the cable clamps the space between the rungs shall be 300mm.200 mm Width X 75 mm Height |
| 118 | 450 mm Width X 75 mm Height |
| 119 | 1000 mm Width X 75 mm Height |
| 120 | Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) amended up to date. 3.5C X 150 Sq.mm Al Cable |
| 121 | 4C X 10 Sq.mm Al Cable |
| 122 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface/cable tray as required.Up to 35 sq. mm (clamped with 1mm thick saddle) |
| 123 | Above 95 sq. mm and up to 185 sq. mm (clamped with 25/ 40x3mm MS flat clamp) |
| 124 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.3.5C X 150 Sq.mm Al Cable |
| 125 | 4C X 10 Sq.mm Al Cable |
| 126 | Supply and laying and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:1554 (Part-I) 1964 of the following sizes in medium duty conduit / cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60 cm and making good the damages colour washing etc as required. and instructed by engineer at site/consultant.1CX6 Sq.mm Copper Flexible Cable |
| 127 | Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.1Cx16 Sq.mm Copper Flexible Cable |
| 128 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 129 | Triple pole |
| 130 | Four pole |
| 131 | Supplying and fixing 40 A to 63 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 132 | Four pole |
| 133 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 134 | RCBO - Supplying, fixing, testing and commissioning following four pole and double pole , 415 volts and 240 volts, residual current circuit breaker with overload protection (RCBO) of the following rating and sensitivity current in the existing MCB SPN and TPN horizontal/vertical DB's complete with connections, etc. as required and instructed by engineer in charge/consultant..32A 30mA FP RCBO |
| 135 | MCCB: Supply, fixing, testing and commissioning of following rating, breaking capacity and pole, Thermal Magnetic Release type MCCB in existing Vertical Distribution Board with spreader links, terminal connections and all accessories as required making all necessary connections etc as required and instructed by engineer in charge/consultant.80 16 kA FP MCCB |
| 136 | Isolator With Enclosure - Supply and fixing of following DP/FP 230V / 415V, isolators in sheet steel powder coated enclosure with door interlock facility on surface confirming to IEC 60947-3 complete with all accessories, connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation.6A - 40A FP Isolator with enclosure |
| 137 | Fabrication, supply, erection, testing, and commissioning of a cubicle-type, dust and vermin-proof, floor-mounted, front-operated Main Panel Board, constructed to Form 4A specifications, with a protection rating of IP-54 for dust and water ingress. The panel shall be made from 16 SWG thick CRCA sheet with 11-tank treatment, fully compartmentalized, and complete with hinged and earthed front doors. It shall include a nameplate, danger notice board, heavy-duty rubber gaskets, and removable gland plates made of 3mm thick sheet steel. All components will be as shown in the schematic drawing. All opening parts of the panel shall be sealable to ensure enhanced security and protection.Incomer - 40A, FP MCB Isolator - 1No.40A, 415V, 25 kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Multi function digital LED meters with accuracy class 1, with necessary CT and accessories for measuring Voltage, current, Frequency, Power Factor, kW, kVA, Old energy, On hours, site selectable kWh/kVAh - 1SetClass B+C / Class 1 + 2 Surge arrestor device with necessary rating MCB for back-up protection - 1 No.RYB phase indicating LED lamps with control fuses and switches - 1 set.Outgoing- 25A, 100mA, FP RCBO - 1 No.16A, 30mA, DP RCBO - 1 No.16A, 415V, 16 kA best conductivity Al DP bus bar with SMC supports, heat shrinkable sleeves etc complete as required - 1 Set10A, 10kA, SP MCB - 1 No.6A, 10kA, SP MCB - 3 Nos.Supply, Installation, Testing and Commissioning |
| 138 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 139 | Supply, fixing, testing and commissioning of Linear Surface Mounted LED Batten with a nominal system lumen output of 2000 lumens. System wattage should not exceed 20W. The luminaire shall have a rated system lifetime of 50,000 burning hours at 70. The luminaire should have a color temperature of 6500K and CRI>80. Driver of the luminaire shall have THD < 20% and PF > 0.95. The heat sink should be made of Extruded thermal polycarbonate and the luminaire optics shall have a high efficiency PC diffuser. The light fixture including driver shall comply to IEC and IS. Similar to Wipro Make Model No:LL20-221-XX-65ALNE*** or equivalent, directly / suspended on ceiling / wall / false ceiling using clamps / GI chain / rope, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required with all accessories required for complete installation. |
| 140 | Supply, fixing, testing and commissioning of 12W Surface mounted Square LED Downlighter, high efficiency with a nominal system lumen output of 1000 lumens. Luminaire wattage should not exceed 9W. The luminaire should have a CRI>80. Driver of the luminaire shall have THD<20% and PF > 0.9. The heat sink should be made of die cast aluminium and the luminaire optics shall have a high efficiency PC diffuser. Aesthetically designed 1X1 LED flat panel of surface mounting which provides soft-light and glare free symmetrical illumination. Similar to Wipro make Model No: LD80-101-XXX-60-SM or equivalent, directly / suspended on ceiling / wall / false ceiling using clamps / GI chain / rope, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required with all accessories required for complete installation. |
| 141 | Supply, fixing, testing and commissioning of 15W 1X1 Square LED Downlighter, high efficiency with a nominal system lumen output of 1610 lumens. Luminaire wattage should not exceed 15W. The luminaire should have a CRI>80. Driver of the luminaire shall have THD<20% and PF > 0.9. The heat sink should be made of die cast aluminium and the luminaire optics shall have a high efficiency PC diffuser. Aesthetically designed 1X1 LED flat panel of surface mounting which provides soft-light and glare free symmetrical illumination. Similar to Wipro make model No: LD81-131-XXX-6-SM or equivalent, directly / suspended on ceiling / wall / false ceiling using clamps / GI chain / rope, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required with all accessories required for complete installation. |
| 142 | Supply, fixing, testing and commissioning of 30W 2X2 LED SQUARE LIGHT with a nominal system lumen output of 3300 lumens and a minimum system efficacy of 95 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. The luminaire should have a CRI > 80. The luminaire shall meet IP54 rating with THD<10% and PF>0.9. The luminaire housing should made of powder coated CRCA sheet steel with HET Diffuser. The total power consumption should not exceed 30W (including driver). LED Shall be Similar to Wipro Make CRCO10R030HP57G1L1 or equivalent, directly / suspended on ceiling / wall / false ceiling using clamps / GI chain / rope, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required with all accessories required for complete installation. |
| 143 | Supply, fixing, testing and commissioning of LED Bulk Head Luminaire with max wattage of 10W with system lumens not less than 1100 Lumes. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. Housing shall be pressure die cast aluminium with IP 65 rating. luminaire should have a color temperature of 5700K and CRI>80. Driver of the luminaire shall have THD<10% and PF >0.9. There should be in-built surge protection up to 2 KV. The LED Shall be ANSI Bin C78.377A and IEC62471 with class1 electrical insulation. Similar to Wipro Make LW07-141-XXX-57-XX or Equivalent, directly / suspended on ceiling / wall / false ceiling using clamps / GI chain / rope, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required with all accessories required for complete installation. |
| 144 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 Nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 145 | Supply, installation, testing and commissioning of exhaust fan of approved make 250mm (sweep size) BLDC motor Energy Saving Exhaust Fan (Black) as per the specification. Similar to atom Berg efficio or equivalent. |
| 146 | 7.5 kVA UPS : Supply, installation, and commissioning of 7.5 kVA UPS standalone Configuration. 1 phase in and out. with indoor (IP21) with surge protection system with 30 Min backup battery @ 7.5 kva Load Minimum VAH 26 AH*20 per batteries of approved make, Input pf 0.99, Input THDi < 5%, double conversion technology, 230V, 50Hz single phase, output 230V, 50Hz single phase, It shall be 100% generator compatible, with Efficiency > 94 % and output power factor 0.9 (7.5kVA = 6.75kW), Eco mode Efficiency 98% and including all accessories etc as required. The acoustic noise at 1m of the system should be<70dB.The system shall comply to IEC /EN 62040-1 (type test of same model will be provided, and relevant IS standard along. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic & manual bypass switch. The system shall have IGBT rectifier and inverter. |
| 147 | Supply, installation and testing of 3 meter air terminal with accessories, providing and fixing air terminals as per IEC - 62305 part-3 16mm rod tapered to 10 mm aluminium rod: Meets the technical specification according to DIN EN 50164 - 2 (VDE 0815 part 202). Meets the requirement of VDE0185/305 (IEC 62305) 101 VL 4000: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. System consist of Fang Fix with base and clamp on the top air terminal is erected. Fang fix clamp made of cable bracket, lightning tested for 100 KA 10/350 micro sec waveform. 2 nos of 16 KG stone of 365 mm diameter, high level of stability. Quick and easy mounting of interception rod using anchors. Concrete, frost-resistant, can be stacked, including all accessories as required for complete installation as instructed by engineer in charge. |
| 148 | Supply and installation of 8mm solid aluminium round conductor: For concrete building Meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance, including all accessories as required for complete installation as instructed by engineer in charge.a) Vertical run- Down conductor |
| 149 | b) Horizontal run - Parapet application |
| 150 | Supply and installation of 8mm solid aluminium round conductor: For TERRACE APPLICATION Meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Stainless steel base with Polyamide Conductor holder top: Adjustable width from 185-260mm. Infinitely adjustable conductor holder. Fast installation using wing screw. Bottom section with 8.5mm diameter slot With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance |
| 151 | Supply and fixing of cross connector / T connector: to route vertical down conductor /mesh formation made of stainless steel/hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts and all accessories as required for complete installation |
| 152 | Supply and fixing of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IEC 62305) and all accessories as required for complete installation |
| 153 | Supply and Fixing Equipotential bonding rail for Lightning Arrestor applications (Test Joint). Equipotential bonding rail for equipotential bonding according to DIN VDE 0100-410/540 and lightning protection equipotential bonding according to DIN VDE 0185-305. Base plate and cover hood from polystyrene. Colour: Black, UV resistant. Can be used outdoor also. Screw and crossbar made of VA. Capable of carrying lightning current 100KA (10/350). Connection options: 7 x single or multi-core conductors to 25mm square or fine core conductors to 16mm square. 1 x round cable Rd 8-10. 1 x flat strip to FL 30 or round cable RD 8-10 including corrosion tapes and all accessories as required for complete installation as instructed by engineer in charge. |
| 154 | Supply and laying hot dip Galvanised Steel Flat having 70 microns zinc 30X3 mm thick from earth electrode directly in ground as required. Hot Dip GI strip, corrosion resistant. Cross sectional area of 90mm square According to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IEC 62305) Zinc coating: 500 g/m square (70 micron coating) Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding including cross connectors and all accessories as required for complete installation as instructed by engineer in charge. |
| 155 | Supply and fixing of PVC trapezoidal 1.5m long ducts including the fastening clamps and all accessories as required. |
| 156 | Providing and fixing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. |
| 157 | Providing maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of 3m length , having a diameter of 14.2 mm with copper coating thickness of 250 microns with fault current withstand capability of 13 KA rms value for 1 second and I peak of 31 KA. Universal Clamp (14 25 RTC) made of SS 304 for clamping. Earth enhancing compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances The mineral compound is required to have 25 kg/pit of the total composite. Polypropylene & Polyethylene (UFE)Earth electrode inspection chamber with heavy duty cover should be used to cover the Earth Rod. The dimension shall be 250mmx 250mm with a weight bearing capacity of 50KN. |
| 158 | Supply, installation and testing of 1200mmx1200mmx12mm CI plate electrode earth station conforming to IS:3043-1987 / NEC / IEE complete with brick masonry chamber, CI cover, CI frame, GI watering pipe of 50 mm dia with funnel having 20G GI wire mesh etc. The CI cover frame/ chamber shall be of 1000mm x 500mm x 600mm size. CI manhole cover with frame shall be painted with bitumastic paint, identification of earth pit with yellow paint below the chamber cover, mixtures of charcoal & common salt around electrode including digging of pit up to permanent moisture level but not less than 3 metre depth and back filling. ( value of earth resistance should be less than 1 ohm ) |
| 159 | Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling, including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant. 25 X 3 Cu strips tinned at the joints |
| 160 | Supply and laying the following sizes of earthing bare copper/strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc as required for complete installation as instructed by engineer in charge/consultant.25 X 3 Cu strips tinned at the joints |
| 161 | Copper wire No.10 SWG |
| 162 | Copper wire No.8 SWG |
| 163 | Sintex Box: Supply,installation, testing and commissioning of SMC Junction boxes,shockproof,rustproof,cable entry from bottom or side, dimension(140x140x95). including all accesories as required for complete installation as instructed by engineer in charge. |
| 164 | Supply and fixing of 4 Kg ABC Dry Powder (Stored Pressure) Type Fire Extinguisher. pressurized with dry nitrogen gas at 15 bar. Design, construction and testing as per IS 2171-1999 external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories. |
| 165 | Supply and providing 2/3 mm thick synthetic type and 1 m wide electrical grade chequered type rubber mat to withstand 3.3 kV dielectric strength conforming to IS 5429/1969. |
| 166 | Supply and providing First Aid Box. |
| 167 | Supply and providing laminated First Aid chart duly framed and placed in a conspicuous location for clear vision. |
| 168 | Supply & fixing Laminated drawings of electrical lay out, schematic drawing etc on good frame work. |
| 169 | Supply and providing MS chequered plate of suitable thickness including cutting, welding, painting etc. as required for cable duct covering etc. |
| 170 | Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold or , duly painted over a coat of primer. Cost inclusive of providing 3 Nos of fire bucks and MS stand frame. |
| 171 | Supply of 1 pair 11 KV rubber hand gloves of approved make. |
| 172 | Supply and providing 12 mm thick and 1 m wide electrical grade chequered type rubber mat to withstand 11 kV dielectric strength conforming to IS 5429/1969 |
| 173 | Schedule E -Fire Protection & Life Safety System |
| 174 | Hydrant, Sprinkler System and Plant Room : Providing, fixing, pressure testing and commissioning of Above Ground Pipe Work with Heavy Duty (Class-C) Mild Steel Pipes, confirming to IS: 3589/1239 Part - I - 100mm dia (wherever applicable) and with Butt Welded Fittings, for pipes above 50mm. dia. confirming to IS:1239 Part - II with all accessories such as tees, elbows, reducers, check nuts, unions, flanges, nipples and neoprene gasket, bolts, nuts, washers etc. including cutting, threading, welding, joining, fixing in ducts, on walls, ceiling etc. by using suitable and strong enough supports as per requirement, providing higher sizes of Sleeves / Opening, wherever required, and closing the gap between the pipes and sleeves/openings as per the direction of Engineer - in - Charge /Consultant. The total pipe work shall be protected with approved painting system as per technical specification. |
| 175 | Providing, fixing, pressure testing and commissioning of Underground Fire Protection Pipe Work with Heavy Duty (Class-C) Mild Steel Pipes, confirming to IS: 3589/1239 Part - I - 100mm dia (wherever applicable) and with Heavy Duty Black Ductile Iron Screwed Fittings for Pipes up to 50mm. dia. and Butt Welded Fittings, for pipes above 50mm. dia. confirming to IS:1239 Part - II, such as tees, elbows, reducers, check nuts, unions, flanges, nipples and neoprene gasket, bolts, nuts, washers etc. including cutting, threading, welding, joining, laying in trenches, providing thrust blocks, providing higher sizes of Protective Sleeve / Pipes and RCC encasement, all as per requirement and to the approval of Engineer - in - Charge /Consultant. The total pipe work shall be protected with approved painting systems and bitumen based flexible wrapping, all as per Technical Specifications. |
| 176 | Providing, fixing, testing and commissioning of Forged Ball Valve 25mm dia, PN-16 or above gunmetal /cast alloy, SS handle including necessary accessories and connections. |
| 177 | Providing, fixing, testing and commissioning of Butterfly Valve - 100mm dia, PN-16 or above, slim seal, standard lever operated type confirming to IS: 13095 Mark, with required companion flanges, nuts, bolts etc. complete. |
| 178 | Providing, fixing, testing and commissioning of Non Return Valve - 100mm dia, Wafer Swing Check type, PN-16 or above, Vertical / Horizontal Type , as per final requirement, conforming to IS: 13095 with nuts, bolts etc. complete. |
| 179 | Supply, installation, testing and commissioning of Air Release Valve Gunmetal, conforming to IS 903:1993, having rubber ball with sealing seat and with 25mm. BSP threaded male inlet, including necessary accessories and connections. |
| 180 | Supply, installation, testing and commissioning of following 4\\" dia. Bourdon Type Pressure Gauge, with ISI Mark or of equivalent International Standards.Weather / Water Proof Type Pressure Gauge with shut off cock and connection Pipe. |
| 181 | Supply, installation, testing and commissioning of Manual Swing Type Fire Hose Reel Complete Set with heavy duty drum / reel, 19 mm. dia, 30 Meter long 2-ply polyester yarn braided / rubber braided pressure hose, Red Coloured, heavy duty nylon on/off jet/spray nozzle, 22 mm. isolating valve and all other necessary fixing accessories including Fabrication and Erection of M.S. Support, as per requirement, for Fixing the Fire Hose Reel Set. |
| 182 | Supply, installation, testing and commissioning of Fire Hydrant Valve, bearing to ISI:5290 Type-A mark, Stainless Steel-304 body with 63 mm. oblique instantaneous single outlet, 75 mm. N.B. flanged inlet, Stainless Steel - 304 spindle, complete with PVC blank cap, G.I. chain etc. |
| 183 | Supply, installation, testing and commissioning of Fire Brigade Inlet Breeching, C.I. body, having 3 Way Gunmetal, 63mm. male instantaneous inlet, conforming to IS: 903, with non return valves, 25mm. drain valve, flanged outlet, 3 Nos. of rubber blank caps and G.I. chains. |
| 184 | Supply, installation, testing and commissioning of Fire Hose, RRL hose jacketed with circular woven synthetic fiber. conforming to IS: 636:88, with Working Pressure 14 Kg/Cm2, Proof Pressure 22 Kg / Cm2 and Burst Pressure 38 Kg / Cm2. The Fire Hose shall be with IS: 636 Type-A marking and 63mm. dia., 15 Meter long with pair of 63mm. male and female instantaneous couplings, Stainless steel - 304, having IS: 903 mark and duly S. S. wire wounded. The hose shall be rolled and hung to suitable M. S. support in the Fire Hose Cabinet. |
| 185 | Supply, installation, testing and commissioning of Branch Pipe, Stainless Steel-304, short type, with 63mm. male instantaneous inlet, male threaded outlet, fitted with 16mm. bore nozzle, having IS: 903 mark. |
| 186 | Supply and fix at site in position MS Fire Hose Cabinet made out of 16 gauge MS Sheet, wall / pole mounting type, to accommodate two 15m length of delivery hose and branch pipe, acrylic fronted double door, with lock, 2 keys and a break glass recess for keys, painted Fire Red. The words \\"FIRE HOSE\\" to be painted on the box. The price shall be inclusive of fixing with all accessories and as per requirement. |
| 187 | Providing, fixing, testing and commissioning of Terrace Pump, Horizontal Centrifugal Pump, Electric driven, Capacity: 450 LPM at 56 Mtr. Head, suitable 15 HP with cast iron Impeller, SS Shaft, Mechanical Seal, coupled to High Efficient IE-3 Rated Squirrel Gauge Induction Electric Motor, 3ph, 2900/3000 RPM, TEFC, complete with base Plate. |
| 188 | Providing, fixing, testing and commissioning of control panel for Terrace Pump with all accessories required for complete installation as required. |
| 189 | Supply, installation, testing and commissioning of Pressure Switches with pressure rating suitable for above Fire Pumps, with a differential of 0.2 to 1.6 Bar, as per Technical Specifications. |
| 190 | Supply, installation, testing and commissioning of microprocessor based, Intelligent / Analogue Addressable, true Peer-to-Peer networkable, Fire Alarm Control Panel (FACP) as per the technical specification and to having a Visual LCD Display Unit with touch keypad Battery Back up for 24 hours for normal operation and 1 hours on alarm condition. The control panel, battery charger etc, shall be UL listed approved. The panel shall networked together and capable of networking with other compatible panels and compactible for BMS connectivity (Backnet/Modbus). The Panel shall have sufficient Loop Capacity to accommodate the total devices and detectors as per the final design for this project with 10 % spare capacity in each loop. The panel shall be expandable for future upgradation, all as per Technical Specifications. |
| 191 | Providing, fixing, test and commission Intelligent / Analogue Addressable Multi Sensor Detectors. The detectors shall have multiple sensitivity (adjustable at site) levels, programmable for timed automatic sensitivity selection complete with Standard Base, junction box and other accessories as required. Detectors shall be UL listed. |
| 192 | Providing, fixing test and commission Intelligent / Analogue Addressable Manual Call Station Point (Break Glass Type) with The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. The device shall comply UL Listed. |
| 193 | Providing, fixing, test and commission of Intelligent / Analogue Addressable notification device (Hooter cum Strobe) rated minimum 80 dB @ 3 Mtr. for audible annunciation and minimum 75 Candela flashing at 1Hz for visual indication, complete as per technical specifications. fully supervised and powered from FACP. Hooter and Strobe elements of the combined unit shall have independent activation & deactivation criteria. Suppliers not having single notification device meeting these requirements shall quote for Hooter cum Strobe with supervised control module separately, powered by FACP notification appliance circuit. No external 3rd party power supply shall be permitted. |
| 194 | Supply, installation, testing and commissioning of Intelligent / Analogue Addressable Input / Monitor Module, as per specification for interface with Flow Switches, Fire Pumps, Supervisory Switches, Alarm Valve, Water Tank Level etc. |
| 195 | Supply, installation, testing and commissioning of Intelligent / Analogue Addressable control / Relay Module, as per specification for interface with Lift Panel, Water Curtain Partition, AHUs, Ventilation System, Smoke Management System, Power Distribution, Public Address System etc. |
| 196 | Supply, installation, testing and commissioning of Intelligent / Analogue Addressable Fault Isolator Module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected, all as per technical specifications. |
| 197 | Supplying & laying of 2 Core 1.5 sqmm fire survival armoured cable, Red Colour, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 198 | Supply, & fixing of following Portable Fire Extinguisher as per BIS 2190 and BIS: 15683:2006 and with relevant ISI Stamping/Marking.ABC Dry Powder, Propellant - Dry Nitrogen, Store Pressure Type - 4 Kg. |
| 199 | CO2 - 4.5Kg. |
| 200 | Modular Fire Extinguisher - 5 Kg |
| 201 | Fire Bucket including Fabricated M. S. Stand |
| 202 | Providing and fixing standard fireman axe with heavy rubber handle. |
| 203 | Supply, installation, testing & commissioning of micro process based automatic talk back system with controller of 6 Zone, 500 W amplifier, Goose neck type microphone, complete with floor to floor announcing and talk back facilities with the following features and made functional: (a) Feather type key pads to select the zones. (b) Moulded plastic attractive enclosure. (c) Backlight Liquid Crystal Display (LCD) (d) User friendly interactive display. (e) Announcement selector - PH Switch. (f) Listen selector switch. (g) All Call switch to select all zones simultaneously for announcement (h) Zones Call Display On the LCD With Audio Alarm.Controller Unit with 500 W amplifier, Goose neck type microphone and with the following features: (i) Built in Power supply. (ii) Zone Selector switching Circuit (iii)Terminal blocks to terminate zones wires, amplifier wires etc., (iv) Zone Call processing Circuit etc and made functional. Panel to be installed in the Fire Control Room. |
| 204 | Supply, installation, testing and commissioning of Public Address speaker with talk back facility 6 Watts with L M T and call switch, made out of powder coated CRCA sheet, wall mounting type and to be installed at a height of not less than 150 CM from the finished floor levels, suitable for concealed mounting. |
| 205 | Fire Exit Light - Laser type, with High Glow LED Light, size: 12” x 6” or nearby, Ceiling Mounting type with hanging clamps, on/off switch, Red / Green Colour option, power consumption: 8 Watt or less with all accessories required for complete installation as directed by the engineer in charge. Power supply should be provided with UPS back-up. |
| 206 | Supply and install in position following Sign Boards made out of 3mm thick \\"Opaque\\" PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners with all accessories required for complete installation as directed by the Engineer in charge.Signage Printed \\"IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE\\" of 1.25cm. height letters in red with white back ground. The size of the board shall be 25 x 30 Cm. and shall be fixed at the height of 2Mts. from finished floor near Manual Pull Stations. |
| 207 | Floor Identification Signage ( i.e., GROUND FLOOR, FIRST FLOOR, etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 5 Cm. with contrasting colour from back ground. Size shall be 15cm x 30cm. |
| 208 | Floor Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMP ROOM, FIRE CONTROL ROOM, ELECTRICAL ROOM, FIRE LIFT, PASSENGER LIFT Etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 5 Cm. with contrasting colour from back ground. Size shall be 15cm x 30cm. |
| 209 | Supply and install in position the Signage \\"FIRE ORDER\\" it should contain the matter specified in the technical details on 3mm thick \\"Opaque\\" PVC foam board of computerized cut, PVC non-reflective self adhesive vinyl painted foam board of 2' x 3'. |
| 210 | Fabrication, supply, and installation at site of Heavy Duty Galvanized Mild Steel Puddle Flange, fabricated from heavy-grade M.S. pipe conforming to IS: 1239 (Part 1) or IS: 3589, with PN 20 drilled mild steel flanges as per BS-10 Table specifications, and M.S. plate, all as per tender drawings and approved technical specifications. After complete fabrication, the puddle flange shall be hot-dip galvanized as per IS:4759, and further coated with epoxy to the satisfaction and approval of the Engineer-in-Charge and Consultant.100 mm dia |
| 211 | FIRE SEALANT for all Shafts - Supply and Fixing of load bearing Fire stop mortar system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for openings in floors or slabs after passing service lines. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96 and shall have a VOC content of approx. <1 g/l as per LEED 2009. Firestop installation should be done by trained applicators (HAFSC) and in accordance with manufacturer's guidelines by providing 10mm dia rebars at 200mm c/c both ways with chemical anchoring along the length and breadth of the shaft and provide 2 layers of chicken mesh etc. The mortar shall be applied with a minimum thickness of 65 mm & having load bearing capacity of 200kg/sqm. Proper engineering judgement needs to be submitted through the manufacturer. Complete installation report through Software CFS DM shall also be submitted for inspection purpose. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail