Indian Tenders

Tender Notice

TDR 55756596
Tendering Authority Post Graduate Institute Of Medical Education And Research
Tender No PGI/Engg/RAC/2026/314
Tender ID 2026_PGIME_910982_1
Tender Brief Corrigendum : Tender For Replacement Of 4 Nos. Existing Ahus With New Ahus Having Combination Of Chilled Water & Dx Type Coil For O.Ts At Advanced Eye Care Centre, Pgimer, Chandigarh.
City Chandigarh
State Chandigarh
Document Fees Refer document
EMD INR 129300.0 /-
Tender Value INR 64.69 Lakhs /-
Tender Type Tender
Bidding Type Open Tender
Competition Type Indian

Tender Details

Tender for Replacement Of 4 Nos. Existing Ahus With New Ahus Having Combination Of Chilled Water & Dx Type Coil For O.Ts At Advanced Eye Care Centre, Pgimer, Chandigarh.

Corrigendum Details

Sr No CorrigendumDate Corrigendum CorrigendumType NewSubmissionDate
1 11-06-2026 date extend Date 18-06-2026

Key Dates

Publish Date 11-06-2026
Last Date of Bid Submission 18-06-2026
Tender Opening Date 19-06-2026

Contact Information

Company Name Post Graduate Institute Of Medical Education And Research
Contact Person HE RAC
Address room no 225 department of hospital Engineering and planning RAC division

BOQ Items

Name of Work:- Replacement of 4 nos. existing AHUs with new AHUs having combination of chilled water & DX type coil for O.Ts at Advanced Eye Care Centre, PGIMER, Chandigarh.
Sl. No. Item Description
1Supply, Installation ,Testing and commissioning of sheet metal sectionalized construction double skin AHU , complete with chilled water coils of copper tube and aluminum fins construction , squirrel cage induction motor , DIDW BACKWARD CURVE centrifugal fan , V-belt drive package (including taper lock pulley arrangement) and vibration isolation (spring mounted). The AHU shall have 25 mm thick panels made out of 0.8 mm thick external Galvanized steel sheet (scratch free plastisol coating) and internal Aluminum sheets of thickness 0.8 mm, with PUF injection inside and static pressure of AHU is 135 mm with HEPA filter. Cooling coil section with 6 rows deep chilled water coil (3 + 3 combination), Heating coil 2 row deep, Cooling coil DX type 3 row deep and gap between all the coils minimum 450 mm and coil tube thickness 0.5 mm.PUF (40 kG/CuM density) injection would be done in a controlled factory environment, by using a PUF injection molding machine. The blower shall be of approved make and specifications, AMCA certified-210 and AMCA 300. Entire unit vibration level as per ISO 2372/3945. The AHU assembly shall be complete with electrically inter-locked fan guard, access doors with nylon hinges, nylon door locks handles, port holes in fan section, sealed screw end caps , internal light and limit switches , SS drain pan & Discharge of AHU etc. Floor mounted AHU motor shall be three phase motor suitable for VFD drive. Motor shall be IE-3. AHU will be compatible with BMS system
25000 CFM
36200 CFM
4Supply, Installation ,Testing and commissioning of sheet metal sectionalized construction double skin AHU , complete with chilled water coils of copper tube and aluminum fins construction , squirrel cage induction motor , DIDW BACKWARD CURVE centrifugal fan , V-belt drive package (including taper lock pulley arrangement) and vibration isolation (spring mounted). The AHU shall have 25 mm thick panels made out of 0.8 mm thick external (scratch free plastisol coating) and internal GSS pre-painted sheets of thickness 0.8mm, with PUF injection inside and static pressure of AHU is 65 mm with Micro filter. Cooling coil section with 6 rows deep chilled water coil (3 + 3 combination), gap between the coils minimum 450 mm and coil tube thickness 0.5 mm.PUF (40 kG/CuM density) injection would be done in a controlled factory environment, by using a PUF injection moulding machine. The blower shall be of approved make and specifications, AMCA certified-210 and AMCA 300. Entire unit vibration level as per ISO 2372/3945. The AHU assembly shall be complete with electrically inter-locked fan guard, access doors with nylon hinges, nylon door locks handles, port holes in fan section, sealed screw end caps , internal light and limit switches , SS drain pan & Discharge of AHU etc. Floor mounted AHU motor shall be three phase motor suitable for VFD drive. Motor shall be IE-3. AHU will be compatible with BMS system
510000 CFM
6Supply, Installation, Testing & commissioning of Outdoor units with twin compressors, statically dynamically balanced centrifugal blower, multi rows cooling coil internally grooved copper tube with Aluminum fins, Inbuilt safety devices for compressor protection like thermal protector, Internal pressure, cutout enclosure shall be equipped with synthetic filter with following capacity.
716.5 TR Outdoor Condensing unit. (2 Compressor) (Refrigerant - R 410/407)
811 TR Outdoor Condensing unit (2 Compressor) (Refrigerant - R 410/407)
9Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for HVAC system, complete with fittings ,with suitable adjustable ring type hanger supports, jointing / brazing including accessories, insulated with XPLE Class-O tubular insulation with Class-O closed cell elastomeric nitrile rubber tubular sleeves section so specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
1028.58mmdia(OD)(Harddrawn)with tube thickness 1.2mm with 19mm thick insulation
1122.2mmdia(OD)(Harddrawn)with tube thickness1.2mm with19mm thick insulation
1215.86 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
1312.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
14AHU Kit
15AHU Kit for connectivity of Outdoor unit with AHU (Including Y joints)
16INSULATED CHILLED WATER PIPING (Expanded Polystrene Insulation)
17Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with fire retardant quality expanded polystyrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessian and finally applying vapor barrier with glass cloth and star bond . as per specifications and as required complete in all respect.
18Note:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
1980mm dia. (50mm insulation)
2065mm dia. (50mm insulation)
2150mm dia. (50mm insulation)
2240mm dia. (50mm insulation)
2332mm dia. (50mm insulation)
2425mm dia. (50mm insulation)
25INSULATED VALVES
26Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications
27BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified
28150 mm
2980 mm
3065 mm
3150 mm
3240 mm
33SITC of bronze ball valve
3425 mm
35NON -RETURN VALVE with duel plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled /hot water circulation including insulation as specified.
36150 mm Dia
37Y -Strainer
38Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
3965 mm
4050 mm
4140 mm
42Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.
43BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O-ring & PN 16 pressure rating as specified.
44200 mm Dia
45SITC of Non-return valve with dual plate pf CI body SS plate vulvanized NBR seal flanged end PN 16 pressure rating as peer specification.
46200mm Dia
47Supply, installation, testing and commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable accepting upto 10 V DC and upto 20 m A elctric signal and shall provide similar transduced feedback output to control system (including thermostste) . Maximum close off pressure shall not be less than 5 Bar for upto 50 mm valve and 7 Bar for 65 mm & above. Valves should have pressure rating of 24 Bar minimum.
4865 mm
4950 mm
5032 mm
51Drain Pipe
52Providing and fixing G.I. drain pipes complete with G.I. fittings including insulation on it
5325 mm dia nominal bore
54Supply, installation, balancing and commissioning of fabricated at site Aluminium sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
5518 GAUGE (1.25 mm)
5620 GAUGE (1.00 mm)
5722 GUAGE (0.80 mm)
58Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
5920 GUAGE (1.00 mm)
6022 GUAGE (0.80 mm)
6124 GUAGE (0.63 mm)
62Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
6319 mm
64P/F Flexible double canvas connection between indoor units and supply air duct.
65SITC of duly painted MS stand.
66Supply installation testing and commisioning of GI volume control damper complete with neoprene rubber gaskets,nuts,bolts,screw linkages,flanges etc as per specifactions.
67Supplying & Fixing of powder coated extruded aluminium Suplly Air grills with aluminium volume control damper as per specifications.
68Supply fixing of powder coated extruded aluminium return Air grills with louvers but without volume control Damper complete as required.
69Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control Dampers with anti smudge ring & removable core.
70Supply, fixing testing commissioning of return air diffusers of powder coated aluminium without volume control Dampers anti smudge ring & removable core.
71Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
72Fire damper
73Actuator
74SITC of Inline fan of the following capacity of approved make & specification including canvass connection.
752500 CFM with 35 mm static
763000 CFM with 35 mm static
774000 CFM with 35 mm static
78Supply Erection, Testing and Commissioning of Electrical Panel Cubical Type, dust and vermin proof ingress protection, IP-42 wall/floor Mounted Switchboard with Hinged Lockable Doors fabricated out of 14 SWG CRCA Sheet with Powder Coating through 7 tank process with all accessories live parts shrouded and busbars insulated with heat shrinkable sleeves including solid / flexible connections, earthing etc., having 3mm thickness Gland Plate. Power and control cable wiring will be (ISI 1100V) flame retardent low smoke, PVC core copper wire, copper luggs, PVC sleeveferrules etc.LT Panel should have withstand fault levet of equal to 50 KA for 1 second. Electrical standard complying and RAL 7032. Fittted with gaskets, Lifting Hooks, Cable Entry as per requirement,Panel designed comprising of the following:-
7932 A. TP MCB 10 KA C CURVE 1 No.
8025 A. TP POWER CONTACTOR 1 No.
81ADD ON BLOCK 2 NO+2 NC 1 No.
829-15 THERMAL OVERLOAD RELAY 1 No.
83Singal pahse preventor relay 1 No.
84Start stop push button 2 Nos.
85R, Y phase indicating lamp 240 V AC 2 Nos.
86B phase indicating lamp 240 V AC 1 No.
87ON OFF indicating lamp 240 V AC 2 Nos.
886 A SP control MCB C curve type 4 Nos.
89A/M selector switch 1 No.
90PLA Relay 2 Nos.
91Neutral Link 1 No.
9232 A. TP MCB 10 KA C CURVE 1 No.
9325 A. TP POWER CONTACTOR 1 No.
94ADD ON BLOCK 2 NO+2 NC 1 No.
956-10 A THERMAL OVERLOAD RELAY 1 No.
96Singal pahse preventor relay 1 No.
97Start stop push button 2 Nos.
98R, Y phase indicating lamp 240 V AC 2 Nos.
99B phase indicating lamp 240 V AC 1 No.
100ON OFF indicating lamp 240 V AC 2 Nos.
1016 A SP control MCB C curve type 4 Nos.
102A/M selector switch 1 No.
103PLA Relay 2 Nos.
104Neutral Link 1 No.
10563 A 4P MCB 10 KA C CURVE TYPE 1 No.
10663 A 4P RCBO 300 MA 1 No.
107R, Y phase indicating lamp 240 V AC 2 Nos.
108B phase indicating lamp 240 V AC 1 No.
109ON OFF indicating lamp 240 V AC 2 Nos.
1106 A SP control MCB C curve type 3 Nos.
111Neutral Link 1 No.
11240 A 4P MCB 10 KA C CURVE TYPE 1 No.
11340 A 4P RCBO 300 MA 1 No.
114R, Y phase indicating lamp 240 V AC 2 Nos.
115B phase indicating lamp 240 V AC 1 No.
116ON OFF indicating lamp 240 V AC 2 Nos.
1176 A SP control MCB C curve type 3 Nos.
118Neutral Link 1 No.
119SITC of armoured copper conductor PVC sheathed, XLPE insulated cable of size 4C x 16 sqmm. on surface/wall/ on cable tray etc complete as per requirement.
120SITC of armoured copper conductor PVC sheathed, XLPE insulated cable of size 4C x 10 sqmm. on surface/wall/ on cable tray etc complete as per requirement.
121SITC of armoured copper conductor PVC sheathed, XLPE insulated cable of size 4C x 6 sqmm. on surface/wall/ on cable tray etc complete as per requirement.
122SITC of armored copper conductor PVC sheathed, XLPE insulated cable of size 3C x 2.5 sqmm. on surface/wall/ on cable tray etc complete as per requirement.
123Supplying and laying 25 mm x 5 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm.)
124Supplying and laying 6 SWG wire at 0.50 metre below ground level for conductor earth electrode, including connection / termination with G.I. thimble etc. as required.
125Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
126600 mm width x 50mm depth x 1.6 mm thickness.
127450 mm width x 50mm depth x 1.6 mm thickness.
128300 mm width x 50mm depth x 1.6 mm thickness.
129150 mm width x 50mm depth x 1.6 mm thickness.
130Minor civil work (including dismantling/cutting of gypsm board, wall, foundation of AHU's, etc for HVAC work and same make good at various location)
131SITC of FN 100 TNP for hot water generator make L&T as per site installation
132Dismantling of existing 4 No. AHU's, butterfly valve, NRV, etc from various location and removing & dumping of scrap and cleaning of site after the completion of work
133Additional GST @ 06.33% as per latest norms
134Buy Back cost of AHU's, ducting, cable, piping etc
135NOTE:1.This is a percentage rate tender, therefore ,percentage is only to be quoted by the agency in figures on the amount mentioned in schedule of quantity.2.The percentage quoted should be inclusive of all taxes including GST etc and nothing extra shall be payable on this account. Please Enable Macros to View BoQ information

Other Detail

Information Source https://eprocure.gov.in/eprocure/app
Download FileName File Description File Size
Download ac221c1e-31b5-44ad-a907-a59aea60f6e3.html Tender Documents 0 KB
Download BOQ_957410.xls Tender Documents 0 KB
Download Tendernotice_1 (2).pdf Tender Documents 0 KB
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.