| 1 | Excavating in trenches n. exc 1.5m wide and not e. 1.5m in depth for foundation of poles, laying UG cables, etc and getting out in soft/loose soil, complete all as specified and as directed. |
| 2 | Removing excavated material not exc. 50 m and depositing where directed at a level not exc 1.5 m above the starting point in soft / loose soil, complete all as specified and as directed. |
| 3 | Returning filling including spreading levelling, watering and well ramming in layers not exceeding 25cm in soft/loose soil, complete all as specified and as directed. |
| 4 | M&L for clean dry (tibba) sand cushioning to U/G cable and punning for cushioning of cable 8cm below the cable and 15cm above cable, complete all as specified and as directed.Note :- Thickness after punning shall not be less then 18 cm. Punned thickness shall only be museared and paid. |
| 5 | Supply and lay common burnt bricks of sub class B old size laid at right angle on the cable complete in trenches for cable protection, complete all as specified and as directed. |
| 6 | M&L for galvanised steel tube 50mm bore (light grade) laying in road/drain crossing for cable protection pipe, complete all as specified and as directed. |
| 7 | Supply and laying in repair XLPE insulated, armoured, heavy duty electric UG cables with aluminium conductor 1100 volts grade complete including porviding lugs as required as specified and directed for cross-sectional area 10 sqmm 2 core, complete all as specified and as directed. |
| 8 | All as per item No 7 here in before but of size 6 Sqmm, 2 core, complete all as specified and as directed. |
| 9 | All as per item No 7 here in before but of size 10 Sqmm, 4 core, complete all as specified and as directed. |
| 10 | All as per item No 7 here in before but of size 16 Sqmm, 2 core, complete all as specified and as directed. |
| 11 | All as per item No 7 here in before but of size 16 Sqmm, 4 core, complete all as specified and as directed. |
| 12 | All as per item No 7 here in before but of size 25 Sqmm, 3 1/2 core, complete all as specified and as directed. |
| 13 | All as per item No 7 here in before but of size 35 Sqmm, 3 1/2 core, complete all as specified and as directed. |
| 14 | All as per item No 7 here in before but of size 50 sqmm, 3 1/2 core, complete all as specified and as directed. |
| 15 | All as per item No 7 here in before but of size 70 sqmm, 3 1/2 core, complete all as specified and as directed. |
| 16 | All as per item No 7 here in before but of size 95 sqmm, 3 1/2 core, complete all as specified and as directed. |
| 17 | All as per item No 7 here in before but of size 120 sqmm, 3 1/2 core, complete all as specified and as directed. |
| 18 | All as per item No 7 here in before but of size 150 sqmm, 3 1/2 core, complete all as specified and as directed. |
| 19 | All as per item No 7 here in before but of size 185 sqmm, 3 1/2 core, complete all as specified and as directed. |
| 20 | Dismantling cross arms of MS channel or angle sections etc. and keeping serviceable materials in safe custody for re-use and/or unserviceable materials removing from the site, complete all as specified and as directed. |
| 21 | Fixing only serviceable cross arm, MS Channel, angle section obtained from item No 28 here-in-before after painting with one coat of aluminium paint including preparation of old steel surfaces, complete all as specified and as directed. |
| 22 | M&L in repair Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections, including nuts, bots, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat (red oxide, zine chrome primer), one under coat and one finishing coat of aluminium paint including preparation of surfaces, complete all as specified and as directed. |
| 23 | Dismantling of ACSR conductors or disturbed span including line spacer and keeping serviceable materials in safe custody for re-use and unserviceable materials removing from the site, complete all as specified and as directed. |
| 24 | Fixing only by re-straining, tightening of ACSR conductors of any size/type on LT poles including necessary new aluminium binding wire for fixing with insulator/PVC sleeves for jumper etc as required complete all as specified and as directed.(Note : Serviceable ACSR conductors shall be obtained from item No. 23 here-in-before). |
| 25 | M&L in repair for aluminium conductor steel reinforced (ACSR) on LT poles including straining, binding with insulators with aluminium binding wire with insulator as in OH conductor, providing PVC sleeves for jumpers, complete all as specified and as directed. |
| 26 | Dismantling insulators of any type and any size and keeping serviceable materials in safe custody for re-use and removing unserviceable materials from the site, complete all as specified and as directed. |
| 27 | S&F in repair pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade, complete all as specified and as directed. |
| 28 | S&F in repair shackle type, porcelain, vitreous white, brown or green insulator including galvanised mild steel straps of size 31 x 3 mm, 12 mm dia insulator bolts, nuts and washers for working pressure 1100 volts of size 75 mm height, 90 mm dia , complete all as specified and as directed. |
| 29 | S&F in repair PVC fibre separator for LT line 1100 volt OH conductor 3/4 wire system for maintaining horizontal spacing of conductor complete with nut & bolt minimum two nos in a span, complete all as specified and as directed. |
| 30 | M & L in repair earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick, burried directly in ground (earth pit not less then 2.25m deep bellow ground level) with top edge of the plate not less then 1.5m deep below normal ground level connected to galvanised iron strip of 32 x 6mm earth lead by means of bolt, nuts, washers of galvanised steel earth strip protected by and including GI pipe 40mm dia bore (light grade) and conncted to main test point as directed and including concrete pit in PCC(1:3:6)type C-1 precast RCC(1:1.5:3) type A-1 cover slab 54 x 5 cm reinforced with 4mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8mm dia TMT bar embedded in precast cover slab funnel wire mens 20mm bore GI pipe (medium grade) for watering charcoal and salt in altemate layers, including necessary excavation and earth work in any type of soil complete all as shown on electrical plate No3 of SSR part-I, complete all as specified and as directed. |
| 31 | M & L in repair earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick buried directly in ground preferably vertically in ground with top edge not less than 1.25 mtr deep below normal ground level connected with and including galvanised iron wire 4 mm dia as earthing lead by means of nuts bolts and washers of galvanized iron protected by 15mm dia (medium grade) GI tubing, funnel, wire mesh, 20mm bore GI tubing (light grade) watering pipe , including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:2:4) type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia TMT bars @ 15cm c/c in both ways and 10mm dia MS handle (01 No) of suitable size, charcoal and salt in alternate layers necessary excavation and earth work in soft/loose soil all as shown in Electric plate No. 3 of SSR part-I and testing on completion complete all as specified and as directed. |
| 32 | Supply,install, commission and testing in repair cubical type LT panel board ,outdoor canopy type, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof,front and rear operated door with necessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheet of 3.00 mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity copper bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles glands complete all as specified and directed with the following accessories :- INCOMING(a) MCCB 4 pole, 415 Volts, 250 Amps, 25 KA - 01 No.OUTGOING(a) MCCB 4 pole, 415 Volts, 125 Amps,16 KA -01 No. (b) MCCB 4 pole, 415 Volts, 100 Amps,16 KA -02 Nos (c) MCCB 4 pole, 415 Volts, 100 Amps,10 KA -01 Nos (Spare) (d) MCB TPN , 415 Volts, 32 Amps, -01 Nos (e) Digital VAF meter for basic electric system monitoring-01 Nos.(f) Indicator lamp (RYB) (set of three) - 01 Set |
| 33 | S&F in repair TPN copper bus bar box, outdoor type of 200 A capacity mounted on porcelain bridge insulator for one incoming cable and 4 out going cable, housing in sheet metal enclosure of MS sheet 3.0 mm thick CRCA sheet and angle iron 40x40x6 mm frame, painted with two coats including arrangement for cable gland for incoming and outgoing cables, locking arrangement, suitable foundation/platform for mounting the FPB with space for and including the following switch gears: (a) MCCB 100 AMP, 10 KA (for incoming control) |
| 34 | Preparation of old painted surface above the planting depth and PCC coping of steel tubular LT pole of 09.00 metre length including MS clamps ,cable protection pipe bracket fitted with street light fittings etc by scraping with steel wire brush and applying two coats, of aluminium paint to external surface of poles MS cross arms MS clamp, cable protection pipe etc to give even shade including Zebra colour of painting from 1.5 mtr height from the top of coping/ bottom of pole as per site condition and numbering of poles complete all as specified and as directed by Engr-in –charge Note: Zebra colour will be applied by synthetic enamel paint of black/yellow colour as approved in alternate layer of 30 cm height of each layer. |
| 35 | Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25-50 Sqmm, complete all as specified and as directed. |
| 36 | Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70-150 Sqmm, complete all as specified and as directed. |
| 37 | Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25-50 Sqmm , complete all as specified and as directed. |
| 38 | Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70-150 Sqmm, complete all as specified and as directed. |
| 39 | S & F in repair Indicator lamp, LED type of colour red, blue and yellow including taking down existing old/unserviceable lamps from LT panel /APFC Panel board after carefully disconnecting the electric connection, complete all as specified and as directed. |
| 40 | S&F in repair MCCB, 415 volts, 400 Amp, breaking capacity 36 KA, 4 pole including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection, complete all as specified and as directed. |
| 41 | S&F in repair MCCB, 415 volts, 250 Amp, breaking capacity 25 KA, 4 pole,including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection, complete all as specified and as directed. |
| 42 | S&F in repair MCCB, 415 volts, 200 Amp, breaking capacity 25 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and as directed |
| 43 | S&F in repair MCCB, 415 volts, 160 Amp, breaking capacity 16 KA, 4 pole including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and as directed |
| 44 | S&F in repair MCCB, 125 Amp, 415 volts, breaking capacity 16 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection, complete all as specified and as directed. |
| 45 | S&F in repair MCCB, 100 Amp, 415 volts, breaking capacity 10 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection, complete all as specified and as directed. |
| 46 | Note:- Schedule of credit Rs 95,150.00 will be deducted from total amount quoted while accepting the bid. Details of schedule of credit is given in tender documents. Please Enable Macros to View BoQ information |