| 1 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. DSR Electrical 2018/ I. No. 12.42 |
| 2 | Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000mm, outer Dia 50 mm inner Dia 25 mm, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing lead of 25mm x 3mm G.I. strip, upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. PS 725 (B) |
| 3 | Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respects. PS No. 716 |
| 4 | Repairing of 11KV Fuse wire/Jumper i/c supply & fixing of required size conductor, fuse wires of 11KV Line/DP Structure of Transformer by taking shutdown from UPPCL Department with all safety instruments like-safety belt, Gloves, Shoes and other necessary items. (AOR) |
| 5 | Supply & erection of overhead line with ACSR conductor on poles / service bracket including binding etc. complete in all respects.PS NO 627 |
| 6 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. DSR Electrical 2018/ I.No. 12.34 |
| 7 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PS No. 501 16 sqmm x 4 core |
| 8 | 25 sqmm x 2 core (AOR) |
| 9 | 16 sqmm x 2 core |
| 10 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making onnection etc. complete in all respect as per direction of the Engineer-Incharge. PS No. 504a) 16 sqmm |
| 11 | b) 25 sqmm |
| 12 | c) 35 sqmm |
| 13 | S/F of 11 KV Disc insulator 70 KN and fitting B&S heavy duty with clamp of cross arm fixed on HT Pole BHEL/Jai Shree/WS/RR/Make UPERC P-43 |
| 14 | S/F of 11 KV pin 12\\" long with insulator of Jai Shree/HBHEL on cross arm fixed on HT pole including all T/P etc UPERC P-39 Annexure-16 |
| 15 | Supply of 11KV Pin Isulator as per UPERC 2019/I. No. 6 page 40 |
| 16 | S/f of 11 KV TPMO relco/Rama make 9 nos insulator of Jai shree/BHEL make complete in all respects. UPERC P No 48 I No. 13 |
| 17 | S/F of 11 kv, 100 Amp, Drop Fuse set Channel type (3 nos) (AOR) |
| 18 | Repair of 63/100 KVA Transformer incl. changing of HV & LV Coil, Bushing, Gasket & Fresh Transformer oil without returning of old & unservicable material. Complete in all respect as per direction of E/I. (AOR) |
| 19 | Dis/Re-fixing of 63/100 kva transformer with connection loading & unloading, cartage charge from site to repairing at worshop complete in all respects as per direction of E/I (AOR) |
| 20 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. PS. No. 807 f (ii) 40 A TPN |
| 21 | Supply of PCC Pole 8.5 Mtrs as per UPERC-2019/I. No. 1 page 48 |
| 22 | Erection of RCC/PCC Pole of following length in Brick ballast and ramming the foundation, finishing with 150mm thick cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) layer on top with including excavation and refilling etc. as required. E/I DSR Electrical-2018. 11.1.3 |
| 23 | Supply of Clamp with nut and bolt as per UPERC 2019/I. No. 21 page 24 |
| 24 | S/F of 1100 Voltage grade aerial bunched cable, Power cable: Standard compacted circular aluminium conductor, XLPE insulator Messenger conductor, standard compacted circular all aluminium alloy bare conductor, 3 power core laid around messenger conductor 1cX16 sqmm lighting core aluminium conductor and XLPE insulated of size 3 core x120 sqmm + 1Cx95 sqmm + 1cx16sqmm. Complete in all recpects as per direction of E/I. (AOR) |
| 25 | Supply and fixing of XLPE insulated Al. unarmoured cable for working voltage for energizing the distribution boxes & street light size 1x16sqmm complete in all respects as per direction of E/I. (AOR) |
| 26 | Supply and fixing of XLPE insulated Al. unarmoured cable for working voltage for energizing the distribution boxes & street light size 1x35sqmm complete in all respects as per direction of E/I. (AOR) |
| 27 | Dismantling of PCC pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. DSR Electrical 2018/ I. No. 12.42 |
| 28 | Supply and Fixing of 10-12 Mtr Lone Octagonal pole door cover hot dip galvanished & proper locking arrangement. Complete in all respect as per direction of E/I. (AOR) |
| 29 | Supply & erection of \\"D\\" clamps of 50 mm x 6mm flat iron on steel tubular poles / steel rail poles with bolts, nuts etc. complete in all respects including painting with aluminium paint PS No. 623 |
| 30 | Supply & fixing of 75 mm x 90 mm shackle insulator /100 mm x 65 mm pin insulator including G.I. Bolts / spindle nuts etc. complete in all respect. . P.S. No.620 |
| 31 | Supply & erection of overhead line with ACSR conductor on poles / service bracket including binding etc. complete in all respects P.S. No. 627 |
| 32 | Supply of Sheet Moulded Compound and Thermoplatic LT Distribution box of size 450x350x200mm, for 3 Phase Out door connection to LT Line consumers through overhead ABC Line, Shockproof, rust proof, termite proof, vermin proof, self extinguished, Complete with provision of 3 phase aluminium bus bars of EC grade of size 25x6x300mm long and neutral bus bar of size 40x6x300mm. It will be with coloured sleeves on each busbar, the same will be with facility of cable termination having i incoming and 4 outgoing with 4 polymeric glands of 25mm dia and 6 Nos rubber gurmuts on each side. (AOR) |
| 33 | Demolishing Cement Concrete manually by mechanical means including disposal of material within 50 mtr lead as per direction of Engineer-in-Charge, Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) DSR Civil 15.2.1 (AOR) |
| 34 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate moorum screening, red bajri and labour required. i) bituminious portion (AOR) |
| 35 | ii) water bound macadam (AOR) |
| 36 | Cement Concrete with 2 cm gauge approved stone ballast, coarse sand & cement in the proportion of 4:2:1 including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. (SOR, UPLNV, I.No. 5.07/S.N. 279 |
| 37 | Cement Concrete with 4cm gauge approved stone ballast, coarse sand & cement in the proportion of 8:4:1 including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. (SOR, UPLNV, I.No. 5.08/S.N. 281 |
| 38 | Taking out existing c.c. interlocking paver blocks from foothpath/central verge, including removal of rubbish etc. disposal of unserviceable material to the dumping ground, for which payment shall be made seperately and stacking off serviceable material withing 50 mtr lead as per direction of E/I (AOR) |
| 39 | Laying Old cemennt concrete interlocking paver blocks of any design/shape laid in required line, level currative colour and pattern over and including 50mm thick compacted bed of course sand filling the joint with fine sand etc. all complete as per direction of E/I (Old CC Paver block shall be supplied by the deptt free of cost) (AOR) Please Enable Macros to View BoQ information |