Tender Brief Tender For Establishment Of Electrical Installation Work For Fire Pump & X-Ray Machine At Tufanganj Sd Hospital, Tufanganj, Cooch Behar.
City Tufanganj
State West Bengal
Document Fees Ref. Document
EMD INR 50741.0 /-
Tender Value 25.37 Lakh
Tender Type Tender
Bidding Type Open Tender
Tender Category Works
Competition Type Indian
Exemption No
Tender Details

Tender for Establishment Of Electrical Installation Work For Fire Pump & X-Ray Machine At Tufanganj Sd Hospital, Tufanganj, Cooch Behar.

Key Dates
Publish Date 27-05-2026
Last Date of Bid Submission 17-06-2026
Tender Opening Date 19-06-2026
Contact Information
Company Name Public Works Department
Contact Person Executive Engineer Cooch Behar Electrical Division
Address Executive Engineer Cooch Behar Electrical Division Sunity Road, Circuit House Campus
Pincode 736121
Other Detail
BOQ Items
Name of Work:- Establishment of Electrical Installation work for Fire Pump & X-ray Machine at Tufanganj SD Hospital, Tufanganj, Cooch Behar.
Sl. No. Item Description
1SUB HEAD 1 :- VTPNDB, TPNDB
2Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make: Legrand/ ABB/ SIEMENS/ Schneider / L&T]
38 way- Up to 160A
4Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment
58 Way
6Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealedin wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make: Legrand/ ABB/ SIEMENS/ Schneider / L&T]
78 Way
8Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment
98 Way
10Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make: Legrand/ ABB/ SIEMENS/ Schneider / L&T]
112+12 Way
12Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection [Make: Legrand/ ABB/ SIEMENS/ Schneider / L&T]
13160 A-FP
1480 A-FP
15Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection [Make: Legrand/ ABB/ SIEMENS/ Schneider / L&T]
1663A TP
176-32A SP
18Supplying and fixing MCCB SS enclosure with IP- 20/30 protection, pwder coated provision for housing Four pole (4P) MCCB, concealed in wall after cutting the wall & mending good the damages to original finish / on flat iron frame incl. painting, connection & provision for earthing attachment
19SUB HEAD 2 :- Distribution Wiring
20Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required
214x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
222x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
23Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works
2425mm size
2520mm size
26SUB HEAD 3 :- Timer DB
27S&F of 250V, 25A timer controlled single starter for controlling Single Air Conditioning Machines in SS double door 2+10 way DB enclosure (L&T / ABB / Legrand make) with S&F following electrical accessories & front door locking arrangement with all connections by finishing the ends of 2 x 4 & 1 x 2.5 mm2 copper wire with dowells solderless socket by crimping method as to GS, earthing attachment on wall incl. necessary connections as per direction of EIC : -
2825A DP MCB (L&T / ABB / Legrand make) – 1 no.
2924Hr x 7 days programmable Digital timer (L&T make Cat no 67DDTO) – 1 no.
303-pole power contactor (L&T make Cat no MNX22 / 250V) – 1 no.
312-Modular AC motor starter (Legrand / Myrius Cat no 673031) – 1 no.
321-Module 10A Modular switch (Make Legrand / Myrius) – 1 no.
333-module plate with cover (Make Legrand / Myrius) – 1 no.
3425A Auto-Off-Bipass SPDT toggle switch (approved reputed make) – 1 no.
35LED indication lamp (approved reputed make) – 1 no.
36Outgoing bakelite connector 32A (Reputed make as approved by EIC) – 2 nos.
37SUB HEAD 4 :- SITC of Sub LT Panel
38Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of the panel has to approved by EIC before making of panel.
39Construction Details :
40All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side.
41Incoming Arrangement :
42a) 415V, 400 Amps Four Pole MCCB of Breaking capacity 50 kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (Make: L&T / Legrand / Schenider /ABB/ Siemens)---- 1 No.
43Bus bar section :
44415 V, 600 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification- 1 set.
45The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
46Outgoing Arrangement :
47a) 415V, 200 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 2 No.
48b) 415V, 125 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 4 No.
49c) E.I. Danger Board of suitable size ------- 1 no.
50Metering Panel:-
51a) Digital multifunction meter with selector push button switch (up/down) with Voltage, Current, Frequency, Total Harmonic Distortion, PF, KW, KVA, Kwh, KVAh and Preloaded Max & Min Demand with Date & Time Stamping display (Make-Schneider Electric/ Cat No- EM6400NG Class accuracy CIo.5S, POP of Accuracy Class 0.5S or equivalent model of Legrand/ Siemens/ L&T) - 1 No.
52b) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Siemens cat.no 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent cat of L&T/ABB/ SCHNEIDER) - 1 No.
53c) 500/5 Amp ratio C.T (Kappa or equivalent) --- 3 nos.
54d)S & F 2 Amp SPMCB for auxiliary supply to meters (Make- SIEMENS/L&T/Legrand) - 1 no.
55Interconnection :-
56All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pvc insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
57Earthing Arrangement :-
58A separate continuous aluminum earth busbar of appropriate size is to be painted at the inside bottom of the panel and run across the full load of the panel board. All electrical equipment are to be properly earthed with suitable size G.I. strip.
59The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
60Installation :-
61The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C.
62SUB HEAD 1 :- Panel for X-Ray & Fire Pump
63Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of the panel has to approved by EIC before making of panel.
64Construction Details :
65All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side.
66Incoming Arrangement :
67a) 415V, 250 Amps Four Pole MCCB of Breaking capacity 50 kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (Make: L&T / Legrand / Schenider /ABB/ Siemens)---- 1 No.
68Bus bar section :
69415 V, 315 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification- 1 set.
70The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
71Outgoing Arrangement :
72a) 415V, 160 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 2 No.
73b) 415V, 125 Amps Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing enclosure and necessary connection (open execution type) (Make: L&T/Legrand/Schenider/ABB/ Siemens)---- 2 No.
74c) E.I. Danger Board of suitable size ------- 1 no.
75Metering Panel:-
76a) Digital multifunction meter with selector push button switch (up/down) with Voltage, Current, Frequency, Total Harmonic Distortion, PF, KW, KVA, Kwh, KVAh and Preloaded Max & Min Demand with Date & Time Stamping display (Make-Schneider Electric/ Cat No- EM6400NG Class accuracy CIo.5S, POP of Accuracy Class 0.5S or equivalent model of Legrand/ Siemens/ L&T) - 1 No.
77b) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Siemens cat.no 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent cat of L&T/ABB/ SCHNEIDER) - 1 No.
78c) 500/5 Amp ratio C.T (Kappa or equivalent) --- 3 nos.
79d)S & F 2 Amp SPMCB for auxiliary supply to meters (Make- SIEMENS/L&T/Legrand) - 1 no.
80Interconnection :-
81All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pvc insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
82Earthing Arrangement :-
83A separate continuous aluminum earth busbar of appropriate size is to be painted at the inside bottom of the panel and run across the full load of the panel board. All electrical equipment are to be properly earthed with suitable size G.I. strip.
84The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
85Installation :-
86The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C.
87SUB HEAD 5 :- Installation of Panels
88Supply & Fabrication of MS structure with 40X40X5 mm MS Angle, 50X50X5 mm MS flat, 75x75x5 mm C Section Channel, 10X10 mm MS Square bar including fixing the same and mending all the damages as per direction of EIC.
89Supply & fixing of 860 mm wide & 8 mm thick MS Chequered Plate incl. providing handle flexible type in both end including drilling hole in the plate & fixing of the same in the ms structure by proper cutting for covering of the trench.
90Painting with best quality synthetic enamel paint of approved make and brand including smoothening surface by sand papering etc. Including using of approved putty etc. on the surface, if necessary : [For colouring of above chequered plate & MS structure]
91(b) On steel or other metal surface :With other than hi-gloss of approved quality-iv) Two coats (with any shade except white)
92Dismantling all types of plain cement concrete works, stacking serviceable materials at site and removing rubbish as directed within a lead of 75 m. In ground floor including roof. upto 150 mm. thick
93Removal of rubbish,earth etc. from the working site and disposal of the same beyond the compound, in conformity with the Municipal / Corporation Rules for such disposal, loading into truck and cleaning the site in all respect as per direction of Engineer in charge.
94Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes. (b) River bazree
95Ordinary Cement concrete (mix 1:1.5:3) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement if any, in ground floor as per relevant IS codes. (ii ) River Bazree
96Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface]With 1:4 cement mortar (b) 15 mm thick plaster
97Neat cement punning about 1.5mm thick in wall, dado, window sill, floor etc. NOTE:Cement 0.152 cu.m per100 sq.m.
98Hire and labour charges for shuttering with centering and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beams and columns, lintels curved or straight including fitting, fixing and striking out after completion of works (upto roof of ground floor) (c) Steel shuttering or 9 to 12 mm thick approved quality ply board shuttering in any concrete work
99Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. (a) For works in foundation and upto roof of ground floor/upto 4 m (i) Tor steel/Mild SteelII. JSW/JSPL/SHYAM/SRMB/BMASL/ELECROSTEEL/SSLQUANTITY SAME AS 1.00% of item Sl no-13 7.85MT/m3
100Brick work with 1st class bricks in cement mortar (1:4)a) In foundation and plinth
101SUB HEAD 6 :- Earthing Installation
102Excavation of soil for installation of Earth Electrode and filling & ramming. (for soft Soil)
103Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:
104By ISI-Medium GI pipe
105Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.
106Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S.
107Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
108Insulating the 65x8 mm MS flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar)
109Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc.
110SUB HEAD 9 : Cable, Cable Laying, Gland & Socket
111Supplying and delivery of following size Armoured cablesXLPE/PVC insulated are designed for 1.1 kV StrandedAluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.) [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C]
1124 Core 185 Sqmm
1134 Core 95 Sqmm
114Laying of one No. cable in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed
115Laying of cable above 3½/4 core cable on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting
116Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
1174 core185 Sqmm
1184 Core 95 Sqmm
119Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :
1204 core 185 Sqmm
1214 Core 95 Sqmm
122Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.
123With 25x25x3mm angle iron support
124200x50x1.25mm (18SWG)
125300x50x1.25mm (18SWG)
126SUB HEAD 10 : Miscellaneous
127Supplying, laying, fiting, fixing of UPVC pipes conforming to IS:4985-2000 with latest revision and amendments, including labour charges for earth work in excavation in any kind of soil including mixed soil with boulder ,road sub-grade and its flanks but excluding moorum and laterite or sand stonehard arock including cutting of brick payment without damaging the existing telephone/electrical cable line etc.(in case of damage of any type of cable line during excavation, necessary damaged charges as applicable by the respaective authority will be borne by the agency in his own cost. Loading, unloading, carrying of pipes, specials, valves from the local store to work site and lowering laying of pipes specials valves carefully in trenches maintaining proper levels and alignment ,including back filling the trenches with good earth obtained from excavation of trenches including consolidation with watering in layer not exceeding 150mm thk. with maintaining an average depth of 1.10 Mtr
128(A) Pressure Rating : Class - III (6 Kg/cm2)(i) Laying of pipe line including cost of pipe only. [Make- Supreme]
129Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees. Please Enable Macros to View BoQ information
View Original Notice/Document
Download FileName File Description
Download 14e52dd2-03de-4722-9e0b-22654fcfe364.html Tender Documents
Download BOQ_5082766.xls Tender Documents
Download Tendernotice_1 (11).pdf Tender Documents
Download Tendernotice_2 (2).pdf Tender Documents