Indian Tenders

Tender Notice

TDR 55847823
Tendering Authority Madhyanchal Vidut Vitran Nigam Limited
Tender No 10(W)/EDCS/2026-27
Tender ID 2026_MVVNL_1154612_2
Tender Brief Corrigendum : Tender For Various Works Related To The Protection System Of 33/11 Kv Power Substation In The Business Plan 2026-2027 Under The Electrical Testing Section Shahjahanpur.
City Shahjahanpur
State Uttar Pradesh
Document Fees INR 3540 /-
EMD INR 30600.0 /-
Tender Value Refer document
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Various Works Related To The Protection System Of 33/11 Kv Power Substation In The Business Plan 2026-2027 Under The Electrical Testing Section Shahjahanpur.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 18-06-2026 TEN Date 22-06-2026
2 15-06-2026 TENDER 10 Date 18-06-2026
3 15-06-2026 TENDER 10 Date 18-06-2026
4 11-06-2026 tender no. 10 Date 15-06-2026
5 11-06-2026 tender no. 10 Date 15-06-2026

Key Dates

Publish Date 18-06-2026
Last Date of Bid Submission 22-06-2026
Tender Opening Date 22-06-2026

Contact Information

Company Name Madhyanchal Vidut Vitran Nigam Limited
Contact Person SE EDC SHAHJAHANPUR
Address KRISHNA NAGAR JAIL ROAD SHAHJAHANPUR

BOQ Items

Name of Work:- विद्युत् परिक्षण खंड शाहजहांपुर के अंतर्गत बिज़नस प्लान २०२६-२०२७ में ३३/११ केवी विद्युत् उपकेन्द्र की प्रोटेक्शन प्रणाली से सम्बंधित विभिन्न कार्य
Sl. No. Item Description
1Loading, Safe carriage & unloading of following stock material from any stores centres under MVVNL, depending upon the availability of material at Stores Centres, with loading & unloading at both ends respectively etc.
233 KV Control pannel for SINGLE Transformer
333 KV Control pannel for double Transformer
433 KV CT 400/200/1-1A
533 KV CT 200/100/1-1A
6Battery charger 24V
7Battery set (12Nos*2V) 24V
833KV Fuse Set
9Supply of following Material by the contractor
10Structure for 33 KV Fuse set as per specification (06 No.)i) M.S. Channel (125x65x6)mm 3.5Mtr long for Vertical Structure.
11ii) M.S. Angle (75x75x6)mm 2.6Mtr long for Horizental Structure.
12Providing of (2x2.5)sq.mm control cables (Armoured)
13Providing of (4x2.5)sq.mm control cables (Armoured)
14Erection of following Material & Miscellaneous Electrical Works.As Per Direction of AE / JE /Incharge Including the cost of labour ,T&P and complete work of instalation material carriage etc. required for proper completion of work .
15Fuse Set structure:-Febrication & Erection of Fuse Set structure and Plinth for the same as per drawing No. RES-39 details:-Excavation of earth (0.30x0.30x1.0)m for 12 Nos. Pits of above structures.
16Fabrication of Fuse Set structure by using M.S. Channel (125x65x6) mm size and 3.5 m minimum height with 2 Nos. M.S. Angle (75x75x6)mm size on top of structure for installation of Fuse Set.
17C.C. work in ratio of 1:3:6 (cement, fine sand and brick ballast) of size (0.30×0.30×0.15)m for 12 Nos. pits for making bed for each structure. Work including proper ramming etc & C.C. work of ratio 1:3:6 (cement, coarse sand and 25 mm size stone grit) for the above plinths for structure of Fuse Set 12 Nos. after ramming of earth of size (0.3x0.3x1.5)m. Over stone pad.
1812mm thick plaster with cement mortar ratio 1:4 (cement & fine sand) of plinth of 0.4m upper side.
19Providing & Laying of G.I.Earth strip of size 50x6mm for connecting the Earth Mat with steel structure. The work also includes cutting, bending, straight-tening, over-lapping and welding the Earth Strip with Earth Mat and various steel structures by using high quality Arc welding in already digged trenches.
20Painting of G.I.Earth Strip of size (50x6) mm with one coat of ready mixed primer with two coats of ISI mark synthetic channel green paint.
21Construction of Control cable trench (300Mtr) as per details (All Material supply by the Contractor).
22Excavation of earth in size 0.650x0.40m.
23C.C. work in foundation in ratio 1:3:6 (cement, sand & brick ballast) with proper ramming in size 0.65x0.15 mtr.) & First Class Brick work in cement mortar in ratio 1:4 in size 0.23x0.32 Mtr. Along with 25mm thick C.C. in floor of Cable Trench in ratio 1:2:4 (cement, coarse sand and stone ballast) 20mm gauge in size 0.3 mtr. Width.
24Providing & Grouting of G.I.. Strip of size 450x25x6mm in cable trench 100mm above floor level and at equal space distance 300mm.
25Providing & Grouting of G.I.. Angle Iron of size 50x50x6mm in upper edge of trench.
26Plastering of Trench in Cement, Mortar in ratio 1:4, 12mm thick in cable trench.
27Providing & Fabrication and fixing cable trench cover of M.S.Angle size 50x50x6mm of size 0.3m wide 0.5 to 1.0 mtr. Length with proper welding of 8 mm size of bar 2 Nos. in length and 6 Nos. in width including cost of CC casting & RCC in Ratio 1:2:4 (cement, coarse sand and stone ballast) (i) 0.5 Mtr. Long 10 Nos. & 1.0Mtr long 55 Nos per job
28Supply of M.S.Angle 50x50x6mm for trench cover.
29Painting of StructuresPainting of the following structure with one coat of ready mixed primer and two coats of ISI Mark Aluminium paint after rubbing with sand paper to the surface of the structure including labour and T&P complete in all respect.(i) fuse set structure
30Installation of 24V Battery and Battery Charger:Assembling and installation of the cabinet of 24V battery and battery charger in switch gear control room including grouting of foundation bolts as per drawing of manufacture, including providing the foundation nuts and bolts of proper size. The electrical connection between battery and battery charge with flexible copper lead of size 7/20 SWG shall be done properly. The work includes installation, wiring upto control panel, testing and commissioning complete in all respect.
31Laying of different size of (2x2.5)mm2control cables (Armoured) i.e. from Buchholz realy to Marshalling box Marshalling box to indication protection board in switch gear room, 33 KV CT’s to CT’s Junction Box, 33 KV CT, 33 KV PT, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box and indication board as per required for installed equipment. Providing & laying of Control cable with in cable tray from VCB & CT Connection.
32Laying of different size of (4x2.5)mm2 control cables (Armoured) i.e. from Buchholz realy to Marshalling box Marshalling box to indication protection board in switch gear room, 33 KV CT’s to CT’s Junction Box, 33 KV CT, 33 KV PT, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box and indication board as per required for installed equipment. Providing & laying of Control cable with in cable tray from VCB & CT Connection.
33Installation of 33 KV Fuse Set:Assembling and installation of fuse set on the fuse set structure. The work includes fabrication for proper fixing, if required.
34Installation of 33 KV VCB Control Panel for single feeder & Double T/F Control Panel.Carefully and safely shifting of 33 KV VCB control panel from outside of the switch gear room to inside of the switch gear room, grouting with anchor bolts in the floor, work also includes cutting & proper finishing of floor if necessary for completion of work. Placing and fixing of panel on foundation, bolts of proper size in proper position and alignment.
35Installation of 33 KV C.T.’s:Installation of C.T.on the C.T’s structure. The work includes fabrication for proper fixing, and also clamps for C.T Connection if required to complete the work.
36SUPPLY & ERECTION BY THE CONTRACTOR
37To provide required No. of technicians to work on power T/f, 33 KV C&R panels /11 KV VCB panels during commissioning & energization, including testing and commissioning activities with experinced tachnical man power as per departmental requirments
38Replacement of defective WTI including removel of existing faulty WTI and providing fixing testing and commissioning of new WTI complete in all respect as per relevent IS/IEC standards and departmental specifications
39replacement of defective OTI including removel of existing faulty OTI and providing fixing testing and commissioning of new OTI complete in all respect as per relevent IS/IEC standards and departmental specifications
40Providing and fixing of OC+EF IDMT Relay with retrofitting arrangement for 33KV C&R Pannel Make Ashida
41Providing and fixing of OC+EF IDMT Relay with retrofitting arrangement for 11KV VCB Pannel make Ashida
42Providing and fixing of Auxallary Relay with retrofitting arrangement for 33KV C&R Pannel Make Ashida
43Providing and fixing of Master Relay with retrofitting arrangement for 33KV C&R Pannel AND 11 KV VCB PANNEL
44Providing and fixing of Anti pumping relay
45Earthing of 33 KV C&R panel by laying and providing G.I. Earth strip (50*6) mm including cutting and welding Please Enable Macros to View BoQ information

Other Detail

Information Source https://etender.up.nic.in
Download FileName File Description File Size
Download BOQ_2168925.xls Tender Documents 0 KB
Download d5eb5f9b-0d71-42eb-8dc9-048090d1d7b3.html Tender Documents 0 KB
Download TENDERFORM_10_2026-2027.pdf Tender Documents 0 KB
Download Tendernotice_1 (19).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.